For battery connection, please mind the recommendation of your battery
manufacturer first. We strongly recommend connecting a fuse to the positive
conductor. For recommended sizes, please refer to below indicated table:
Model No.
Fuse (A)
SI1500-24110/24230
100
SI1500-48110/48230
50
WARNING:
Wrong polarity connection may damage the inverters without the external fuse
protection.
WARNING:
Make sure the connections are very well made, or overheating and fire may
occur.
WARNING:
The installation of a fuse must be on the positive conductor. Otherwise it may
cause damage to the inverter and will void the warranty.