FIGURE 1: 

DIMENSIONS

INTERFACE SERIES

Installation & Operation Instructions

AIM2

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

The AIM2 optically isolates an analog (voltage 
or current) input signal from its 
corresponding output signal. It will accept 
any input signal between 0 and 20 VDC, or 0 
and 20 mA, and output any signal within 
those ranges. The AIM2 has preset or 
adjustable inputs and preset or adjustable 
outputs that can be either voltage or current. 
The current signals on the input or output can 
be either sink or source. The AIM2 requires 
one external 24 VAC isolation transformer 
with floating secondary for power. It has an 
onboard 24 VAC isolation transformer to 
supply power to the isolated output. The 
AIM2 is field calibratable, however, factory 
calibration is available upon request for an 
additional charge. This will speed up 
installation time for the end user.

 

MOUNTING INSTRUCTIONS

Ground yourself to discharge static electricity 
before touching any electronic equipment, as 
some components are static sensitive.  The 
interface device can be mounted in any position.  If circuit board slides out of snap track, a non-conductive 
“stop” may be required.  Use only fingers to remove board from snap track.  Slide out of snap track or push 
up against side of snap track and lift that side of the circuit board to remove.  

Do not flex board.  Do not 

use tools.

WIRING INSTRUCTIONS

PRECAUTIONS
•   Remove power before wiring. Never connect or disconnect wiring with power applied.
•   When using a shielded cable, ground the shield only at the controller end. Grounding both 
ends can cause a ground loop. 
• This device needs to have its own Isolated Transformer. This transformer cannot be 
connected/or shared with any other device. It is recommended you use an isolated UL-listed class 
2 transformer.
•   All wiring must comply with all local and National Electric Codes.

I

4.60” (116.84mm)

3.23”

(81.90mm)

3.25”

(8255mm)

4.69” (119.13mm)

0.70” 

(17.78mm)

Содержание AIM2

Страница 1: ...le upon request for an additional charge This will speed up installation time for the end user MOUNTING INSTRUCTIONS Ground yourself to discharge static electricity before touching any electronic equipment as some components are static sensitive The interface device can be mounted in any position If circuit board slides out of snap track a non conductive stop may be required Use only fingers to re...

Страница 2: ... Power 24 VAC Source Current or Voltage Output Signal Sink Loop Powered Current Input Connections using Internal VDC Supply Sink Current Output Two Wire Loop Powered Device Sink Loop Powered Current Output Connections using External VDC Supply Input Sink Current Connections 24VDC In Set Jumper For Sink Current Sink Loop Powered Current Output Connections using Internal VDC Supply Controller ...

Страница 3: ...ING CONNECTIONS With the power OFF make the following connections Connect a 24 VAC power supply to the 24VAC terminals of the AIM2 Connect the input signal common to the COM input terminal of the AIM2 and the input signal positive to the IN input terminal of the AIM2 Connect the output signal common COM and the output signal positive OUT to their respective terminals on the controlled device SETTI...

Страница 4: ...s other than zero set maximum as in step 2 and use the following steps to set the minimum A Set switch 8 ON and 6 and 7 OFF B Produce the minimum signal value at the input terminal IN C Measure the voltage between the TP1 test point and COM Record or remember D Now measure voltage between the TP3 test point and COM Adjust the input MIN pot until the voltage at TP3 is equal to the voltage recorded ...

Страница 5: ...UT OFFSETS If your offset is not 0 1 or 2 volts you will need to adjust for your offset The offset can be adjusted from 0 to approximately 10V Adjustable 8 ON 5 6 7 OFF Generate the minimum input signal at the input terminals IN and COM and calibrate the output OFFSET pot until the offset required is reached check with a voltmeter at output terminals OUT and COM From this point on no further DIP s...

Страница 6: ...0 mA 5 000Ω 500Ω 3 1 45 Captive screw Terminal Blocks 12 3 31 mm2 to 22 AWG 0 33 mm2 0 5 Nm Minimum 0 6 Nm Maximum 35 to 120 F 1 7 to 48 9 C 10 to 95 non condensing 20 to 150 F 28 9 to 65 5 C NON SPECIFIC INFORMATION Supply Voltage Supply Current Input Voltage Signal Preset Ranges Input Current Signal Preset Ranges Input Signal Adjustable Voltage Span Input Signal Adjustable Voltage Offset Input S...

Страница 7: ...NOTES Page 7 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 9 0 I0000585 ...

Страница 8: ...nents Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 9 0 I0000585 ...

Отзывы: