SUN SHIELD HUMIDITY

SERIES

Installation & Operation Instructions

GENERAL INFORMATION 

The Solar Radiation Shield is a solution for 
protecting temperature and relative humidity 
sensors from error-producing solar radiation and 
precipitation. The highly reflective white wedge-
shaped plates provide maximum airflow around 
the sensors while at the same time minimizing 
direct exposure to sunlight.  The passive shield is 
shaped to allow natural air convection around the 
sensors so that the air temperature and relative 
humidity inside the shield is a good representation 
of the outside air. The RH Sun Shield transmitter 
is field selectable with a 4-20 mA, 0-5 VDC, or 
0-10 VDC output signal that is equivalent to 0 
to 100% RH. This sensor is designed for use with 
electronic controllers in commercial heating and 
cooling building management systems. All units 
are shipped from the factory set up for a 4-20 
mA output. The transmitter can also include an 
optional temperature sensor for monitoring the 
space temperature.

For optimal readings, follow these tips:  

• Place the shield in an open area to insure 

unrestricted air flow or wind

• Keep away from large radiant heat sources, such 

as sun exposed buildings and solar panels.

• Avoid building exhaust vents, electrical 

machinery, and motors.

• Do not install over or near sprinklers. Continuous 

moisture may damage the sensors.

Phone: 

1-888-967-5224

Website: 

workaci.com

MOUNTING INSTRUCTIONS

The Solar Radiation Shield is designed for two 

different mounting configurations such as a metal 

pipe with outside diameter between 1" and 1.5" 

(U-Bolts included) or on the side of a building or 

wooden post (Hardware Not included).

Pole Mounting 

• Locate the four U-Bolt mounting holes on the 

back panel of the mounting bracket. Attach the 
U-Bolts, U-Bolt Washers and 5/16" Hex Nuts as 
shown in 

Figure 2

FIGURE 2:

 MOUNT BRACKET

FIGURE 1: 

ENCLOSURE DIMENSIONS

[94.0mm]

3.70in

[56.7mm]

 2.23in

[379.7mm]

14.95in

[64.8mm]

2.55in

Содержание SUN SHIELD HUMIDITY Series

Страница 1: ... heating and cooling building management systems All units are shipped from the factory set up for a 4 20 mA output The transmitter can also include an optional temperature sensor for monitoring the space temperature For optimal readings follow these tips Place the shield in an open area to insure unrestricted air flow or wind Keep away from large radiant heat sources such as sun exposed buildings...

Страница 2: ...ng both ends can cause a ground loop Do not run the temperature sensor wiring in any conduit with line voltage 24 120 230 VAC if utilizing resistance temperature signal It is recommended you use an isolated UL listed class 2 transformer when powering the unit with 24 VAC Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by th...

Страница 3: ...53562 Phone 1 888 967 5224 Website workaci com Page 3 Version 6 0 I0000647 FIGURE 4 OUTPUT SIGNALS FIGURE 5 PRINTED CIRCUIT BOARD FIGURE 6 TEMPERATUREWIRING ON 4 2 3 6 PUSH TAB IN AND PULL UP ON THE SENSOR CABLE TO REMOVE FROM J13 CONNECTOR FACTORY USE ONLY 1 5 7 8 ...

Страница 4: ... 0 10 V output mode 0 V 0 RH and 10 V 100 RH Reverse Acting RA 0 10 V output mode 0 V 100 and 10 V 0 To change the transmitter to reverse acting or back to direct acting set switch 4 to ON to put the unit in setup mode After switch 4 is on turning switch 2 to ON will put the unit in direct reverse acting mode When switch 2 is set to ON the out put can be used to show if the unit is in direct or re...

Страница 5: ...ut This will reset the RH output back to the original calibration Switch 4 must be set to ON first After switch 4 is on toggle switches 5 and 6 ON then OFF After 5 and 6 are OFF slide switch 4 OFF When all calibration is completed remember to place the switches back into the positions that corre spond to the output needed as shown in FIGURE 8 RH CALIBRATION Continued TEST INSTRUCTIONS Test mode wi...

Страница 6: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 6 Version 6 0 I0000647 PRODUCT SPECIFICATIONS ...

Страница 7: ...Outside Series RH sensors are covered by ACI s Five 5 Year Limited Warranty which is located in the front of ACI S SENSORS TRANSMITTERS CATALOG or can be found on ACI s website www workaci com W E E E DIRECTIVE At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre Do not dispose of with household waste Do not burn ...

Страница 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 6 0 I0000647 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com ...

Отзывы: