Mounting of ACDC Surge Protectors
ACDC Surge Protectors
-
Series have to be installed at ENTRY POINT
the Main
Distribution Boards (MDB) or
internal Sub Distribution Boards (SDB) right in front of the input power to the device that should be protected The ACDC Surge Protector
could be install in series or parallel configuration depending of total load per phase (>100A<).
- If the load per phase is <100A the ACDC Surge Protector
install in SERIES configuration.
- If the load per phase is >100A the ACDC Surge Protector must be installed in PARALLEL configuration.
Type-PI 3/3 - M Red
before
Power
or
.
have to be
ed
Only in SERIES configuration all nine (9) protection stages are in function.
ACDC Surge Protectors are designed to fixed to the wall
.
2
2
1.
If the the load per phase is <100A, our RECOMMENDATION is to install the surge protector in SERIES configuration
because only in this state your electrical devices will be fully protected.
If the total load per phase is >100A and ACDC Surge Protector is installed in PARALLEL configuration our
RECOMMENDATION is to install another ACDC Surge Protector in SERIES configuration (
Sub Distribution Board),
downstream power grid where the load per phase drops bellow 100A,
before
Condition for Installations:
Mounting:
Terminal and Wire size:
During the installation please check:
with screws
Each terminal is designed to accept wire sizes from 4mm to 25mm solid or stranded conductor. The wire insulation should be stripped back
8mm
The voltage of the ACDC Surge Protector matches actual system voltage.
2. All conductors are in accordance with the appropriate installation drawings.
THIS UNIT SHOULD BE INSTALLED AND SERVICED ONLY BY QUALIFIED PERSONNEL.
Before installing the ACDC Surge Protector, AC power must be OFF.
CORRECT INSTALLATION - THE LIGHTS GREEN AND YELLOW ARE LIT
TROUBLESHOOTING - IF THE RED LED IS BLINKING THE GROUND WIRE IS NOT CONNECTED OR THE GROUND OF THE
POWER GRID SYSTEM IN NOT WELL PERFORMED
- rovides adequate electrical and safety protection
- Prevents the ingress of moisture and water
- Allows operating diagnostic status to be inspected
p
.
.
:
.
.
..
DANGER
CAUTION
!
!
CAUTION
!
!
CAUTION
!
!
Mounting of Protectors
Sur
Sur e
G
MULTI-STAGE SURGE PROTECTION