Installation and Operation Instructions 

                                                                                                                             Part #A/MCS, A/MSCS  

 
 
 

 

AUTOMATION COMPONENTS, INC                                                                                                                                                                                 Version : 1.0  
2305 Pleasant View Road                                                                                        Page 1 of 3                                                                                              I0000557     
Middleton, Wisconsin 53562 (888) 967-5224 

www.workaci.com

                                                                                                                                                   

Please Read Instructions Carefully Before Installation!

 

 

 Safety 

 

 

This product is not intended to be used for Life or Safety applications. 

 

This product is not intended for use in any hazardous or classified locations.

 

Disconnect and lock out all power sources before installation as severe injury or death may result from electrical 
shock due to contact with high voltage wires. 

 Installation 

Make sure that all installations are in compliance with all national and local electrical codes. Only qualified individuals that are 
familiar with codes, standards, and proper safety procedures for high-voltage installations should attempt installation.   The current 
switches will not require external power, since the power for the current switch is induced from the conductor being monitored. 

 
 
 

The A/MCS and A/MSCS Current Switches should be used on 

Insulated Conductors Only

!  The current switch may be mounted 

in any position using the (2) #8 x 3/4” Tek screws and the mounting holes in the base.  Leave a minimum distance of  
1” (3 cm) between the current switch and any other magnetic devices such as contactors and transformers. 
 

#8 x 3/4" Tek Screw

(Qty. 2/Unit)

 

                                                     

Figure 1: A/MCS                                        Figure 2: A/MSCS 

 

 

For applications in which the normal operating current is below the 0.20 Amps (A/MCS) or 0.55 Amps (A/MSCS) 
trip point

 (See Figure 3 below

), the conductor being monitored may be looped through the sensor 4 times giving you a total 

 operating current of 4X the original current.  

Example

: A small fan operating at 0.2A should be wrapped through the sensor 

4 times to give you a total operating current of 0.8Amps flowing through the A/MCS or A/MSCS. 

 

 

 

Figure 3: Wires Through Sensors 

 