aci A/CTE2 Series Скачать руководство пользователя страница 4

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

Version: 8.0

I0000790

TROUBLESHOOTING

PROBLEM

No reading

Erratic readings

Inaccurate readings

Current Sensor is operating at a 
low-level current or failing to operate 
within the accuracy specifications.

SOLUTION(S)

- Verify that there is current flowing through the conductor being monitored with a 

clamp-on current probe.  The power for the current sensor is induced from the conductor 

being monitored.   

- Check the polarity of the circuit.

- Verify that the terminals are screwed down, wires are firmly in place.

- Disconnect the wires from the current sensor output.  Measure the voltage across the 

current sensor output with a Voltmeter to verify that the sensor is working properly.

- Verify that the wires are terminated properly.

- In areas of high RF interference, shielded cable may be necessary to stabilize signal.

- If you suspect that the current sensor is not reading within the accuracy specifications, 

please contact the factory for assistance.

-Visually check the mating parts of the core to ensure there is no debris between the split 

  contacts. See 

Figure 2

.

-Remove all debris or dust manually and close the current sensor. 

-Continue to retest the sensor in your application. 

STANDARD ORDERING

Model #

A/CTE2-50
A/CTE2-150
A/SCTE2-50
A/SCTE2-150
A/SCTE2-250
A/CTV2-50
A/CTV2-150
A/SCTV2-50
A/SCTV2-150
A/SCTV2-250

Item #

142389
142388
142385
142384
142383
142387
142386
142382
142381
142380

Selectable Ranges

0 to 10/20/50A
0 to 50/100/150A
0 to 10/20/50A
0 to 50/100/150A
0 to 100/200/250A
0 to 10/20/50A
0 to 50/100/150A
0 to 10/20/50A
0 to 50/100/150A
0 to 100/200/250A

Measurement

Average
Average
Average
Average
Average
Average
Average
Average
Average
Average

AC Waveform

Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal
Pure Sinusoidal

Output Signal

0 to 5 VDC
0 to 5 VDC
0 to 5 VDC
0 to 5 VDC
0 to 5 VDC
0 to 10 VDC
0 to 10 VDC
0 to 10 VDC
0 to 10 VDC
0 to 10 VDC

Solid-Core

Split-Core

Содержание A/CTE2 Series

Страница 1: ...nd split core versions which also includes a Patented 35 mm Din Rail mounting foot for easy installation in panel mount applications The solid core versions are a great choice for new installations or...

Страница 2: ...ent sensor as shown in Figure 2 Press down firmly on the cover to close the current sensor An audible click will be heard as the tab slides over the tongue on the base CAUTION Mating surfaces of the m...

Страница 3: ...When using a shielded cable be sure to connect only 1 end of the shield to ground at the controller Connecting both ends of the shield to ground may cause a ground loop When removing the shield from...

Страница 4: ...ent sensor is not reading within the accuracy specifications pleasecontact thefactoryfor assistance Visuallycheck thematingpartsofthecore to ensure there is no debris between the split contacts SeeFig...

Страница 5: ...f Selected Range A SCTV2 Series 0 to 10A Range Only 2 from 5 to 100 of Selected Range A SCTV2 Series All Other Ranges 1 from 5 to 100 of Selected Range 300 mS Rise and Fall Times 0 75 19 05 mm 35 mm U...

Страница 6: ...NOTES Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 6 Version 8 0 I0000790...

Страница 7: ...NOTES Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 7 Version 8 0 I0000790...

Страница 8: ...c 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page...

Отзывы: