PRODUCT SPECIFICATIONS

WARRANTY

The Freeze Stat Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S 
SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.

W.E.E.E. DIRECTIVE

 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling 
centre. Do not dispose of with household waste. Do not burn.

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

Version: 10.0

I0000298

Self-contained, electromechanical

Vapor-filled capillary

Temperature in air

14°F to 54°F (-10°C to 12°C)

392°F (200°C), maximum 60 minutes

To lowest temperature sensed by any 1 ft section of the capillary element

Copper

Duct and across coil mounted

Ø0.08 in. (2 mm) (6’ Length models have a larger bulb at the end)

ON/OFF, low-level single-stage or cut-out control, with One (1) microswitch output

At 39°F (4°C), and safety-lock secured

14°F to 54°F

Over full operating range, via screwdriver slot

Form 1C (SPDT Contact)

250 VAC

15 (8) A

1.8°F (1°K), auto- or manual reset

14°F to 131°F (-10°C to 55°C)

0 to 95% RH, non-condensing

14°F to 158°F (-10°C to 70°C)

Steel, galvanized

ABS, fire retardant

NON-SPECIFIC INFORMATION

 

Thermostat Type:

Sensing Element:

Sensing Media:  

Sensing Temperature Operating Range: 

Sensing Capillary Overload 

Temperature:

Sensing Response:

Sensing Capillary Material: 

Sensing Capillary Length:

Sensing Capillary Diameter:

Type of Control: 

Low-Level Setpoint (Factory Set):

Low-Level Setpoint Visual Range:

Low-Level Setpoint Adjustment:

Contact Form:

Maximum Contact Switching Voltage:

Maximum Contact Switching Current:

Switching Differential:

Enclosure Operating Temperature 

Range:

Operating Humidity Range:

Storage Temperature Range: 

Enclosure Base Material: 

Enclosure Cover Material:

Содержание FREEZE STATS Series

Страница 1: ...capillary lengths are also available MOUNTING INSTRUCTIONS Do not uncoil more element or capillary than is required for the application Do not sharply bend the element or capillary more than necessary bending hardens the element and makes it brittle If the element or capillary can be subjected to vibration protect any surface that makes contact Strap the element on a coil for example in an area wh...

Страница 2: ... thermostat in an upright position so that the bellows point down and the capillary tube exits the bottom of the unit WIRING INSTRUCTIONS All wiring should comply with National and Local Electrical Codes A M20 watertight fitting is installed in the conduit knockout If the knockout is needed remove the M20 fitting and install the appropriate conduit fitting in the 0 830 knockout in the bottom of th...

Страница 3: ...D FS 1 FS 1A FS 3 FS 3A FS 5 FS 5A FS 6 FS 2 FS 2A FS 4 FS 4A FS 6 FS 6A FS 50 FS 50A Note Falling Temperature and attained low cut out point Contact Connection Red to Blue White Red Blue N C Common N O Schematic Diagram Note Falling Temperature and attained low cut out point Contact Connection Red to Blue White Red Blue N C Common N O Schematic Diagram White Red Blue N C Common N O ...

Страница 4: ... 6 Length models have a larger bulb at the end ON OFF low level single stage or cut out control with One 1 microswitch output At 39 F 4 C and safety lock secured 14 F to 54 F Over full operating range via screwdriver slot Form 1C SPDT Contact 250 VAC 15 8 A 1 8 F 1 K auto or manual reset 14 F to 131 F 10 C to 55 C 0 to 95 RH non condensing 14 F to 158 F 10 C to 70 C Steel galvanized ABS fire retar...

Отзывы: