aci P51 Series Скачать руководство пользователя страница 3

FIGURE 3: 

CURRENT WIRING 

DIAGRAM

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 3

Version: 3.0

I0000792

MEDIA COMPATIBILITY

The bulk micro-machined transducer features a stainless steel diaphragm with welded construction that 
contains no O-rings, which makes them compatible with any gas or liquid that’s compatible with 304L or 
316L stainless steel.  Some compatible gasses and liquids include refrigerants, glycol, motor oil, diesel, 
hydraulic fluid, brake fluid, water, waste water, hydrogen, nitrogen and air.

Installation

LOCATION

Install the sensor in a location where it will not be exposed to extreme temperatures, vibration or shock.  
Install the pressure sensor above or on the side of pipes, in a location where liquid will not drip on the unit.  
Condensation can potentially build up and run down the harness; position the unit and harness so water 
does not pool on the back of the sensor.  Do not install the sensor at the end of a long run of pipe.

CONNECTION

The P51 series sensor is available with multiple 
external thread sizes, see the Datasheet chart 
for more details.  Standard pipe fittings and 
installation procedures should be used during 
installation.  Install pipe tape, thread sealant or 
other suitable pipe compound when 
connecting the sensor to the pressure source or 
any of the accessories.  For pressure ranges 
more than 500 PSI (3447.4 kPa), we recommend 
the use of a sealant such as Loctite Hydraulic 
Sealant.  Do not use excessive amounts of 
sealant or you might block the pressure going 
into the transducer.  Install the device using a 
wrench on the hex flats provided.  Do not use a 
strap wrench on the body.  When installing the 
sensor, the torque limit will vary, see the Torque 
Limits Table for more detail. Do Not over 
tighten.  Overtightening metal fittings may 
cause a slight zero shift.  The use of plastic 
fittings typically results in no noticeable zero 
shift.  The torquing effect does not appreciably 
affect linearity or sensitivity.  In liquid pressure 
monitoring applications, air present in the lines 
will cause erratic readings, use bleed fittings to 
bleed off any air that has been trapped before 
transducer installation.

WIRING INSTRUCTIONS

The supply voltage and current required will 
vary per unit, see the General Specifications 
Table for more details.  If you’ve selected a Packard connector make the proper connections to the harness, 
then install the P51 Sensor onto the harness.

Note:

 Be careful not to kink the vent tube if cutting the 24” PVC wire down or removing all together. 

Kinking the clear tube will affect the reference pressure on all PSIG Series Transducers.

4-20 OUTPUT CONNECTIONS

Connect the Power lead (Red) to the plus terminal of the supply voltage.  Connect the Return lead (White)
 

WIRING INSTRUCTIONS 

(Continued)

to the plus terminal of the current measuring device (controller).  Connect the minus terminal of the 

current measuring device to the minus terminal of the supply voltage, and the Shield Wire (Green) should 

be connected to the system or earth ground.  See 

Figure 3

, Current Wiring diagram.

Note: 

If the harness has a black wire, do not use it.

COM

RED WIRE

WHITE WIRE

CLEAR VENT TUBE

Clear Vent Tube on

I24 Lead Style Only

Optional 250 Ohm or 500 Ohm

Load Resistor for a 1-5 VDC or

2-10 VDC Output

SHIELD

POWER SUPPLY

 +13 TO 30 VDC

-     +

AUTOMATION

      PANEL

AI1

FIGURE 4: 

VOLTAGE WIRING 

DIAGRAM

COM

RED WIRE

WHITE WIRE

BLACK WIRE

Note:

 Clear Vent Tube on 

I24 Lead Style Only

AI1/AI2 = VDC

Analog Input

CLEAR VENT TUBE

SHIELD

POWER SUPPLY

 +5 TO 30 VDC

-     +

AUTOMATION

      PANEL

AI1

VOLTAGE OUTPUT CONNECTIONS

Connect the Power lead (Red) to the plus terminal of the supply voltage.  Connect the Ground lead (Black) 
and the minus terminal of the supply voltage to the minus input of your voltage measurement equipment.  
Connect the Vout lead (White) to the plus input of your voltage measurement equipment, and the Shield 
Wire should be connected to the system or earth ground.  See 

Figure 4

, Voltage Wiring diagram. 

Содержание P51 Series

Страница 1: ...pressure snubber is a cost effective solution that can extend the life of your sensor by smoothing out pressure spikes surges and pulsations and prevent debris from collecting in the sensor diaphragm opening The A 0 25 Snubbers are made of 316 Stainless Steel and should be used with compatible materials Syphons The A Syphon must be used to protect the sensor from extreme operating temperatures whe...

Страница 2: ...kPa we recommend the use of a sealant such as Loctite Hydraulic Sealant Do not use excessive amounts of sealant or you might block the pressure going into the transducer Install the device using a wrench on the hex flats provided Do not use a strap wrench on the body When installing the sensor the torque limit will vary see the Torque Limits Table for more detail Do Not over tighten Overtightening...

Страница 3: ... Tube on I24 Lead Style Only Optional 250 Ohm or 500 Ohm Load Resistor for a 1 5 VDC or 2 10 VDC Output SHIELD POWER SUPPLY 13 TO 30 VDC AUTOMATION PANEL AI1 FIGURE 4 VOLTAGE WIRING DIAGRAM COM RED WIRE WHITE WIRE BLACK WIRE Note Clear Vent Tube on I24 Lead Style Only AI1 AI2 VDC Analog Input CLEAR VENT TUBE SHIELD POWER SUPPLY 5 TO 30 VDC AUTOMATION PANEL AI1 VOLTAGE OUTPUT CONNECTIONS Connect th...

Страница 4: ...ci com Page 4 Version 3 0 I0000792 PROBLEM No Output or Output Signal Reading Low Output Signal is Inaccurate SOLUTION S ConfirmtheDCsupplyvoltageis 0 5 to 4 5 VDC Output Only 5 00 VDC 0 500 VDC 4 to 20 mA and 1 to 5 VDC Outputs Only 8 to 30 VDC No Load 4 20 mA Output 250 Ohm Load 13 to 30 VDC 500 Ohm Load 18 to 30 VDC Disconnect the sensor from the line to ensure No debris or sediment isblockingt...

Страница 5: ...C 40 to 176ºF 40 to 80ºC 304L or 316L Stainless Steel See Datasheet for more details 0 to 95 RH non condensing Any gas or liquid compatible with 304L or 316L Stainless Steel All Ports except U and Y 150 lbs in 16 95 Nm Ports U and Y 120 lbs in 13 56 Nm Packard Connector Cables ordered separately per Ordering Grid on back of data sheet 124 24 Lead Length PVC Jacketed Cable 18 0 823 mm2 or 24 AWG 0 ...

Отзывы: