TROUBLESHOOTING

PROBLEM                                                              SOLUTION(S)

No Reading:

- Verify that there is current flowing through the conductor being monitored with a   

clamp-on current probe.

- Check the polarity of the circuit.

- Verify that the terminals are screwed down, wires are firmly in place.

MSCTA-40

- Confirm that you have +13.5 to 30VDC in series with the current sensor output 

terminals and the analog input of the control panel.

- Disconnect the input to the control panel and then insert a current meter (mA 

range) in series with the current sensor output to verify that the circuit is working 

properly.

MSCTE-40

- No power supply needed. The power for the current sensor is induced from the 

conductor being monitored.

- Disconnect the wires from the current sensor output and tighten down the screws. 

Measure the voltage across the current sensor output with a Voltmeter to verify that 

the sensor is working properly.

Erratic Readings:

- Verify that the wires are terminated properly.

- In areas of high RF interference, shielded

cable may be necessary to stabilize signal.

Inaccurate Readings:

- If you suspect that the current sensor is not reading within the accuracy 

specifications, please contact the factory for assistance.

Current Sensor is operating at a low-level 

current or failing to operate within the accuracy 

specifications:

-Visually check the mating parts of the core to ensure there is no debris between the 

split contacts. 

-Remove all debris or dust manually and close the current sensor.

-Continue to retest the sensor in your application.