background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 5

Version: 9.0

I0000585

TABLE 6: 

PRESET OUTPUT OFFSETS

OUTPUT DIP SWITCH

5 ON…………… 6, 7, 8 OFF

6 ON……………..5, 7, 8 OFF

7 ON……………..5, 6, 8 OFF

VOLTAGE OUTPUT 

 

0V or 0mA 

1V or 4mA

2V or 8mA

TO SET ADJUSTABLE OUTPUT SPANS

If your output span is not a listed preset, set the span 
DIP switches 1 through 4 to one of the three 
adjustable  ranges (just above in bold), and the offset 
switches to the adjustable range by placing switch 8 
ON, and 5,6,7  OFF.  Give the AIM2 the maximum input 
signal and adjust the SPAN pot until the required span is reached on the output terminals. 

Three preset output signal offsets are available.  These will raise the entire span by the amount indicated, 
above zero.  For example, an 8V span with a 2V offset will give you a 2 – 10V output signal.  If your offset (or 
minimum output) is zero, set switch 5 ON and switches 6,7,8 OFF. See 

Table 6

.

ADJUSTABLE OUTPUT OFFSETS

If your offset is not 0, 1, or 2 volts, you will need to adjust for your offset.  The offset can be adjusted from 0 
to approximately 10V.

Adjustable:     8 ON………………...5,6,7 OFF

Generate the minimum input signal at the input terminals IN and COM and calibrate the output OFFSET 
pot until the offset required is reached (check with a voltmeter at output terminals OUT and COM).

From this point on, no further DIP switch changes are necessary.  Toggle back and forth between the 
maximum and minimum to check the accuracy of the calibration.  If the span (or maximum of the output) 
needs adjustment, turn the span pot.  If the offset (or minimum) needs adjustment, turn the offset pot.  
Repeat until calibrated correctly.

POWER UP AND CHECKOUT

STEP 2) POWER UP

Turn on the 24 VAC power supply.  Both power indicators on the AIM2 will light.

STEP 3) OPERATION

The AIM2 will now operate to your specifications, or the standard settings from the factory.  If no field  
calibrations were made, then the AIM2 will accept a 0 to 5 volt DC input signal and produce an isolated and  
proportional 0 to 5 volt DC output signal.  For example, a 3.50 volt input signal will produce a 3.50 volt DC  
output signal.

Содержание AIM2

Страница 1: ...le upon request for an additional charge This will speed up installation time for the end user MOUNTING INSTRUCTIONS Ground yourself to discharge static electricity before touching any electronic equipment as some components are static sensitive The interface device can be mounted in any position If circuit board slides out of snap track a non conductive stop may be required Use only fingers to re...

Страница 2: ... Power 24 VAC Source Current or Voltage Output Signal Sink Loop Powered Current Input Connections using Internal VDC Supply Sink Current Output Two Wire Loop Powered Device Sink Loop Powered Current Output Connections using External VDC Supply Input Sink Current Connections 24VDC In Set Jumper For Sink Current Sink Loop Powered Current Output Connections using Internal VDC Supply Controller ...

Страница 3: ...ING CONNECTIONS With the power OFF make the following connections Connect a 24 VAC power supply to the 24VAC terminals of the AIM2 Connect the input signal common to the COM input terminal of the AIM2 and the input signal positive to the IN input terminal of the AIM2 Connect the output signal common COM and the output signal positive OUT to their respective terminals on the controlled device SETTI...

Страница 4: ...s other than zero set maximum as in step 2 and use the following steps to set the minimum A Set switch 8 ON and 6 and 7 OFF B Produce the minimum signal value at the input terminal IN C Measure the voltage between the TP1 test point and COM Record or remember D Now measure voltage between the TP3 test point and COM Adjust the input MIN pot until the voltage at TP3 is equal to the voltage recorded ...

Страница 5: ...UT OFFSETS If your offset is not 0 1 or 2 volts you will need to adjust for your offset The offset can be adjusted from 0 to approximately 10V Adjustable 8 ON 5 6 7 OFF Generate the minimum input signal at the input terminals IN and COM and calibrate the output OFFSET pot until the offset required is reached check with a voltmeter at output terminals OUT and COM From this point on no further DIP s...

Страница 6: ...0 mA 5 000Ω 500Ω 3 1 45 Captive screw Terminal Blocks 12 3 31 mm2 to 22 AWG 0 33 mm2 0 5 Nm Minimum 0 6 Nm Maximum 35 to 120 F 1 7 to 48 9 C 10 to 95 non condensing 20 to 150 F 28 9 to 65 5 C NON SPECIFIC INFORMATION Supply Voltage Supply Current Input Voltage Signal Preset Ranges Input Current Signal Preset Ranges Input Signal Adjustable Voltage Span Input Signal Adjustable Voltage Offset Input S...

Страница 7: ...NOTES Page 7 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 9 0 I0000585 ...

Страница 8: ...nents Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 9 0 I0000585 ...

Отзывы: