Accurex XRV-25-5I Series Скачать руководство пользователя страница 20

Packaged Rooftop Ventilator

20

CAUTION

When operating conditions of the fan are to be 
changed (speed, pressure, temperature, etc.), consult 
manufacturer to determine if the unit can operate 
safely at the new conditions.

Supply Fan (Plenum Type)

The unit contains one plenum supply fan located on 
the end of the unit opposite the outdoor air intake and 
may optionally have a relief air blower which is referred 
to as an exhaust blower in this document. Efficient fan 
performance can be maintained by having the correct 
offset. 

Refer to the respective Installation, Operation and 
Maintenance Manual shipped with this unit for additional 
start-up and maintenance information regarding the 
plenum fan.

Start-Up Components

Fan

The fan should be checked for free rotation. If any 
binding occurs, check for concealed damage and 
foreign objects in the fan housing.

Inlet 

Cone

Wheel

Offset

Offset:

 Proper offset, or overlap, is 

adjusted by loosening the wheel hub 
from the shaft and moving the wheel 
to the desired position along the shaft. 
The transition between the inlet cone 

and the wheel should 
be as shown; there is 
a smooth feel to the 
profile when moving 
one component to the 
other.

Supply/Exhaust Fan

The optional exhaust fan is a direct-drive plenum type. 
Fan speed is controlled by a VFD which, in turn, is 
controlled by the microprocessor controller or by an 
external signal. Motor speed will be set on the VFD 
during the unit Test and Balance, but after that, the 
VFD will not normally be changed. Always check the 
motor amperage rating shown on the motor nameplate 
when changing the fan RPM. All access doors must be 
installed except the control center door.

Vibration

Excessive vibration may 
be experienced during 
initial start-up. Left 
unchecked, excessive 
vibration can cause a 
multitude of problems, 

including structural and/or component failure. The most 
common sources of vibration are listed.

Many of these conditions can be discovered by careful 
observation. Refer to the Troubleshooting section of 
this manual for corrective actions. If observation cannot 
locate the source of vibration, a qualified technician 
using vibration analysis equipment should be consulted.

Generally, fan vibration and noise is transmitted to other 
parts of the building by the ductwork. To eliminate this 
undesirable effect, the use of flexible connectors is 
recommended.

Discharge Air Temperature Sensor

Units are supplied with a Discharge Air Temperature 
Sensor that is to be field-installed prior to unit start-
up. The sensor is to be installed at least three duct 
diameters downstream of the heat exchanger. 
The sensor must be connected directly to the 
microprocessor controller. All other sensors and 
low voltage devices are to be 
connected to the low voltage 
terminal strip in the control center. 
The discharge air sensor is 
shipped loose and can be found 
in the unit’s control center. See 
the unit-specific wiring diagram 
for connection locations.

Optional Hot Gas Bypass Valve  

(standard scroll)

To adjust, connect a pressure gauge to the suction line 
and block the entering air to the evaporator coil. The 
valve should begin to open when the suction pressure 
drops to approximately 115 PSIG for R-410A (the valve 
will feel warm to the touch). Adjustments are made by 
first removing the cap on the bottom of the valve and 
then turning the adjusting stem clockwise to increase 
the setting pressure (counterclockwise to decrease). 
Allow several minutes between adjustments for the 
system to stabilize. When adjustment is complete, 
replace the cap on the valve.

Vibration Causes

Off axis or loose components
Drive component unbalance
Poor inlet / outlet conditions
Foundation stiffness

Typical Discharge Air 

Temperature Sensor

Fan Wheel Rotation Direction

Check for proper wheel rotation by momentarily 
energizing the fan. Rotation is determined by viewing 
the wheel from the drive side and should match the 
rotation decal affixed to the fan housing.

If the wheel is rotating the wrong way, direction can be 
reversed by interchanging any two of the three electrical 
leads. Check for unusual noise, vibration or overheating 
of the bearings. Refer to the Troubleshooting portion of 
this manual if a problem develops.

Fan Size

Offset  

(inches)

Tolerance 

(inches)

ER35C

5/32

± 1/32

ER45C

3/16

± 1/32

ER50C

13/64

± 1/32

ER56C

1/4

± 1/32

Содержание XRV-25-5I Series

Страница 1: ...en servicing the unit the internal components may be hot enough to cause pain or injury Allow time for cooling before servicing Only quali ed personnel should install and maintain this system Personne...

Страница 2: ...VFD Sequence 13 OA and Recirc Air Damper Sequence 13 Exhaust Fan Only Power 13 Vapor Tight Lights 13 EC Condenser Fans 14 Airflow Monitor 14 Dirty Filter Sensor 15 Microprocessor Control 15 Unoccupie...

Страница 3: ...ove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose to permit air circul...

Страница 4: ...illed water coil Units with packaged DX are shipped fully charged with refrigerant and are ready for operation upon arrival Heating There are three different optional heat sources that can be ordered...

Страница 5: ...denser Coils optional Outdoor Air Damper Coils optional Recirculating Damper Main Control Center Furnace Vest Plate and Furnace Control Center optional Outdoor Air Filters Weatherhood Filters metal me...

Страница 6: ...ce Optional Electric Heater 4 Electrical 5 Supply Blower 6 Coil 7 Filters Unit Size Nominal tonnage tons Height H Width W Length L Intake A Condensing Section B Nominal weight lbs Outdoor Intake Suppl...

Страница 7: ...nit Weights Dimensions section of this manual 3 Unit must be lifted by all lifting lugs provided at top of unit 4 Spreader bars must span the unit to prevent damage to the cabinet by the lift cables 5...

Страница 8: ...Shim the curb as required to level Install gasketing on top surface of curb provided by others 3 Install Ductwork Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines...

Страница 9: ...There are three penetrations into the cabinet that are required one for high voltage supply wiring one for low voltage control wiring and one for either gas supply or high voltage supply wiring for a...

Страница 10: ...aking the weld between coil connection and header 2 Connect the water supply to the bottom connection on the air leaving side and the water return to the top connection on the air entering side Connec...

Страница 11: ...ater disconnect and must be compatible with the ratings on the nameplate supply power voltage phase and amperage Consult ANSI NFPA 70 and CSA C22 1 for proper conductor sizing Provide the Opening s fo...

Страница 12: ...ontroller Optional Indirect Gas Fired Furnace Note In some models two furnaces are installed to provide greater output When two furnaces are installed they are in parallel and both will operate at the...

Страница 13: ...ain room air temp at a desired set point Optional 0 10 VDC by others to VFD Supply fan is modulated by a 0 10 VDC eld provided by others Component Operation Exhaust Fan VFD Sequence Optional Building...

Страница 14: ...actual cubic feet per minute CFM or actual liters per second LPS on a 16 character LCD display Two con gurable analog outputs for transmitting outdoor and or exhaust air ow rate outdoor air temperatur...

Страница 15: ...or relative humidity sensor the unit can cycle on to maintain unoccupied room set points if there is a call for unoccupied heating cooling or dehumidi cation During the unoccupied mode the supply and...

Страница 16: ...ble and is located on the side of the evaporator coil and can be accessed through the coil access panel 13 Evaporative Coil 14 Low Limit Pressure Switch The switch is installed on the suction line and...

Страница 17: ...is below 40 F Do not short cycle the compressor Allow 5 minutes between on cycles to prevent compressor damage DX system is charged with refrigerant Start up must be performed by EPA Certified Technic...

Страница 18: ...wer supplied to it 24 hours prior to start up If start up is scheduled in 24 hours unlock the disconnect power and energize unit Compressor shipping brackets are removed if provided SPECIAL TOOLS REQU...

Страница 19: ...r Air Temperature Deg F Outdoor Air Relative Humidity RH Return Air Temperature Deg F Return Air Relative Humidity RH Compressor 1 Compressor 2 Compressor 3 Compressor 4 L1 Amps Amps Amps Amps L2 Amps...

Страница 20: ...vation cannot locate the source of vibration a quali ed technician using vibration analysis equipment should be consulted Generally fan vibration and noise is transmitted to other parts of the buildin...

Страница 21: ...unit using the power disconnect s a Recycling of the power resets the manual override values that were set during the calibration Air ow Monitor For additional information on how to navigate through t...

Страница 22: ...as a voltage spike occurs the VFD will go into alarm and will not reset until a hard restart is performed See the unit speci c manufacturer s manual supplied with the unit VFDs are located in the mai...

Страница 23: ...er motor System static pressure too high Improve ductwork to eliminate losses using good duct practices Blower speed too low Check maximum motor RPM and compare with catalog data Verify that external...

Страница 24: ...or reason and repair Replace fuse after correcting problem Low line voltage Check line voltage If more than 10 from compressor marking correcting is necessary Compressor motor protector open Motor the...

Страница 25: ...f compressor is hot allow compressor to cool for two hours Recheck for open circuit Improper refrigerant charge Check subcooling Improperly wired Review wiring schematics Loose wiring Check all connec...

Страница 26: ...Check subcooling Remove excess refrigerant Non condensable in system Remove non condensable from system Dirty condenser coil Clean condenser coil Condenser fan not running or running backwards Check e...

Страница 27: ...back Check thermal expansion valve setting Check for refrigerant overcharge Check crankcase heater operation Reheat ush cycle inadequate Contact factory Not enough cooling or lack of cooling Refriger...

Страница 28: ...ebris in the air which can be drawn into the lters and the coils they should be checked more frequently If the system is being used for only a few hours per day the frequency may be reduced Use the ma...

Страница 29: ...integral metal grid Two acceptable lter replacements are Aerostat Series 400 or Farr 30 30 Filters upstream of the coil should be checked regularly If the lters are dirty they should be cleaned or re...

Страница 30: ...V 45 300 14 8 23 3 38 1 44 1 6 6 6 400 6 6 6 500 14 9 23 6 25 2 57 1 6 6 6 B A C D 500MBH 300 400MBH A B C D 200 300MBH 100 150MBH C A B D C A B D COMBUSTION AIR INLET EXHAUST OUTLET IG FURNACE ACCESS...

Страница 31: ...5 12 5S 3550 XRV 25 15I 3775 XRV 25 15D 3775 XRV 25 15S 3775 XRV 45 15I 4100 XRV 45 15D 4100 XRV 45 15S 4100 XRV 45 17 5I 4650 XRV 45 17 5D 4650 XRV 45 17 5S 4650 XRV 45 20I 5300 XRV 45 20D 5300 XRV 4...

Страница 32: ...______________________________________ _________________________________________________ Date ___________________Time _____________ AM PM Notes ___________________________________________ ____________...

Отзывы: