background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 2

Version: 2.0

I0000857

+VDC (Red Wire)

4 to 20mA Output 

(White Wire)

RTD Wires

(100 Ohm RTD Brown Wires)
(1K Ohm RTD Black Wires)

+VDC (Red Wire)

GND (White Wire)

Voltage Output 

(Yellow Wire)

(1 to 5, 2 to 10VDC)

RTD Wires

(100 Ohm RTD Brown Wires)
(1K Ohm RTD Black Wires)

Current Output

(4 to 20 mA)

Current Output

(4 to 20 mA)

Voltage Output

(1 to 5, 2 to 10VDC)

Voltage Output

(1 to 5, 2 to 10VDC)

+VDC

4 to 20mA Output

+VDC

GND

Voltage Output

(1 to 5, 2 to 10VDC)

+

- GND VOUT

RTD

+ -

RTD

SPAN

ZERO

SPAN

ZERO

SPAN

ZERO

SPAN

ZERO

POTTED UNITS

STANDARD UNITS

FIGURE 3: 

WIRING DIAGRAMS

VAC

FIGURE 2: 

OUTSIDE MOUNTING

WIRING INSTRUCTIONS

PRECAUTIONS 
• Transmitter is powered by 24 VDC only.
• Remove power before wiring. NEVER 

connect or disconnect wiring with power 
applied.

• When removing the shield from the sensor 

end, make sure to properly trim the shield to 
prevent any chance of shorting.

• When using a shielded cable, ground the 

shield ONLY at the controller end. Grounding 
both ends can cause a ground loop.

• If the 24 VDC power is shared with devices 

that have coils such as relays, solenoids, or 
other inductors, each coil must have an MOV, 
DC Transorb, Transient Voltage Suppressor 
(ACI Part: 142583), or diode placed across the 
coil or inductor. The cathode, or banded side 
of the DC Transorb or diode, connects to the 
positive side of the power supply. Without 
these snubbers, coils produce very large 
voltage spikes when de-energizing that can 
cause malfunction or destruction of electron-
ic circuits.

Open the cover of the enclosure. ACI recommends 
16 to 26 AWG twisted pair wires or shielded cable 
for all transmitters. Twisted pair may be used for 
2-wire current output transmitters or 3-wire for 
voltage output. Refer to 

FIGURE 3

 (right) for wiring 

diagrams. All wiring must comply with local and 
National Electric Codes. All ACI TT and TTM tempera-
ture transmitters can be powered from either an 
unregulated or regulated 8.5 to 32VDC power 
supply. The TT and TTM DO NOT support an AC 
input. All TT and TTM temperature transmitters are 
reverse polarity protected. After wiring, attach the 
cover to the enclosure.

The minimum voltage at the transmitter power 
terminal is 8.5V after load resistor voltage drop.

249 Ω load resistor (1-5 VDC output) = 13.5 V min supply 

voltage

499 Ω load resistor (2-10 VDC output) = 18.5 V min 

supply voltage

Note: 

Adding extra wire length between the 

sensor and transmitter board may affect accuracy. 

Recommended 1-2 ft 

(0.3-0.6 m) Below Eave

Install Sensor

Downward

Roof

Ground

Отзывы: