INSTALLATION OF THE INDOOR UNIT

The indoor unit must be installed such that there is 
no short circuit of the cool discharge. Respect the 
installation clearance.
Do not put the indoor unit where there is direct 
sunlight on unit. The location is suitable for piping 
and drainage and it must have a large distance 
between a door and unit.

In cases where the temperature above the ceiling 
might reach 30°C or the humidity RH80%, reinforce 
the drain pan insulation (10mm or thicker) or adding 
secondary Drain Pan. Condensation may form on 
the surface of the insulating material.

Provide clearance for servicing ease and optimal air 

fl

 ow as shown in the diagram.

Ceiling Concealed Mounting

•  Use the hanger supplied with the unit.
•  Make sure that the ceiling is suf

fi

 ciently strong to 

withstand the weight.

300mm* or more

300mm 

or more

10mm 

Floor

2300mm or more

Ceiling

 

* Can be smaller than 300mm if ceiling is removable.

Field supply

Washer for hanger bracket 
(attached)

Tighten

Detail A

 

CAUTION

Do not install the unit at altitude over 2000m for both indoor and outdoor.

Ceiling Concealed Drain Piping Work

DRAIN PIPE
The suggested slope of the 
drain pipe is at least 1:50

Insulate securely

10mm (0.39")

•  The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by 

leaks and condensation. 

•  For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the 

fl

 ow.

•  Ensure the drain pipe is securely insulated.
•  Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
•  Conduct a water drainage test after the installation is completed. Make sure that the drainage 

fl

 ow is smooth.

•  In humid environments, use an extra drain pan to cover the entire area of the indoor unit.

Insulation material
(field supply)

Aluminium tape 
(field supply)

Air outlet side

Air inlet side

See Detail A

Aluminium tape 
(field supply)

IM-CCFWD-0117(1)L-ACSON.indb   3

IM-CCFWD-0117(1)L-ACSON.indb   3

5/31/2017   10:14:55 AM

5/31/2017   10:14:55 AM

Содержание 06FWD

Страница 1: ...MANUAL CEILING CONCEALED CHILLED WATER FAN COIL UNIT F SERIES IM CCFWD 0117 1 L ACSON Part No R08019046054A IM CCFWD 0117 1 L ACSON indb i IM CCFWD 0117 1 L ACSON indb i 5 31 2017 10 14 55 AM 5 31 201...

Страница 2: ...IM CCFWD 0117 1 L ACSON indb ii IM CCFWD 0117 1 L ACSON indb ii 5 31 2017 10 14 55 AM 5 31 2017 10 14 55 AM...

Страница 3: ...dimensions are in mm KE KD KC KB KA 31 321 183 48 31 140 32 552 11 186 87 71 31 247 20 20 129 143 Dimension Model KA KB KC KD KE 06 09FWD 619 477 437 440 501 12 15FWD 870 726 687 690 751 18FWD 1060 9...

Страница 4: ...e Ensure that the unit s panel is closed after service or installation Unsecured panels will cause the unit to operate noisily Sharp edges and coil surfaces are potential locations which may cause inj...

Страница 5: ...movable Field supply Washer for hanger bracket attached Tighten Detail A CAUTION Do not install the unit at altitude over 2000m for both indoor and outdoor Ceiling Concealed Drain Piping Work DRAIN PI...

Страница 6: ...ypes of piping and connection must be insulated with closed cell polyurethane to avoid condensation Do not use contaminated or damaged pipe and fitting for installation Some main fitting components ar...

Страница 7: ...type of installation and size of conductors The appropriate voltage range should be checked with label data on the unit A main switch or other means for disconnection having a contact separation in al...

Страница 8: ...pressure 16 bar Air temperature as below Cooling Mode Temperature Ts C F Th C F Minimum indoor temperature 19 0 66 2 14 0 57 2 Maximum indoor temperature 32 0 89 6 23 0 73 4 Ts Dry bulb temperature T...

Страница 9: ...2nd air filter with 1st air filter hook Push the air filter to the end of air filter rail Put back the side air filter cover Figure 2 Install air filter from bottom Figure 4 Insert the 1st air filter...

Страница 10: ...f the air conditioner unit is noted immediately switch off the power supply to the unit Check the following fault conditions and causes for some simple troubleshooting tips Fault Causes Action 1 The a...

Страница 11: ...IM CCFWD 0117 1 L ACSON indb 9 IM CCFWD 0117 1 L ACSON indb 9 5 31 2017 10 14 56 AM 5 31 2017 10 14 56 AM...

Страница 12: ...without prior notification All images are for illustration purposes only Lot 60334 Persiaran Bukit Rahman Putra 3 Taman Perindustrian Bukit Rahman Putra 47000 Sungai Buloh Selangor Darul Ehsan Malaysi...

Отзывы: