PRODUCT SPECIFICATIONS
WARRANTY
The Freeze Stat Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S
SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone:
1-888-967-5224 |
Website:
workaci.com
Page 4
Version: 10.0
I0000298
Self-contained, electromechanical
Vapor-filled capillary
Temperature in air
14°F to 54°F (-10°C to 12°C)
392°F (200°C), maximum 60 minutes
To lowest temperature sensed by any 1 ft section of the capillary element
Copper
Duct and across coil mounted
Ø0.08 in. (2 mm) (6’ Length models have a larger bulb at the end)
ON/OFF, low-level single-stage or cut-out control, with One (1) microswitch output
At 39°F (4°C), and safety-lock secured
14°F to 54°F
Over full operating range, via screwdriver slot
Form 1C (SPDT Contact)
250 VAC
15 (8) A
1.8°F (1°K), auto- or manual reset
14°F to 131°F (-10°C to 55°C)
0 to 95% RH, non-condensing
14°F to 158°F (-10°C to 70°C)
Steel, galvanized
ABS, fire retardant
NON-SPECIFIC INFORMATION
Thermostat Type:
Sensing Element:
Sensing Media:
Sensing Temperature Operating Range:
Sensing Capillary Overload
Temperature:
Sensing Response:
Sensing Capillary Material:
Sensing Capillary Length:
Sensing Capillary Diameter:
Type of Control:
Low-Level Setpoint (Factory Set):
Low-Level Setpoint Visual Range:
Low-Level Setpoint Adjustment:
Contact Form:
Maximum Contact Switching Voltage:
Maximum Contact Switching Current:
Switching Differential:
Enclosure Operating Temperature
Range:
Operating Humidity Range:
Storage Temperature Range:
Enclosure Base Material:
Enclosure Cover Material: