background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 4.0

I0000744

FIGURE 1: 

DIMENSIONS

CARBON DIOXIDE DUCT SERIES

Installation & Operation Instructions

A/CO2-DUCT

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

The ACI Carbon Dioxide Duct Series (A/CO2-D) 
monitors the carbon dioxide (CO2) levels in 
industrial, commercial, school, and office-type 
environments. The concentration of CO2 is a 
strong indication of the overall indoor air 
quality. The A/CO2 Series is based on a single 
beam, non-dispersive infrared technology 
and is a cost-efficient solution for measuring 
carbon dioxide levels for building climate 
control. In addition, ABC software eliminates 
the need for manual calibration. Carbon 
Dioxide concentration is measured up to 
2,000 ppm and is converted into proportional 
analog outputs. The factory default output is 
4-20 mA, whereas 0-5 VDC and 0-10 VDC 
outputs are field selectable via integral dip 
switches. The A/CO2-D provides data which 
can be used in conjunction with a Building 
Automation System or Demand Control 
Ventilation to decrease energy consumption while creating a healthier indoor climate.  

MOUNTING INSTRUCTIONS

Since there might be a substantial pressure difference in duct mounting applications, it is essential to avoid 
ambient air from suction into the duct mounting box. For correct function it is indispensable that the 
sealing of the box cover, the cable entry bushings, the cable feed through and the duct entrance are 
absolutely tight. The duct entrance may need extra sealing paste in order to prevent leakage. The PCB must 
be handed carefully and protected from electrostatic discharge.

• Place the O-ring around the hole at the back of the box. See 

figure 2

.

• Electrical cable entry: The box has a factory mounted cable entry bushing. Never feed more than one 
cable through each cable entry bushing, or else gas might leak through!

• Mounting the tube: Drill a 1” (25 mm) diameter hole for the sampling probe and two holes with 0.16” (4 
mm) diameter for the screws (5) into the air duct and mount the tube (1) with the gasket (2). The sampling 
probe should be mounted with the largest locking knob on top. The unit can be mounted with the air 
coming from the left or right.

• Attaching the sensor box is made to the sampling probe by a snap-in bayonet fitting. Orient the box onto 
the sampling probe so that the box upside is on the same side as the largest locking knob (3). When the 

probe is fitted into the notches of the box, then turn the box clockwise until stop (see 

Figure 2

). Position 1 

indicates open where the box can be removed from the sampling probe. In position 2 the box is locked to 
the probe.

3.31” (84mm)

5.59” 

(142mm)

5.98” 

(151.89mm)

8.03” (203.96mm)

1.65” 

(41.91mm)

1.81” 

(46mm)

WIRING

PRECAUTIONS   
• Remove power before wiring. Never 
connect or disconnect wiring with power 
applied.
• When using a shielded cable, ground the
shield only at the controller end. 
Grounding both ends can cause a ground 
loop.
• It is recommended you use an isolated
UL-listed class 2 transformer when 
powering the unit with 24 VAC. Failure to 
wire the devices with the correct polarity 
when sharing transformers may result in 
damage to any device powered by the 
shared transformer.
• If the 24 VDC or 24VAC power is shared 
with devices that have coils such as 
relays, solenoids, or other inductors, 
each coil must have an MOV, DC/AC 
Transorb, Transient Voltage Suppressor 
(ACI Part: 142583), or diode placed across 
the coil or inductor. The cathode, or 
banded side of the DC Transorb or diode, 
connects to the positive side of the power supply. Without these snubbers, coils produce very 
large voltage spikes when de-energizing that can cause malfunction or destruction of electronic 
circuits.

Open the cover of the enclosure. ACI recommends 16 to 26 AWG twisted pair wires or shielded cable
for all transmitters. Refer to

 FIGURE 3

 for wiring diagrams. All wiring must comply with all local and 

National Electric Codes.

Note:

 The 4-20mA output requires 3 wires. 

Note: 

When using a shielded cable, be sure to connect only (1) end of the shield to ground at the 

controller. Connecting both ends of the shield to ground may cause a ground loop. When removing the 

shield from the sensor end, make sure to properly trim the shield to prevent any chance of shorting.

DIP SWITCH CONFIGURATION

SW 1 sets the Output Signal. 

SW2 controls the ABC Logic. 

The default setting is 0-10 VDC output (switch 1 on) and ABC on (switch 2 on). For 0-5 VDC output set

switch 1 to off. The 4-20 mA output can be used with switch 1 in the on or off position.

ABC stands for automatic baseline correction, a self-calibration function for achieving maintenance-free 

gas sensors. To turn off ABC, set switch 2 to off. The ABC Logic must be turned off in applications where 

there is 24/7 occupancy. ie: Hospital

Содержание Carbon Dioxide Duct Series

Страница 1: ...healthier indoor climate MOUNTING INSTRUCTIONS Since there might be a substantial pressure difference in duct mounting applications it is essential to avoid ambient air from suction into the duct mounting box For correct function it is indispensable that the sealing of the box cover the cable entry bushings the cable feed through and the duct entrance are absolutely tight The duct entrance may nee...

Страница 2: ...sted class 2 transformer when powering the unit with 24 VAC Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any device powered by the shared transformer If the 24 VDC or 24VAC power is shared with devices that have coils such as relays solenoids or other inductors each coil must have an MOV DC AC Transorb Transient Voltage Suppressor ACI Part...

Страница 3: ...event any chance of shorting DIP SWITCH CONFIGURATION SW 1 sets the Output Signal SW2 controls the ABC Logic The default setting is 0 10 VDC output switch 1 on and ABC on switch 2 on For 0 5 VDC output set switch 1 to off The 4 20 mA output can be used with switch 1 in the on or off position ABC stands for automatic baseline correction a self calibration function for achieving maintenance free gas...

Страница 4: ...grid 1 F 0 6ºC 32 to 122ºF 0 to 50ºC 0 to 95 non condensing Duct Box PC ABS blend Flammability Rating UL94V 0 Cover Makrolon 6555 plastic Flammability Rating UL94V 0 Pipe PC ABS blend Flammability Rating UL94V 0 7 500 sq ft maximum 4 6 ft 15 years typical ABC algorithm Automatic Baseline Correction NON SPECIFIC INFORMATION Supply Voltage Power Consumption Sensing Technology Sensing Method Measurem...

Отзывы: