Operation
Conditions, restrictions and recommendations
for unit operation (only for unit operation):
n
If the unit has not been actively operating
(no wastewater entering the unit) for more
than two days, it is necessary to flush the unit
with 30 litres of water each subsequent day.
n
Never open the drain ball valve at the bottom
of the separator during normal operation.
This valve can only be opened during
quarterly maintenance.
n
When the heater is plugged in, the unit
must always be completely filled with water,
otherwise the heater may suffer damage
and require replacement.
n
We recomend that the drain downstream
of the separator is cleaned once a year to prevent
a reduction in the flow rate capacity of the unit
and resultant overflows.
n
The heater maintains the internal water temperature
at around 40°C.
n
When the heater is plugged in, the green light
on the heater box must be on. If it doesn´t light green,
see page 17 Daily Maintenance OIM.
Maintenance
Conditions, restrictions and recommendations:
n
The grease separation process loses efficiency
if the unit is not properly maintained.
n
The unit requires daily maintenance
(this takes approximtely five minutes).
Maintenance is the responsibility of the operator.
Weekly maintenance (takes around 10 minutes)
is also undertaken by the operator’s own staff.
Quarterly service (1 hour) shall only be undertaken
by a trained service person, please contact your local
service provider to arrange.
Daily Maintenance
Ins
tallation
Oper
ation
Maint
enance
ACO Grease Capture
Installation and Maintenance Manual
ACO Grease Capture
Installation and Maintenance Manual