WIRING INSTRUCTIONS

PRECAUTIONS

Do not run the temperature sensor wiring in 

any conduit with line voltage (24/120/230 

VAC) if utilizing resistance temperature 

signal.

Remove power before wiring. Never 

connect or disconnect wiring with power 

applied.

When using a shielded cable, ground the 

shield only at the controller end. Grouding 

both ends can cause a ground loop.

It is recommended you use an isolated 

UL-listed class 2 transformer when powering 

the unit with 24 VAC. Failure to wire the 

devices with the correct polarity when 

sharing transformers may result in damage 

to any device powered by the shared 

transformer.

If the 24 VDC or 24VAC power is shared with 

devices that have coils such as relays, 

solenoids, or other inductors, each coil must 

have an MOV, DC/AC Transorb, Transient 

Voltage Suppressor (ACI Part: 142583), or 

diode placed across the coil or inductor. The 

cathode, or banded side of the DC Transorb or 

diode, connects to the positive side of the 

power supply. Without these snubbers, coils 

produce very large voltage spikes when 

de-energizing that can cause malfunction or 

destruction of electronic circuits.

RELATIVE HUMIDITY WIRING INSTRUCTIONS

ACI recommends 16 to 26 AWG twisted pair wires 
or shielded cable for all transmitters. Refer to 

FIGURE 4 

(top) or wiring diagrams.

TEMPERATURE WIRING INSTRUCTIONS

ACI recommends 16 to 26 AWG twisted pair wires 
or shielded cable for all temperature sensors. ACI 
recommends a separate cable be pulled for 
Temperature signal only. Temperature Signal 
wiring must be run separate from low and high 
voltage wires (24/120/230VAC). 

All ACI thermistors and RTD temperature sensors are 
both non-polarity and non-position sensitive. All 
thermistor type units are supplied with (2) flying lead 
wires, and all RTD’s are supplied with (2) or (3) flying 
lead wires – see 

FIGURE 6 

(bottom). The number of 

wires needed depends on the application.

FIGURE 4: 

OUTPUT SIGNALS

FIGURE 5: 

PRINTED CIRCUIT BOARD

OPTIONAL TEMP. SENSOR (-)

VOLTAGE OUTPUT SIGNAL

CONNECT TO THE 2 or 3

22 AWG FLYING LEADS

OPTIONAL TEMP. SENSOR (+)

4-20mA

0-10 or 0-5 VDC OUTPUT SIGNAL

SUPPLY GROUND /  SIGNAL COMMON

AC or DC SUPPLY VOLTAGE

TB1

COM

VIN

VOUT

ON

4

2 3

1

5 6 7 8

FACTORY USE ONLY

SW1

J13

J14

J2

4-20mA

VIN

CO
M

V

OUT

TB1

SPAN

WIRE CONNECTIONS

ZERO

P1

J13

Push tab in and pull up on the sensor

cable to remove from J13 connector.

FIGURE 6: 

WIRING

THERMISTOR OR

RTD 2-WIRE

WIRE NUT

RTD 3-WIRE

SAME COLOR WIRES

WIRE NUT

WIRING FROM CONTROLLER

ANALOG INPUT

WIRING FROM CONTROLLER

ANALOG INPUT

3-WIRE RTD WIRING

2-WIRE THERMISTOR or RTD WIRING