44
S G M 1 4 3 0 - B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l – S M E T S 2
Supply Disconnect and Reconnect
Load Limiting
The SGM1430-B meters support automatic disconnection of supply if the
delivered power from the network to the customer exceeds a predefined average
threshold over a predefined period of time.
When this functionality is enabled, the service will be disconnected for a defined
period of time if the average consumption over the configured period of time
exceeds the configured threshold.
Under/Over Frequency
The SGM1430-B meters support disconnection of service if the supply frequency
goes above an upper limit or below a lower limit.
When this functionality is enabled, the contactor will be disconnected for a
defined period of time if the average frequency over a configured period of time
exceeds either of the configured thresholds.
Sag/Swell (Short Term)
The SGM1430-B meters support disconnection of service if the supply voltage
goes above an upper limit or below a lower limit.
When this functionality is enabled, the contactor will be disconnected for a
defined period of time if the average voltage over a configured period of time
exceeds either of the configured thresholds.
Under/Over Voltage (Long Term)
The SGM1430-B meters support disconnection of service if the supply voltage
goes above an upper limit or below a lower limit for an extended period.
When this functionality is enabled, the contactor will be disconnected for a
defined period of time if the average voltage over a configured period of time
exceeds either of the configured thresholds.
Over Current
The SGM1430-B meters support automatic disconnection of supply if the
measured current exceeds a predefined average threshold over a predefined period
of time.
When this functionality is enabled, the service will be disconnected for a defined
period of time if the average current over the configured period of time exceeds
the configured threshold.
Power Factor
The SGM1430-B meters support automatic disconnection of supply if the
calculated power factor goes below a predefined average threshold over a
predefined period of time.
When this functionality is enabled, the service will be disconnected for a
configured period of time if the average consumption over the configured period
of time is less than the configured threshold.
Содержание SGM1430-B
Страница 1: ...SGM1430 B Smart Meter Polyphase User Manual SMETS2 Y20995 TUM Revision A www Aclara com...
Страница 2: ......
Страница 4: ...ii S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2...
Страница 8: ...vi S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2...
Страница 14: ...2 S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2 Aclara Support...
Страница 20: ...8 S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2 Terminal Arrangements...
Страница 40: ...28 S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2 Power Outages...
Страница 54: ...42 S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2 Billing Data...
Страница 80: ...68 S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2 Prepayment Solution...
Страница 94: ...82 S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2 Disposal...
Страница 98: ...86 S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2 Catalogue Codes...
Страница 110: ...UK SMETS2 98 S G M 1 4 3 0 B S m a r t M e t e r P o l y p h a s e U s e r M a n u a l S M E T S 2...