15-4 System Maintenance & Testing LC 1200 Manual
1. Notify staff and security that you will be
testing zone performance and alarms
will
be generated. They should pay
special attention to traffic during this
time.
2. While not in the zone, use a TAD to
activate the test Tag.
3. Approach the door.
4. The Lock should engage.
NOTE:
The LED on the Lock will turn
from green to red when the Lock is
engaged.
5. Remember once the Lock is engaged, in
order to open the door, you have invoke
the Delayed Egress Circuitry feature. To
do this, press on the door for the
duration of the nuisance delay (
1 to 3
seconds
) and the delayed egress
countdown (
15 to 30 seconds
) then the
Lock will disengage and you can open
the door.
NOTE:
During the delayed egress
countdown the Lock’s piezo will beep.
After you open the door, the Lock’s
piezo will sound continuously.
6. Record the results (pass or fail).
7. If the test fails to cause an alarm:
a. Notify staff and security of the
vulnerable area.
b. Check for visible damage or
tampering to the zone equipment.
c. Have a maintenance technician
verify power to the zone equipment.
d. Have a maintenance technician
verify the FPI is set properly.
e. Call your Accutech Representative.
9. To reset the zone, enter a Keypad reset,
deactivate the test Tag, close the door
completely, and, if necessary, clear the
alarm on the PC.
Zone, Hallway Test
Two conditions are required to generate an
alarm at a hallway zone: Tag detection and PIR
detection. This test will evaluate this operation.
1. Notify staff and security that you will be
testing zone performance and alarms
will
be generated. They should pay
special attention to traffic during this
time.
2. Using a TAD, activate the test Tag.
3. Enter the monitored hallway zone and
move in the path of the PIR. An alarm
should be generated and an alarm may
sound.
4. Record the results (pass or fail).
5. If the test fails to cause an alarm:
a. Notify staff and security of the
vulnerable area.
b. Check for visible damage or
tampering to the zone equipment.
c. Have a maintenance technician
verify power to the zone equipment
d. Call your Accutech Representative.
Содержание 800121
Страница 1: ...LC 1200 Manual 800 356 2671 Accutech www accutech ics com...
Страница 2: ......
Страница 3: ...LC 1200 Manual 800 356 2671 Accutech www accutech ics com Version 1 00 October 12 2004 DOC 970015...
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 20: ......
Страница 21: ...LC 1200 Manual Chapter 2 The LC unit...
Страница 22: ......
Страница 33: ...LC 1200 Manual Chapter 3 Tags TAD Part s 77L016 67L016 660021...
Страница 34: ......
Страница 43: ...LC 1200 Manual Chapter 4 The Magnetic Switch Part 650514...
Страница 44: ......
Страница 49: ...LC 1200 Manual Chapter 5 Passive Infrared Reader PIR Part 300302...
Страница 50: ......
Страница 54: ...5 4 Passive Infrared Reader PIR LC 1200 Manual Figure 5 4 Wiring the PIR...
Страница 56: ......
Страница 57: ...LC 1200 Manual Chapter 6 The Keypad Part 650202...
Страница 58: ......
Страница 68: ......
Страница 69: ...LC 1200 Manual Chapter 7 Push Button Override PBO Part 700022...
Страница 70: ......
Страница 74: ...7 4 Push Button Override PBO LC 1200 Manual Figure 7 2 Wiring the PBO to the LC unit...
Страница 75: ...LC 1200 Manual Chapter 8 External Sounders Part s 700216 300150...
Страница 76: ......
Страница 80: ......
Страница 81: ...LC 1200 Manual Chapter 9 Magnetic Locks Part s 700218 700228...
Страница 82: ......
Страница 86: ...9 4 Magnetic Locks LC 1200 Manual Figure 9 1 3101 Magnetic Lock PCB...
Страница 87: ...LC 1200 Manual Magnetic Locks 9 5 Figure 9 2 Wiring the 3101 Magnetic Lock...
Страница 91: ...LC 1200 Manual Magnetic Locks 9 9 Figure 9 4 Wiring a 3000 Series Magnetic Lock...
Страница 92: ......
Страница 93: ...LC 1200 Manual Chapter 10 Elevator Deactivation Part 700027...
Страница 94: ......
Страница 98: ...10 4 Elevator Deactivation LC 1200 Manual Figure 10 2 Wiring Elevator Deactivation...
Страница 99: ...LC 1200 Manual Chapter 11 Automatic Door Deactivation Part 700033...
Страница 100: ......
Страница 102: ...11 2 Automatic Door Deactivation LC 1200 Manual Figure 11 1 Wiring for Automatic Door Deactivation on Tag Detection...
Страница 103: ...LC 1200 Manual Chapter 12 Fire Panel Interface FPI Part 700013...
Страница 104: ......
Страница 106: ...12 2 Fire Panel Interface FPI LC 1200 Manual Figure 12 1 The FPI with cabinet...
Страница 109: ...LC 1200 Manual Chapter 13 Timer Part 700018...
Страница 110: ......
Страница 114: ......
Страница 115: ...LC 1200 Manual Chapter 14 Alert Panels Part s 700080 700050 700052...
Страница 116: ......
Страница 119: ...LC 1200 Manual Alert Panels 14 3 14 2 Wiring a SAP or GDP FPI also shown...
Страница 121: ...LC 1200 Manual Chapter 15 System Maintenance Testing...
Страница 122: ......
Страница 130: ......
Страница 131: ...LC 1200 Manual Chapter 16 FAQ Troubleshooting...
Страница 132: ......
Страница 136: ......
Страница 137: ...LC 1200 Manual Appendix A Component Cut Sheets...
Страница 138: ......