Accutrol ZPS-H Скачать руководство пользователя страница 4

www.accutrolllc.com

 

 

 

 

4

 

 

ZPS-H QUICK START GUIDE Rev. L    11/4/2020

 

 

 

 

2e.  Adjusting the Set Points and Delays using Insight

 

  
After the controller is tuned and operating at normal velocity set point, the technician should configure DI#1 as Normally 
Closed, and set the delay period so the AVC as a fume hood controller switches set points safely according to the 
customer’s requirements. These adjustments are made in the 

Insight 

software by pressing the MODE button on the 

Airflow Setpoint gauge and then select “Configure Control Setpoints” as shown below. 

  
 

 

 

 

 

 

 

 
 

 

 
 
In the Configure Control Setpoint window, Select Enable next to DI-1 and a drop-down table will appear.  This is where 
you select which velocity setpoints are used for each position of Digital Input #1.  Since we are only using DI #1, there 
are only two conditions to be concerned about, open and closed. 
  
Based on the wiring instructions provided in the previous section, the ZPS-H contacts will be closed when presence is 
not  detected  in  front  of  the  fumehood  and  open  when  presence  is  detected.  For  this  example,  the  Face  Velocity 
Setpoints will change from 100 FPM to 80FPM when presence is no longer detected at the fume hood. 
 
Note the 300 second out delay prevents the Fume Hood Controller from changing its face velocity setpoint to 80 fpm 
until five minutes after the ZPS-H detects no movement. 

2f. Verification 

Once the ZPS-H is set up, verify that the Digital Input of the AVC is configured to trigger the setback to lower flow and 
test entire system by walking in front of the hood to verify that the hood responds appropriately.

 

Repeat walking test to 

verify proper operation. (You may have to stand out of the area in front of the hood to give time for the AVC Fume Hood 
Controller to revert to the Setback of the reduced velocity setpoint.) 

When you are satisfied with the operation of the sensor, replace cover by engaging the cover on left side first then snap 
down.  Be careful not to change the position of the swivel sensor and move the sensor wires out of the way so they are 
not pinched.  The cover will not change the sensitivity of the ZPS-H. 

 

   Replacing the Cover 

  
  
  

  

  

For additional technical support please call Accutrol at 203-445-9991. 

Caution: Be sure to have a 

sufficient time delay to prevent the valve 
from entering unoccupied mode while 
the hood is in use

Отзывы: