5.9 AUXILIARY OUTPUTS
The PP-32 can control up to two auxiliary outputs. They are used as
supplementary outputs for heating or cooling and may be used to control
several devices such as chimney dampers, stir fans, lamps, heat mats, etc.
The user must specify if the auxiliary output operates in heating or in cooling
mode. In heating mode, the output is activated whenever the temperature
decreases below its start temperature. In cooling mode, the output is activated
whenever the temperature increases above the start temperature.
1. In heating mode, the auxiliary output operates below its start temperature:
2. In cooling mode, the auxiliary output operates above its start temperature:
ON
ROOM T°
OFF
AUXILIARY
OUTPUT
STATUS
AUX. OUTPUT
TURNS ON
AUX. OUTPUT
TURNS OFF
AUXILIARY OUTPUTS - IN HEATING MODE
ON
ROOM T°
OFF
AUXILIARY
OUTPUT
STATUS
AUX. OUTPUT
TURNS ON
AUX. OUTPUT
TURNS OFF
AUXILIARY OUTPUTS - IN COOLING MODE