Installation & Operation Manual - Model AVC4000
Contents of this Manual are Subject to Change Without Notification
Page 23
Output Source Selected:
MANUAL
sets the AO to correspond
with the value entered in the box after
the “=” sign
Output Full Scale: Sets the full-scale range of the AO
Signal & corresponding AO Gauge.
Output Signal Type: Select from dropdown list. For this
example, 10v corresponds full scale.
Setting Manual = 5 with the Output Full
Scale set to 10.00 will result in AO = 5v.
6.5.6 Control Output Gauge
The Control Output Gauge displays the Control Output % and provides a means for overriding
the control-loop enabling direct command of the actuator.
6.5.6.1
Control Output Override
To override the control to Manual;
1.
Select the OVERRIDE button at the bottom of the Control Output Gauge.
2.
Select “Manual” and enter the desired control output % to position the actuator.
3.
Select Update Controller.
NOTE:
Because the Override function is not intended to be used for extended durations the
manual override value is not saved to
the controller’s nonvolatile memory
. A power cycle will
release the control to Auto.
To return to Auto Control;
4.
Select the OVERRIDE button at the bottom of the Control Output Gauge.
5.
Select “Auto”.
6.
Select Update Controller.
Before
After
After
Before