Q6 Operation And Maintenance Manual
86650-001-000 RB
Feb 22, 2019
15
3.4 Menu “1_SYSTEM SETUP”
The system setup subdivision contains general settings for monitor operations,
communications.
3.4.1
System Settings
Password:
Default password is 4321.
Q6M
MAC
Address:
Q6M monitor address can be defined from 0 to 255. Default is 3.
Q6R address would be a 1
Note: In Modbus protocol, the address 0 is for broadcast.
Baud rate:
Define baud rate for RS-485 communication with ACI controllers OptoMux
protocol or other SCDA system with Modbus protocol.
Q6 default baud rate is 4800 bps
Scroll Rate:
In normal operation, the sensor and relay status information scrolls
automatically. Set the number of seconds for each item to be displayed.
Default value is 3 seconds.
Backlight:
The LCD backlight can be set to Always Off, Always On and Auto Power
Saving mode. In Auto Power Saving mode, the backlight will turn on for 10
seconds after any key has been pressed. Default setting is Auto.
New
Password:
The new password can be any combination of up to four digits. Default
password is 4321.
Warning:
Be sure that you record the new password in a safe and
secure location!
Protocol:
The Q6 Default protocol is OptoMux.
The Q6 also supports Modbus protocol, responds as a Modbus Slave using
RTU protocol. When it’s set to Modbus, the parity bit can be defined as
EVEN, ODD and No Parity.