Acorn Safety S0410 Скачать руководство пользователя страница 2

Installation & Operation Manual

  

 

 

 

 

ROUGH-IN

 

 

 

BEFORE INSTALLATION

1. Read the installation instructions prior to beginning the installation.

2. Separate parts from packaging and verify all necessary parts are accounted for and undamaged. Obtain missing or 

damaged parts from Acorn Safety prior to beginning installation. See page 4.

3. Thoroughly rinse unit inside and outside with HOT soapy water (use mild soap & potable water). Ensure that no foreign 

matter or particles are left inside unit especially in the sprayhead ports. Inspect for leaks.

4. In order to comply with ANSI Z358.1, the safety equipment must be inspected periodically. An inspection tag is provided for 

documentation purposes.

5. All employees at risk of eye contamination should be informed and trained in the use of this and any other safety equipment.

GENERAL NOTES:

1. ALL DIMENSIONS ARE IN INCHES

*2. DIMENSIONS SHOWN ARE FOR NORMAL ADULT HEIGHT. ANSI Z358. 1 REQUIRE NOZZLES TO BE

     BETWEEN 33" AND 45" ABOVE THE FLOOR.

35 

3
8

"

1
4

"

OD

TAILPIECE

3
8

"

SUPPLY

* 31 

5
8

"

* 36"

*40 

3
8

"

*42"

* 35 

3
8

"

REF

1"

5
8

"

5
8

"

1
2

" NPT

SUPPLY

4XØ 

3
8

" MTG HOLES

FLOOR LINE

MOUNTING DETAIL

FLOOR LINE

FINISHED

WALL

Revised: 07/23/13

Manual #7109-100-001

 

 

Acorn Safety

 

a division of Acorn Engineering 

Company

Page 2 of 5