Quick Start Guide 

AFM5000

  

Air

 

Flow

 

Monitor

 

for

 

AVC5000

 

Controller

                     

Covers

 

Models:

 

AFM5000

xxx

 

&

 

AFM5001

xxx

 

This Quick Start Guide provides the basic steps required 
for the installation, wiring and start-up of the AFM5000 
and the AFM5001 Air Flow Monitors, when used with the 
AccuValve AVC5000 controller.  For details, refer to the 
individual product Submittal Drawings, User Manuals and 
Job-Specific Requirements.  

APPLICATION 

The AFM5000 connects directly to the 
AccuValve AVC5000 control module and 
gives the user a local Airflow Volume 
Display and Alarm Indication. The 
AFM5000 also gives the user the ability 
to “plug in” to the AVC5000 controller 
remotely to monitor and adjust the 
AVC5000 using Accutrol’s Insight User 
Interface from a convenient location.  
The AFM5000 can also be provided with 
a set point adjustment dial to change the 
airflow set point in the AVC controller. 

WIRING 

Route the Monitor Cable from the back of the electrical box to 
the location of the AVC5000 control enclosure and insert the 
Monitor Cable  into the  Monitor Cable receptacle.  Anchor the 
cable to the strain relief with a cable tie. 

For applications using the AFM5001, the yellow pig tail on the 
Monitor Cable is connected to AI-1 (+).  The jumper for AI-1 is 
set to “R” to configure the input. 

INSTALLATION

 

The AFM5000 is designed to be installed into a single-gang 
electrical box, with the minimum internal dimensions of 3.825”H 
x 2.35”W to  accommodate the set point adjustment knob on the 
AFM5001 and the additional wires. 

 
Once the properly sized box is 
installed, route the Monitor Cable 
into the electrical box and use a 
strain relief to prevent the cable 
from being damaged. In the case 
where an AFM5001 is installed, 
connect the yellow pigtail on the 
end of the cable with a wire nut 
to the yellow wire that extends 
from the back of the display 
module. 

Secure the AFC5000 to the 
electrical box using the two 
screws provided. 
 

 

Connections to the AVC5000 Control Module will vary 
depending on the application requirements. The  diagram 
below is provided as a general reference only.  For detailed 

wiring requirements, refer to the job specific submittal wiring 
diagrams and AVC5000 Manual. 

 
START UP 

Before proceeding with start-up, verify the following 
items have been completed: 



All installation has been completed and verified. 



All wiring has been completed and verified. 



Power is present at the AVC5000 and verified to spec. 



System is operating with static pressure control. 



The configuration PC has Insight loaded and operational. 

AFM

 

QUICK

 

START

 

GUIDE—NOVEMBER

 

2015

 

www.accutrolllc.com

   

                                      

WIRING

 

DETAIL

 

for

 

AFM5001

XXX

  