- 3 -
(3)After the leakage function (L) is selected, each protector is equipped with a leakage transformer.
The dimensions of the leakage transformer are shown in the section "overall dimensions and
installation". Leakage transformer is equipped with 2m
±
10cm secondary line as standard. If
you need other length, please contact the manufacturer.
4 Main parameters
4.1
Technical indicators
ARD2M technical indicators are shown in Table 3:
Table 3
Technical parameters
Technical indicators
Protector
auxiliary
power supply
AC85-265V/DC100-350V
Rated working voltage
of the motor
AC220V / 380V
,
50Hz / 60Hz
Rated operation current
of the motor
1 (0.1A-5000A)
Integrated/Split current transformer
5 (0.1A-5000A)
25(6.3A-25A)
100(25A-100A)
250(63A-250A)
Split current transformer
800(250A-800A)
Relay output contact
capacity
Impedance load
AC250V
、
10A
Switching input
8 channels of passive dry contact (active DC110V, DC220V, AC220V
input can be optional)
Communication
RS485 Modbus_RTU,Profibus_DP
Environment
Working temperature
-10ºC
~
55ºC
Storage temperature
-25ºC
~
70ºC
Relative temperature
≤95
﹪
No condensation, no corrosive
gas
Altitude
≤2000m
Pollution levels
3 level
Protection grade
IP65(installed on the cabinet panel)
Installation category
III
级
4.2 Functional configuration
ARD2M Functional configuration shown in Table 4:
Table 4
Type
Function
Functional configuration
Standard
function
Optional function
Protection
function
Fixed time overload
√
Inverse time overload
√