background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone: 

1-888-967-5224  |  

Website:

 workaci.com

Page 2

Version: 6.0

I0000647

FIGURE 3:

 SENSOR PROBE/ 

ENCLOSURE REMOVAL

Note:

 The mounting bracket can be removed from 

the shield if needed for easier access. Loosen the 

two Phillip screws holding the probe retaining clip 

until the sensor probe/enclosure is loose enough 

to remove as shown in 

Figure 3

• Finger tighten the assembly around the 

mounting pole. With a level, make sure the solar 
radiation shield is level, and tighten the hex nuts 
with a wrench. 

Surface Mounting

• Loosen the two Phillip screws holding the probe 

retaining clip until the sensor probe/enclosure is 
loose enough to remove as shown in 

Figure 3

• Attach the mounting bracket directly to the wall 

or post(Hardware not included).  

• Slide the sensor probe/enclosure back into the 

shield. Tighten the two Phillip screws holding 
the probe retaining clip until the sensor probe/
enclosure is tight. 

Install the PG11 watertight fitting supplied 

with the sensor if not using conduit. The outer 

knockout ring (PG 11/16) on housing should not 

be removed when using a ½" NPT conduit fitting. 

The 4X enclosure has (4) screws. Confirm gasketed 

cover is fastened securely in order to prevent any 

moisture being introduced into housing. 

Refer to Wiring Instructions) to make necessary 

connections.

WIRING INSTRUCTIONS

PRECAUTIONS
• Remove power before wiring. Never connect 

or disconnect wiring with power applied.

• When using a shielded cable, ground the 

shield only at the controller end. Grounding 
both ends can cause a ground loop.

• Do not run the temperature sensor wiring in 

any conduit with line voltage (24/120/230 
VAC) if utilizing resistance temperature signal.

• It is recommended you use an isolated UL-

listed class 2 transformer when powering the 
unit with 24 VAC. Failure to wire the devices 
with the correct polarity when sharing 
transformers may result in damage to any 
device powered by the shared transformer.

• If the 24 VDC or 24VAC power is shared 

with devices that have coils such as relays, 
solenoids, or other inductors, each coil must 
have an MOV, DC/AC Transorb, Transient 
Voltage  Suppressor (ACI Part: 142583), or 

diode placed across the coil or inductor. The 

cathode, or banded side of the DC Transorb 

or diode, connects to the positive side of the 

power supply. Without these snubbers, coils 

produce very large voltage spikes when de-

energizing that can cause malfunction or 

destruction of electronic circuits.

RELATIVE HUMIDITY WIRING 

INSTRUCTIONS

Open the cover of the enclosure.  ACI recommends 

16 to 26 AWG twisted pair wires or shielded cable 

for all transmitters. Twisted pair may be used for 

2-wire current output transmitters or 3-wire for 

voltage output. Refer to 

FIGURE 4 

(p. 3) or wiring 

diagrams.

TEMPERATURE WIRING INSTRUCTIONS

ACI recommends 16 to 26 AWG twisted pair wires 

or shielded cable for all temperature sensors.
ACI recommends a separate cable be pulled for 

Temperature signal only. Temperature Signal 

wiring must be run separate from low and high 

voltage wires (24/120/230VAC). All ACI thermistors 

and RTD temperature sensors are both non-

polarity and non-position sensitive. 
All thermistor type units are supplied with (2) 

flying lead wires, and all RTD’s are supplied with 

(2) or (3) flying lead wires – see 

FIGURE 6

 (p. 3). 

Содержание SUN SHIELD HUMIDITY Series

Страница 1: ... heating and cooling building management systems All units are shipped from the factory set up for a 4 20 mA output The transmitter can also include an optional temperature sensor for monitoring the space temperature For optimal readings follow these tips Place the shield in an open area to insure unrestricted air flow or wind Keep away from large radiant heat sources such as sun exposed buildings...

Страница 2: ...ng both ends can cause a ground loop Do not run the temperature sensor wiring in any conduit with line voltage 24 120 230 VAC if utilizing resistance temperature signal It is recommended you use an isolated UL listed class 2 transformer when powering the unit with 24 VAC Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by th...

Страница 3: ...53562 Phone 1 888 967 5224 Website workaci com Page 3 Version 6 0 I0000647 FIGURE 4 OUTPUT SIGNALS FIGURE 5 PRINTED CIRCUIT BOARD FIGURE 6 TEMPERATUREWIRING ON 4 2 3 6 PUSH TAB IN AND PULL UP ON THE SENSOR CABLE TO REMOVE FROM J13 CONNECTOR FACTORY USE ONLY 1 5 7 8 ...

Страница 4: ... 0 10 V output mode 0 V 0 RH and 10 V 100 RH Reverse Acting RA 0 10 V output mode 0 V 100 and 10 V 0 To change the transmitter to reverse acting or back to direct acting set switch 4 to ON to put the unit in setup mode After switch 4 is on turning switch 2 to ON will put the unit in direct reverse acting mode When switch 2 is set to ON the out put can be used to show if the unit is in direct or re...

Страница 5: ...ut This will reset the RH output back to the original calibration Switch 4 must be set to ON first After switch 4 is on toggle switches 5 and 6 ON then OFF After 5 and 6 are OFF slide switch 4 OFF When all calibration is completed remember to place the switches back into the positions that corre spond to the output needed as shown in FIGURE 8 RH CALIBRATION Continued TEST INSTRUCTIONS Test mode wi...

Страница 6: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 6 Version 6 0 I0000647 PRODUCT SPECIFICATIONS ...

Страница 7: ...Outside Series RH sensors are covered by ACI s Five 5 Year Limited Warranty which is located in the front of ACI S SENSORS TRANSMITTERS CATALOG or can be found on ACI s website www workaci com W E E E DIRECTIVE At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre Do not dispose of with household waste Do not burn ...

Страница 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 6 0 I0000647 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com ...

Отзывы: