9
Application Information
1) Installation Clearances
Refer diagram below for the space required around the unit. Note that:
a) All dimensions shown are in mm.
b) All space values shown are minimum clearance required for the unit.
c) Unit shown in the diagram is A5RT210/240C. Other models shall follow the same clearance.
3000
1200
1200
Evaporator coil & motor
service, Air filter service
1200
Condenser
air inlet
Evaporator coil,
air filter service
Condenser
air inlet
Condenser
air inlet
Condenser
air outlet
Condenser
air inlet
Electrical
control circuit
service &
compressor
service
Model : A5RT120/150/180/210/240/300C
Model : A5RT60/90C
Evaporator coil &
Air filter service
1200
1200
1200
3000
Condenser
air inlet
Evaporator coil, motor
& Air filter service
Electrical control circuit service &
compressor service
Condenser
air inlet
Condenser
air inlet
Condenser
air outlet
2) Cable Size
Model
Power Cable
(mm
2
)
Breaker Capacity
(A)
Over Current
Protection Switch (A)
Earth Cable
(mm
2
)
A5RT60C
2.5
20
20
2.5
A5RT90C
4
32
32
4
A5RT120C
6
32
32
6
A5RT150C
10
40
40
10
A5RT180C
10
50
50
10
A5RT210C
16
63
63
16
A5RT240C
16
63
63
16
A5RT300C
25
80
80
25
Note:
- A main switch or other means for disconnection, having a contact separation in all poles, must be
incorporated in fi xed wiring in accordance with local and national legislation.
- The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or
HRC fuse.
- Fix the power supply to control module. Connect control wiring to control terminal block through the control
box’s hole.
- Earth wiring must be connected.
- The power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used
in protective tube.