background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 15.0

I0000777

Version: 15.0

I0000777

FIGURE 1: 

DLP DIMENSIONS

DLP SERIES

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

4.35"

(110.43 mm)

2.23"

(56.52 mm)

2.48"

(62.99 mm)

5.56"

(141.29 mm)

6.02"

(152.82 mm)

CORDGRIP /

1/2 “ CONDUIT FITTING

HIGH PRESSURE PORT

LOW PRESSURE PORT

-H

-L

PRECAUTIONS
• Do not switch pressure range and output 
mode when power is on. Make sure to power off 
the unit first, then set the DIP Switches to the 
correct positions and then power on the 
transmitter.

GENERAL INFORMATION

The DLP Series is based on a piezoresistive, silicon 
sensing element which senses Differential Pressure 
and provides an analog output. Field selectable 
analog outputs include 0-5 and 0-10 VDC, or 4-20 
mA which correlate to a uni or bi-directional 
pressure range from 0-0.1” up to 0-40” of water 
column, depending on your model selection. Each 
unit has up to 8 field selectable, uni or bi-directional 
ranges (see 

Figure 6

 p. 3). 

MEDIA

The DLP can be used to monitor the differential 

pressure in any application that uses dry air or inert 

gas.

Mounting 

Find a suitable location for the enclosure. The DLP 

has 2 two mounting holes located on the top and 

bottom flanges. Drill pilot holes for the (2) #8 x 3/4” 

self-drilling screws(supplied). Use the enclosure flange as a guide, or use the dimensions listed in 

Figure 1

.  

Mount the unit vertically with the brass fittings pointing towards the ground. This ensures that any 

condensation that may form in the tubing does not have an effect on the pressure sensor.  If mounting the 

unit horizontally, a slight zero shift may occur and care must be taken to prevent moisture from building 

up in the sensor. 

FIGURE 2: 

DIN RAIL MOUNTING 

DIN RAIL

DIN RAIL

DIN RAIL

CLIP

DIN RAIL MOUNTING

 (Optional)

Attach the DIN Rail Mounting accessory to the 

back of the enclosure using the two screws 

provided.  To mount the sensor on the DIN Rail, 

place the bottom of the DIN Rail Clip into the 

35mm DIN Rail and push the unit upward to 

engage the spring clip.  Now press the top of 

the unit back until it locks into place - see 

FIGURE 2 

(p.1).

PITOT TUBE INSTALLATION 

(Optional)

Slip the rubber washer over the threaded end 

of the pitot tube, keeping the washer as close 

to the threaded end as possible. Fasten the 

pitot into the threaded insert on the back of 

the enclosure. Press the rubber washer against 

the enclosure  - see 

FIGURE 3

.

Tubing Setup When Pitot Tube is Installed

Units will be shipped with silicone tubing 
attached to the high and low pressure barb 
fittings. The silicone tubing will need to be 
removed from the High Pressure (H) barb 
fitting and secured onto the pitot tube barb 
fitting. This will leave the high pressure barb 
fitting open to atmosphere, and the Low 
pressure barb fitting remaining at default 
setup.

Pressure Connections

The recommended connection tubing is ¼” 
O.D push-on tubing (1/8” to 3/16” I.D.). For best 
results, all tubing lengths should be limited to 
a maximum length of 75 feet (23 meters). 
Longer runs will affect the response time. 

WIRING

PRECAUTIONS
• Remove power before wiring. Never 

connect or disconnect wiring with 
power applied.

• When using a shielded cable, ground the 

shield only at the controller end. 
Grounding both ends can cause a ground 
loop.

• It is recommended you use an isolated 

UL-listed class 2 transformer when 
powering the unit with 24 VAC. Failure to 
wire the devices with the correct polarity 
when sharing transformers may result in 
damage to any device powered by the 
shared transformer.

• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or 

other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI 
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC 
Transorb or diode, connects to the positive side of the power supply. Without these snubbers, 
coils produce very large voltage spikes when de-energizing that can cause malfunction or 
destruction of electronic circuits.

Open the cover of the enclosure. ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for 
all transmitters. Twisted pair may be used for 2-wire current output transmitters or 3-wire for voltage 
output. Connect the wires to the unit’s finger push-button terminal blocks.  Each DLP unit can be 
configured to three output signals: 4-20 mA, 0-5 V or 0-10 V. Use the Wiring Connections and diagrams 
to determine the proper wiring for your application. See 

TABLE 1

 (p.3) for Output Mode and Output 

Signal switch positions.

Note:

 When using 1/2” conduit, the strain relief fitting must be removed from the enclosure.

Note:

 Make sure that any conduit or metal fittings do not come in contact with the circuit board.

ZERO FUNCTION

The DLP unit should be “ZEROED” before 
pressure is applied to the unit. The zero button 
is used to cancel out any offsets caused by 
installation and sensor drift. The Zero 
adjustment must be performed with NO 
pressure applied to either side of the sensor.

Remove the tubing connected to the H(High) 
and/or L(Low) pressure fittings. Push “ZERO” 
button for more than three seconds before installation or whenever necessary.

For units with LCD display, “AUTOZERO” icon will be on when the unit enters zero mode. If zeroing 
process is successful, the “AUTOZERO” icon will flash twice.

PRESSURE RANGE SELECTION

If a custom calibrated pressure range is ordered, DO NOT change the Pressure Range Selection DIP switch 
settings. 

Table 2 

lists ACI’s 12 standard model #’s.

UNIDIRECTIONAL AND BIDIRECTIONAL 

MODE

The DLP can operate in either unidirectional mode (0 – X 
inWC) or bidirectional mode (± X inWC).  Each unit could have 
up to eight field selectable, uni or bidirectional ranges.

CAUTION

See TABLE 3  for your DLP model’s maximum pressure.

DO NOT switch pressure range or output mode when POWER is ON.  Make sure POWER to the 
unit is OFF. Failure to do so WILL NOT ALLOW any new switch settings to take place.

Choose differential pressure range based on the expected differential pressure in your 
application. Move switches to the correct positions and THEN POWER ON the transmitter.

Unidirectional Mode

DIP switch SW3 position five set at UNI side. 

DIP switch SW3 positions one and two are for Pressure Range Selection 

Bidrectional Mode

DIP switch SW3 position five set at BI side. 

DIP switch SW3 positions one and two are for Pressure Range Selection.

Note:  

In Bidirectional mode, a value of 0 inWC will have an output equal to 50% of the output signal range 

(12mA, 2.5V, 5V).

ADDITIONAL LCD FEATURES

LCD Engineering Units Adjustment

This option is ONLY for units with LCD display. Switch DIP switch SW3 position three to select Pa or inWC. 
If switched with power on, unit change will not take place until power is cycled.

“Out Of Range”

“OUT OF RANGE” icon will be on when differential pressure is over or under the minimum or maximum 
pressure range selected. If a DLP unit is outputting “OUT OF RANGE”, please turn off the unit immediately, 
and check the pressure input with a gauge or other test instrument. Once the pressure has been verified, 
set the Pressure Range Selection DIP switch to the proper positions based upon your maximum expected 
differential pressure.

CALIBRATION

DLP utilizes a digital pot for Span calibration and is factory set. There is no Span potentiometer for 
adjustment. In the event you require Span calibration, the unit must be sent back to ACI. 

The Offset can be adjusted using the Auto Zero function discussed on pg 4. Drift is a function of stress 
relaxation over time and this results in the offset shifting, and not the span . Periodically re-zeroing the 
device will eliminate the effect of drift.

Содержание ACCESS series

Страница 1: ...and 0 10 VDC or 4 20 mA which correlate to a uni or bi directional pressure range from 0 0 1 up to 0 40 of water column depending on your model selection Each unit has up to 8 field selectable uni or...

Страница 2: ...osure Press the rubber washer against the enclosure see FIGURE 3 Tubing Setup When Pitot Tube is Installed Units will be shipped with silicone tubing attached to the high and low pressure barb fitting...

Страница 3: ...ACTransorb TransientVoltageSuppressor ACI Part 142583 or diode placed across the coil or inductor The cathode or banded side of the DC Transorb or diode connects to the positive side of the power supp...

Страница 4: ...t The Zero adjustment must be performed with NO pressure applied to either side of the sensor Remove the tubing connected to the H High and or L Low pressure fittings Push ZERO button for more than th...

Страница 5: ...inWC 10V UNI 1 2 3 4 5 0 to 40 inWC ON 1 A Po 5V BI 2 B inWC 10V UNI 1 2 3 4 5 0 to 10 inWC ON 1 A Po 5V BI 2 B inWC 10V UNI 1 2 3 4 5 1 to 1 inWC ON 1 A Po 5V BI 2 B inWC 10V UNI 1 2 3 4 5 40 to 40...

Страница 6: ...not take place until power is cycled Out Of Range OUT OF RANGE icon will be on when differential pressure is over or under the minimum or maximum pressure range selected If a DLP unit is outputting O...

Страница 7: ...Retardant Polycarbonate UL94 5VA Finger Pushbutton Spring Terminal Blocks accepts 16 24 AWG wires WatertightCordgripInstalled 1 2 NPTConduitfittingsacceptedwhenCordgripremoved Nickel Plated Brass or S...

Отзывы: