background image

 

 

 

                                Fire Alarm Panels 

 

 

 

User Manual 

 

 

 

The operation and functions described in this manual are available from Software Version 5000-050-04 onwards. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Mx-5100

Страница 1: ...Fire Alarm Panels User Manual The operation and functions described in this manual are available from Software Version 5000 050 04 onwards www acornfiresecurity com www acornfiresecurity com ...

Страница 2: ...2 This page is intentionally blank www acornfiresecurity com www acornfiresecurity com ...

Страница 3: ...LEMENT CONDITION 15 3 4 1 Disabled Inputs 15 3 4 2 Disabled Outputs 16 3 5 ALARM CONDITION 16 3 6 SUPERVISORY CONDITION 17 3 7 MULTIPLE CONDITIONS 17 3 8 MENU FUNCTIONS 17 3 8 1 Using the Buttons to Navigate Menus 19 3 8 1 1 Selecting Menu Options 19 3 8 1 2 Selecting Individual Zone Numbers 19 3 9 VIEWING 20 3 9 1 View Fires 20 3 9 2 View Faults 20 3 9 3 View Alarms 20 3 9 4 View Disabled 20 3 9 ...

Страница 4: ...30 3 12 DELAYS 31 3 12 1 Turn Off Delay Mode 31 3 12 2 Turn On Delay Mode 31 3 12 2 1 Extend Delays 32 3 12 2 2 Holiday Inhibit 32 3 13 TESTING 33 3 13 1 Test Zones 33 3 13 2 Test Display 34 3 13 3 Test Buzzer 34 3 13 4 Test Printer 35 3 13 5 Test Outputs 35 3 14 TOOLS 36 3 14 1 Printing 36 3 14 1 1 Printer Communications Settings 36 3 14 1 2 Set up Printer 36 3 14 1 3 Print Inputs 37 3 14 1 4 Pri...

Страница 5: ...puts Dependency on more than one alarm signal Fault Signals from Points Disablement of Points Alarm Counter Test Condition Standardised Input Output EN54 4 1997 A1 2002 A2 2006 Power supply equipment for fire detection and fire alarm systems for buildings Mx 5100 Mx 5200 Mx 5400 MX 5800 Mx 5100V Mx 5200V Mx 5400V MX 5800V Mx 5100N Mx 5200N Mx 5400N MX 5800N In addition the products comply with the...

Страница 6: ...Commissioning Manual Document No 680 165 for details of how to install and program the panel All panel models are available in a range of enclosure sizes and with a range of alternative optional features 1 3 1 5000 Series The 5100 is a Single Loop Analogue Addressable Fire Alarm Control Panel The 5200 is a Two Loop Analogue Addressable Fire Alarm Control Panel The 5400 is a Multiple Loop Analogue ...

Страница 7: ...LE FAULT FIRE ROUTING ACTIVATED FIRE ROUTING FAULT FIRE ROUTING DISABLED PRE ALARM SOUNDER SILENCED SOUNDER FAULT Graphical Liquid Crystal Display Navigation Keys Zone LED Indicators Optional Number Keys Control Keys General Status Indicators Slide in labels are used to annotate Function Indicators and Programmable Control Keys and Indicators 2 1 Graphical Display The graphical display provides de...

Страница 8: ... Indicates that the circuit to fire extinguishing or other fire protection equipment has been activated or that the fire protection equipment itself has been activated Sounder Silenced Yellow Indicates that the sounders have been silenced Sounder Fault Yellow Indicates the presence of a fault in one or more sounder wiring circuits Sounder Disabled Yellow Indicates that one or more sounders have be...

Страница 9: ...el 2 Access Resound Press to re activate the sounders Only available with Level 2 Access Evacuate Press to initiate a manual evacuation and sound the alarms Only available with Level 2 Access LED Test Press to illuminate ALL LED indicators Available in both Level 1 and Level 2 Disable Press to disable the zone or device in a fire alarm condition Australia only Only available with Level 2 Access Fu...

Страница 10: ... Maintenance Engineer Special Tools required A Level 1 Untrained User can view the current operational condition of the system and may MUTE the internal buzzer NOTE Depending on the configuration settings a Level 1 user may also be permitted to EVACUATE and or SILENCE and or RESET the system by pressing the appropriate button and entering a password A Level 2 Authorised User can view the operation...

Страница 11: ...umber is entered an asterisk is shown on the display For example CONTROLS DISABLED Please Enter Your Password If the password is correct the Level 2 Menu options will be shown If the password is incorrect the display briefly shows the following message CONTROLS DISABLED Please Enter Your Password Password Not Recognised 3 1 1 2 Control Buttons at Level 1 If any of the control buttons Reset Silence...

Страница 12: ...ocation Text for First Zone Location Text and Type of Device 2 Zones in Fire Last Zone 0005 BASEMENT EAST No of Zones in Fire Last Zone Zone Description for Last Zone Press the MUTE button to silence the internal buzzer the FIRE LED will change from flashing to steady illumination Press the MORE ALARMS button to view an scroll through a full list of zones in a fire alarm condition When the panel i...

Страница 13: ... Delays The Investigation Delay Function can be disabled or enabled as required by EN54 2 Refer to Section 3 12 If the Investigation Delay Function Stage 1 Stage 2 Investigation Delay is enabled a fire alarm is registered at the panel but does not immediately activate the sounders On registering the alarm the display shows FIRE STARTED IN ZONE 1 12 Header Zone Device BASEMENT WEST KITCHEN TEMPERAT...

Страница 14: ...s the current time and date and service centre telephone number along with the indication of the fault FOR SERVICE CALL 01234 567890 LEVEL 2 16 05 04 MAR 2008 Panel access level Service Call Number and Time Date 1 Zone In Fault More No of Zones in FAULT To obtain more detailed information about the faults press the button The display then presents a list of all of the zones in a fault condition wi...

Страница 15: ...d then press the button to view further information 3 4 1 Disabled Inputs The display presents a list of all of the zones in a disabled condition with the first disablement highlighted For example 2 Zones with Inputs Disabled More ZONE MODE LOCATION 0001 PART DISABLED BASEMENT WEST 0002 ALL DISABLED BASEMENT EAST Zone disablement condition and location text The display shows the status as ALL DISA...

Страница 16: ...nformation including type value and state etc Outputs in Zone 0100 More Mode Type Disabled SOUNDER Disabled SOUNDER Disabled SOUNDER Disabled SOUNDER Press the buttons to scroll through the list of individual outputs within the selected zone Press the Esc button to return to previous views and the main display 3 5 Alarm Condition When the system registers a pre alarm or plant alarm condition the i...

Страница 17: ...condition to occur however is shown at the top of the display An example of the display is shown below ZONE 0011 SUPERVISORY PLANT ROOM SPRINKLER SHUT OFF INPUT MON Location Text for First Zone Location Text and Type of Device 1 Zone In Alarm More 1 Zone In Supervisory More 1 Zone In Fault More No of Zones in Supervisory An arrow is shown on the display to indicate the scroll options first row las...

Страница 18: ...ed disablement group ENABLE Zone Inputs Enable a complete zone or an individual input Outputs Enable sounder outputs or other devices Groups Enable a user defined disablement group Remote Permits remote access controls TEST Zones 2 Configure one or more zones for walk test Display Test the Graphics Display Status Indicators and Keyboard Buzzer Test the Internal Buzzer Printer Test the connection t...

Страница 19: ... to the normal operating display Press the Menu button to return directly to the Level 2 Menu display previously shown 3 8 1 2 Selecting Individual Zone Numbers When the display is showing a list of Zone Numbers it is possible to select a specific zone number by using the number keys For example if the display is showing a list of zones Inputs More Zone Mode Location 0001 Enabled BASEMENT WEST 000...

Страница 20: ...y in a Fault condition The operation of the panel and the information that can be shown is identical to the views available from the main operating display Refer to Section 3 3 for further information 3 9 3 View Alarms This function shows the Zones and Inputs that are currently in an Alarm condition These may occur if The Zone or Input is currently in a Fire Test condition and or Inputs that are c...

Страница 21: ...ional condition for all Outputs Outputs More Zone Location 0002 Reception 0003 Ground Floor 0013 First Floor Corridor 0014 First Floor Press the buttons to highlight the required zone and then press the button to view the individual outputs For example Outputs in Zone 0003 More Mld Mode Device text Enabled Kitchen Disabled Reception Press the button to view further information on each point for ex...

Страница 22: ... optional interface cards 3 9 7 1 Software Software PANEL DISPLAY LOOP CARDS NETWORK PSU PERIPHERAL PRINTER Panel Software Software PROGRAM ID MX5000 050 04 CHECKSUM 92879016 Other Software Select the other options and the display shows the software version incorporated into these circuit cards functions and the hardware build variant A number of peripheral modules may be installed up to 32 press ...

Страница 23: ...l Earth Volts 0V 30V 2 5V 14 5V 6 Normal Too High Too Low System Volts 19V 30V 28 0V Normal Aux Load 0mA 500mA 5 Normal Too High 1 st Loop Load 7 0mA 500mA 5 Normal Open Circuit Too High Short Circuit 1 st Loop V Out 7 24V 32V 5 Normal 1 st Loop V In 7 24V 32V 5 Normal Panel Switch Inputs 1 9 L H L Normal Programmable inputs Normal L H L Normal Relay 1 Normal Relay 2 Normal Relay 3 8 Normal Relay ...

Страница 24: ... buttons to highlight the required menu option and then press the button to select it The display then shows the appropriate list of events 3 9 8 1 Event Log The display will always show the most recent event to have occurred e g View Fire Events Entry 0076 Time Date Node Lp Addr Zone 10 54 23 1 1 001 0 001 14 03 06 FIRE ALARM 64 BASEMENT ROOM 10 Number of Highlighted Event Time Origin and Zone Da...

Страница 25: ...0 502 Pressing 0 allows the stored network status information to be cleared 3 9 10 View Warnings This Option can be used to obtain information about warning conditions on the panel A warning condition is created whenever a detector device reaches its limit drift of compensation This does not affect the performance or operation of the panel in detecting and responding to fire alarm conditions from ...

Страница 26: ...scroll through the available zones or key in a specific zone number To disable the entire zone move over to the Mode column and highlight the existing mode Press the button and a pop up window appears showing the possible options ALL INPUTS SELECTED INPUTS ONLY AUTOMATIC DETECTORS ONLY MANUAL DEVICES ALL OTHER DEVICES Press the buttons to scroll through and highlight the required option and then p...

Страница 27: ...UTS FIRE PROTECTION OUTPUTS FAULT ROUTING OUTPUTS ALL OTHER RELAY OUTPUTS ONLY SELECTED OUTPUTS PAGERS 3 10 2 1 All Sounder Outputs Press the buttons to scroll through and highlight the ALL SOUNDERS Option and then press the button to disable them The display automatically reverts to the Main Disable Menu The Sounder Disabled Indicator will be illuminated 3 10 2 2 All Beacon Outputs Press the butt...

Страница 28: ...sable Menu 3 10 2 9 Only Selected Outputs Allows selection of a single output 3 10 3 Disable Controls Disabling Controls will cancel Level 2 access and return the panel to Level 1 operation If the panel has an access key switch fitted use the key switch in preference to the menu option shown below Disable User 1 Node 1 ZONE INPUTS OUTPUTS GROUPS CONTROLS USER ID Press the buttons to highlight the ...

Страница 29: ... Disablement Groups are a means of disabling enabling custom groups of devices The commands are command across the network of panels and can be invoked from any panel The installer will have configured these groups If no groups exist selection of this option will show a NOT CONFIGURED message Some typical examples are Stage Smoke Detectors Floor 2 Sounders ALL Sounders The display will show for ex...

Страница 30: ...abled The individual outputs within the zone can then be enabled The display format is virtually identical to the equivalent Disable Menu 3 11 3 Enable Groups This option allows the re enabling of User defined Disablement Groups The display is identical to the disable option 3 11 4 Enable Remote Information on the detectors connected to the panel and on the condition of all zones can be obtained w...

Страница 31: ...tion delays in operation If the investigation delays are in operation then the Delayed LED Indicator is illuminated When the investigation delays are turned off the Delayed LED Indicator is turned off Press Esc to cancel and make no change to the current operational setting 3 12 2 Turn On Delay Mode This option allows the operation of Investigation Delays and other related functions The Investigat...

Страница 32: ...holiday periods On selection the display shows Inhibit Delay End Date TIME 15 49 DATE 02 07 08 WED 02 JUL 2008 Press the buttons to select the time date fields Enter the required time and date using the number buttons Any pre configured automatic delays or manual delays will be immediately suspended and the panel will operate without any investigation delays On reaching the time date programmed th...

Страница 33: ...issioning to define which of the sounders are activated during a test The display then shows a list of the available Zones and their current test status For example 0 Zones in Test Zone Test State Location 0001 BASEMENT WEST 0002 BASEMENT EAST 0100 MAIN RECEPTION Press the buttons to scroll through and highlight the required zone and then press the button to change the Test State For example 1 Zon...

Страница 34: ...D TEST option will cancel all zone tests The Test LED will then extinguish Alternatively it is possible to leave the Zone Test Function with one or more Zones still in Test by selecting the KEEP ZONES IN TEST option This will enable the inspection or use of other menu functions and return the display to the normal operating mode The Test LED will stay illuminated if this option is selected 3 13 2 ...

Страница 35: ...OOM 0100 MAIN RECEPTION Press the buttons to scroll and highlight the required zone or key in the required zone number and then press the button to show the output devices in that zone For example Outputs in Zone 37 More Mode Device Text Enabled Room 151 Enabled Room 152 Press the buttons to scroll and highlight the required output and then press the button to test the output The display will prom...

Страница 36: ...n to confirm If the current User ID does not have the necessary permission the display prompts for entry of a password to guard against inadvertent changes Enter the password as normal The display then shows a pop up window giving programming options as follows FIRES ALARMS FAULTS TESTS Printer Internal External Wide The upper line of options determines whether the panel shall automatically print ...

Страница 37: ...n printed includes Device Text Zone Number Loop and address current status and analogue value 3 14 1 4 Print Outputs To print information on any output highlight the Outputs option and press the button to confirm The display will show the following Outputs First Zone 98 Last Zone 98 Press to Start Print The display will prompt the zones in use on this panel For networked systems it is possible to ...

Страница 38: ...e number keys to change the zone number as required Press the key to start printing The printout will show the location and state of all input and output points in a disabled condition for the zones selected The display always present the zones with inputs disabled first if any exist After printing the inputs the display will present the information on disabled outputs if any exist Note If there a...

Страница 39: ...009 To change the settings use the buttons to highlight the required option Directly enter the new time or date using the number buttons As soon as a number button is pressed the display will clear the current setting and show the new value as it is entered For example SET TIME DATE TIME 1 DATE 05 01 09 MON 5 JAN 2009 If this panel is connected to a network ALL panels on the network will assume th...

Страница 40: ...40 This page is intentionally blank www acornfiresecurity com www acornfiresecurity com ...

Страница 41: ...41 This page is intentionally blank www acornfiresecurity com www acornfiresecurity com ...

Страница 42: ...42 USER NOTES www acornfiresecurity com www acornfiresecurity com ...

Страница 43: ...www advancedco com www acornfiresecurity com www acornfiresecurity com ...

Отзывы: