OPERATION INSTRUCTIONS:

become familiar with the location and operation of the 
nearest emergency plumbing fixture. Emergency 
plumbing fixtures stations are simple to use and require 
hands free operation once the station is activated. 
Regular instruction regarding proper care and use will 
increase confidence that the units are accessible and 
function properly.
The route and area surrounding the Eye Wash should 
be clear and unobstructed; the sooner eyes are flushed, 
the less likelihood of damage. Eye Wash stations should 
be located in close proximity to the hazard and take no 
more than 10 seconds to reach. In the case of sever eye 
contamination the victim may require assistance to the 
Eye Wash station and help flushing their eyes.
Safety plumbing fixture equipment should be operated 
weekly for a period long enough to verify operation, 
clear the supply line of any sediment build-up and 
minimize microbial contamination due to sitting water.
1. To start the Eye Wash, swing spray nozzle assembly 

down horizontally over the basin or fully “ON” position. 
Flushing should start, popping the spray nozzle caps 
open.

2. Lower both eyes into flow. Both eyes should be 

flushed to prevent contamination from one eye from 
being delivered to unaffected eye. Personnel who 
wear contact lenses should remove them immediately 
prior to or during the flush to prevent the 
contamination from remaining against the cornea 
possibly causing unnecessary damage or pain.

3. Using thumb and forefingers, fully open eyelids and 

flush eyes thoroughly for approximately 15 minutes or 
until medical personnel arrive. Be prepared to let the 
doctor know what type of contamination has entered 
the eye. 

4. When finished swing spray nozzle assembly up  or 

fully “OFF” position. Flushing fluid should stop. Once 
flushing fluid has stopped flowing, return spray nozzle 
lids to the closed position to protect from airborne 
contaminates.

MAINTENANCE GUIDE:

Maintain and inspect in accordance with ANSI Z358.1-
2009
1. Check for obvious signs of wear, broken or defective 

equipment. Re-paint if necessary. Replace missing or 
defective equipment such as broken push paddles, 
missing signs and inspection tags. 

2. Remove strainer and washout any debris collected 

–replace as required.

3. Operate Eye Wash nozzles swinging the spray nozzle 

assembly down to place ball valve in the fully “ON” 
position checking for smooth operation of valve push 
paddle mechanism at the same time ensuring that the 
Eye Wash spray nozzle caps pop off immediately 
when actuated. If the ball valve does not operate 
smoothly check the actuating assembly for binding or 
missing parts. If the 

Employees who work with hazardous materials should 

Eye Wash spray nozzle caps do not pop off immediately 

when actuated check for correct supply inlet 
pressure.

4. While in operation, inspect spray nozzles for clogs or 

debris correct or replace as required.

5. Swing spray nozzle assembly up to fully “OFF” 

position and swing back to stand by position. To 
prevent Eye Wash spray nozzles from becoming 
contaminated, always close nozzle lids after each 
use. 

 