PuliMATIC - ENGLISH
MAN141 PAGE E-12
EV (Solenoid 1): voltage-free contact for managing auxiliary equipment served by the filter
(e.g. solenoid valves, pumps, alarms, etc.). This voltage-free contact can support a
maximum load of 5A at 24V AC/DC.
Caution!
Since this is a voltage-free contact, this
cable cannot be directly connected to electrical loads;
Caution!
In the event of an alarm, this contact is enabled
EV2 (Solenoid 2): Voltage-free contact for managing auxiliary equipment served by the filter
(e.g. solenoid valves, pumps, alarms, etc.). This voltage-free contact can support a
maximum load of 5A at 24V AC/DC.
Caution!
Since this is a voltage-free contact, this
cable cannot be directly connected to electrical loads;
DIFF: Input for managing the pressure differential switch.
Caution!
Since this is a voltage-
free contact, this cable cannot be directly connected to electrical loads;
Note: The filter washing will start 5 seconds after the signal from the pressure differential
switch is received;
ALIM: input for filter power supply with the supplied device already connected
The diagram shows the logical
functioning of the connections
between the PuliMATIC filter, the
control panel and 24 Vac devices.
A
: 230 Vac/50 Hz power supply;
B
: PuliMATIC power transformer;
C, D
: Fuse;
E
: Control panel transformer;
F
: 24 Vac devices served by the control
panel.