Accutrol AVC5000 Скачать руководство пользователя страница 2

2

 

 

 

Connect PC to AFM5000 

 

 
 

 
 
 

 

 
 
 
Verify the 
Mode of 

Operation is 

SETPOINT 

MODE

 

 
 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
  
(Jumper position) 
 
 
 
 
In the 

MODE 

OF 

OPERATION window above: 



Select whether the set point is 

coming from AI-1, Dry Contact, or BACnet Communications. 



If ANALOG (AI-1), Select Analog signal (be sure to 
configure input at AVC5000 by moving JP-3 as described). 



For AFM5001, ANALOG AI-1 is set up for Resistor (R) 



Select the range of the set point signal in the bottom 
window. 

 

 

 

 

 
 

 
In the CONTROL OUTPUT window 
above: 



With the OVERRIDE 
button, Select 
MANUAL and a value 
in % to force the 
actuator to a specific 
position, (the gage 
face will go red).

 



Go to OVERRIDE and select AUTO to release control, (the 
gage face will go back to normal). 

 

 
 
 
In the TUNING window above: 



Adjust the Deadband%, Gain (P) and the 
Integral (I) to address tuning.

 



Adjust the OFFSET or differential in a 
tracking valve application 

 

 

 

 

 

 

 
 
In the ALARM window above: 



Enable and Disable Alarms

 



Select Airflow Volume Alarm or Set Point Deviation 

Alarm

 



Enter values and delays

 

 

 
In the A0-1 and AO-2 Window on the right: 



Configure the AO Signals to Voltage or Current 



Set either for Volume or Output position 



Manually operate the Outputs to a value for trouble shooting  

 
 
 

Remove the rubber port plug 
to access the AFM5000 USB 
Port. 

Plug USB Mini Cable from PC into 
the AFM5000 USB Port. 

Open the AVC Insight 
UI Program. 