 Troubleshooting 

 

Problem

 

Solution

 

No reading 

- Confirm that you have +13.5 to 30VDC in series with the current sensor output terminals and  
  the analog input of the control panel. 
- Check the polarity of the circuit. 
- Verify that the terminals are screwed down, wires are firmly in place. 
- Disconnect the input to the control panel and then insert a current meter (mA range) in series  
  with the current sensor output to verify that the circuit is working properly. 

Erratic readings 
 

- Verify that the wires are terminated properly. 
- Check that the +13.5 to 30VDC input is clean.  In areas of high RF interference, shielded cable  
  may be necessary to stabilize signal. 

Inaccurate readings 

- If you suspect that the current sensor is not reading within the accuracy specifications, please  
  contact the factory for assistance. 

Current Sensor is operating at 
a low-level current or failing 
to operate within the accuracy 
specifications. 

-Visually check the mating parts of the core to ensure there is no debris between the split  
  contacts. 

See Figure 2

-Remove all debris or dust manually and close the current sensor.  
-Continue to retest the sensor in your application.  

 

 Current Conversion Formulas 

 

To convert the current sensor output signal to a current reading. 

 

 

4-20mA output to Current reading  

(4mA = 0 Amps and 20mA = 250 Amps for 

A/CTA2-250

 

 

Example: 12mA current sensor output signal  

 

 

Total Span = 250 Amps 

 

 

Multiplier = 20mA-4mA/Total Span = 0.064 

 

 

(12mA-4mA)/0.064= 

125 Amps 

 