For applications in which the normal operating current is greater than 150 Amps or for conductor diameters larger than 0.530” 
(1.35 cm) in diameter, an external 5 Amp Current Transformer must be used as shown in 

Figure 4 below

.  

Remember that the 

secondary of the 5A CT must be shorted together before the power may be turned onto the monitored device.

 

 

In

sula

te

d

Example: For currents up to 600 Amps
                (and not below 70 Amps (A/MCS-A)
                or 95 Amps (A/MSCS-A), where
                Current Transformer (C.T.)
                secondary falls below 1 Amp
                use a 600:5 ratio C.T. as shown:

Nut

Cond

uctor

600:5 Ratio 5A C.T.

Wire

 

Figure 4: Current Transformer 

 

 Wiring 

ACI recommends the use of a two conductor 16 to 22 AWG shielded cable or twisted pair 

copper wire only

 for all current switch 

applications.  A maximum wire length of less than 30 meters (98.4 feet) should be used between the A/MCS-A and A/MSCS-A 
current switches and the Building Management System or controller.  

Note:

  

When using a shielded cable, be sure to connect 

only (1) end of the shield to ground at the controller.  Connecting both ends of the shield to ground may cause a ground loop.

  

When removing the shield from the sensor end, make sure to properly trim the shield so as to prevent any chance of shorting. The 
current switch output terminals represent a solid-state switch for controlling both AC and DC loads and is not polarity sensitive.  
The recommended torque to be used on the terminal block connections is 0.67 Nm or 5.93 in-lbs...  The aperture (hole) size of the 
current switch is 0.53” (1.35 cm) and will accept a 1 AWG maximum wire diameter. 

 Operating Specifications 

 

 
See 

Figure 5

 and 

Figure 6

 for two different current switch applications using your Building Management System (DDC/PLC 

Controller).  

Figure 5

 is showing the use of the Adjustable Current Switch as a Digital Input to your DDC Controller, whereas 

Figure 6

 is showing you how to use the Adjustable Current Switch in conjunction with your building management system to  

monitor belt loss on a motor.

  

 

 

System

Building Management

Digital Input #1

24 VAC

Line

120 VAC

24 VAC Coil

(Status)

Contactor)

Transformer

(Relay Coil or

DO

Relay / Contactor

DDC Controller

DI

 

                             Figure 5: Digital Circuit                                                                 Figure 6: Analog Circuit 


ACI Model # 

Adjustable Trip 

Point 

Output Switch Rating 

Max. Sensing 

Current Voltage 

Max. Continuous 

Current  

Max. Current for  

6 seconds 

Max. Current for  

1 second 

A/MCS-A 

0.32 - 150 Amps 

1.00 Amp @ 36 VAC/VDC 

600 VAC 

158 Amps 

240 Amps 

600 Amps 

A/MSCS-A 

0.70 - 150 Amps 

1.00 Amp @ 36 VAC/VDC 

600 VAC 

158 Amps 

240 Amps

 

600 Amps 