FIGURE 3: 

BACKPLATE

Refer to the wiring instructions to make necessary 
connections. After wiring, attach the cover to the 
base by snapping the top of the cover on first and 
then the bottom. 

Take care when mounting. Check local code for 
mounting height requirements. Typical mounting 
heights are 48-60”(1.22-1.52m) off the ground and 
at least 1.5’(0.5m) from the adjacent wall. The 
sensor should be mounted in an area where air 
circulation is well mixed, and not blocked by 
obstructions. 

WIRING INSTRUCTIONS 

PRECAUTIONS

•  DO NOT RUN THE WIRING IN ANY CONDUIT 

WITH LINE VOLTAGE(24/120/230VAC).

• Remove power before wiring. Never 

connect or disconnect wiring with power 

applied.

•  It is recommended that you use an isolated 

UL-listed Class 2 transformer when 

powering the unit with 24 VAC. Failure to 

wire the devices with the correct polarity 

when sharing transformers may result in 

damage to any device powered by the 

shared transformer.

•  IF THE 24 VDC OR 24VAC POWER IS SHARED 

WITH DEVICES THAT HAVE COILS SUCH AS 

RELAYS, SOLENOIDS, OR OTHER 

INDUCTORS, EACH COIL MUST HAVE AN 

MOV, DC/AC TRANSORB, TRANSIENT 

VOLTAGE SUPPRESSOR (ACI PART: 

142583), OR DIODE PLACED ACROSS THE 

COIL OR INDUCTOR. THE CATHODE, OR 

BANDED SIDE OF THE DC TRANSORB OR 

DIODE, CONNECTS TO THE POSITIVE SIDE 

OF THE POWER SUPPLY. WITHOUT THESE 

SNUBBERS, COILS PRODUCE VERY LARGE 

VOLTAGE SPIKES WHEN DE-ENERGIZING 

THAT CAN CAUSE MALFUNCTION OR 

DESTRUCTION OF ELECTRONIC CIRCUITS.

ACI recommends 16 to 26 AWG twisted pair wires 
or shielded cable for all transmitters.

ACI recommends using BELDEN 3105 for communi-
cation(Modbus) wiring. This wire has 120 ohm 
input impendence. The terminal blocks allow for (1) 
or (2) wires to be connected in each position for 
daisy chaining. Daisy chain the RS-485 wiring and 
do not use “Star” or “T” wiring. Avoid running 
communication wires next to AC line voltage wires. 
These can be sources of noise that can affect signal 
quality.

FIGURE 4: 

WIRING

Note: Different models have 
different electrical terminals.

Terminal 3 is 0-10VDC output
Terminal 4 is 4-20mA output.

POWER SUPPLY

 

24VDC
24VAC

RS485

Vout

mA

A

B

NO

(Normally Open)

Relay Output

C

(Common)

1

2

9

4

6

10

Version: 1.0

I0000941

Содержание PM2.5-ROOM

Страница 1: ...set to Auto Mode IMPORTANT PRECAUTIONS This product uses a laser particulate matter sensor It is strictly prohibited to be disassembled It is dangerous if the human body is exposed to the laser directly If the environment exceeds the measurement range for an extended period it may lead to a decrease of the measurement accuracy The performance of the sensor may be decreased due to excessive dust an...

Страница 2: ...ansformer IF THE 24 VDC OR 24VAC POWER IS SHARED WITH DEVICES THAT HAVE COILS SUCH AS RELAYS SOLENOIDS OR OTHER INDUCTORS EACH COIL MUST HAVE AN MOV DC AC TRANSORB TRANSIENT VOLTAGE SUPPRESSOR ACI PART 142583 OR DIODE PLACED ACROSS THE COIL OR INDUCTOR THE CATHODE OR BANDED SIDE OF THE DC TRANSORB OR DIODE CONNECTS TO THE POSITIVE SIDE OF THE POWER SUPPLY WITHOUT THESE SNUBBERS COILS PRODUCE VERY ...

Страница 3: ... measuring time to extend the service life of the sensor when the dust concentration changes very slightly Use MODE jumper to choose the mode The factory default mode is AUTO Notes P999 Reset Once entered rST is displayed Press button All factory default settings will be restored P161 1 Point Calibration The current value is displayed Press button to increase an offset Press button to decrease an ...

Страница 4: ...uires that the last device in a chain have a termination resistor This is controlled using a jumper in the center and right pins 120 Ω position marked on FIGURE 7 When the jumper is set to 120 Ω a 120 Ω resistance is added in parallel to the data line When the jumper is set to left and center pins disabled the resistance is not added By default the jumper is placed in the disabled position ERROR C...

Страница 5: ...Menu selection see above for Menu Adjustments The device that requests information is called the Modbus Master and the devices giving the information are Modbus Slaves The Modbus sensors are slave devices and the number of Data Bits needs to be the same as in the Master device configuration ACI s Modbus RTU sensors utilize 8 data bits during communication exchange Parity default setting is NONE St...

Страница 6: ...emarks PM series Product code 9070 PM2 5 Value ug m PM10 Value ug m Default slave address 1 RTU 9600 n 8 1 Write 40016 21845 to reset to factory default setting 0 Off 1 Relay activated Below the set point 2 Relay activated Higher than set point 3 Relay activated in the set range 4 Relay activated outside the set range Relay control parameters set Baud rate 9600 default or 4800 Parity 0 NONE 1 ODD ...

Страница 7: ...0 reading 100 500 600µg m3 25 C 50 RH 1 μg m3 In continuous service mode sample time 1s response time 10s 15 minutes MTBF more than 3 years in continuous service mode service life up to 8 10 years in auto intermittent service mode Modbus RTU EIA RS 485 1 247 4800 or 9600 None Even Odd 1 8 ScrewTerminal Blocks 16 AWG 1 31 mm2 to 22 AWG 0 33 mm2 0 45 lbf in 0 5 Nm nominal 32 to 122 F 0 to 50 C 30 to...

Страница 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 1 0 I0000941 ...

Отзывы: