Accurex Vari-Flow Скачать руководство пользователя страница 2

2

Vari-Flow Air Management System

INDOOR — 

The ideal environment for the storage of 

units and accessories is indoors, above grade, in a 
low humidity atmosphere which is sealed to prevent 
the entry of blowing dust, rain, or snow. Temperatures 
should be evenly maintained between 30°F (

-1°C

) and 

110°F (

43°C

) (wide temperature swings may cause 

condensation and “sweating” of metal parts). All 
accessories must be stored indoors in a clean, dry 
atmosphere.
Remove any accumulations of dirt, water, ice, or snow 
and wipe dry before moving to indoor storage. To 
avoid “sweating” of metal parts, allow cold parts to 
reach room temperature. To dry parts and packages 
use a portable electric heater to get rid of any 
moisture build up. Leave coverings loose to permit air 
circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off 
the floor on wooden blocks covered with moisture 
proof paper or polyethylene sheathing. Aisles between 
parts and along all walls should be provided to permit 
air circulation and space for inspection.

Inspection and Maintenance during Storage

While in storage, inspect equipment once per month. 
Keep a record of inspection and maintenance 
performed.
If moisture or dirt accumulations are found on parts, 
the source should be located and eliminated. 

REMOVING FROM STORAGE — 

As units are removed 

from storage to be installed in their final location, 
they should be protected and maintained in a similar 
fashion, until the equipment goes into operation.
Prior to installing the unit and system components, 
inspect the unit assembly to make sure it is in working 
order.

1.  Check all fasteners, and accessories for 

tightness.

Receiving

Upon receiving the product check to make sure all 
items are accounted for by referencing the bill of 
lading to ensure all items were received. Inspect 
each crate for shipping damage before accepting 
delivery. Notify the carrier if any damage is noticed. 
The carrier will make notification on the delivery 
receipt acknowledging any damage to the product. 
All damage should be noted on all the copies of the 
bill of lading which is countersigned by the delivering 
carrier. A Carrier Inspection Report should be filled out 
by the carrier upon arrival and the Traffic Department. 
If damaged upon arrival, file claim with carrier. Any 
physical damage to the unit after acceptance is not 
the responsibility of Accurex.

Unpacking

Verify that all required parts and the correct quantity 
of each item have been received. If any items are 
missing, report shortages to your local representative 
to arrange for obtaining missing parts. Sometimes it 
is not possible that all items for the unit be shipped 
together due to availability of transportation and truck 
space. Confirmation of shipment(s) must be limited to 
only items on the bill of lading.

Handling

Handle in such a manner as to keep from scratching 
or chipping the coating. Damaged finish may reduce 
ability of unit to resist corrosion.

Storage

Units are protected against damage during shipment. 
If the unit cannot be installed and operated 
immediately, precautions need to be taken to prevent 
deterioration of the unit during storage. The user 
assumes responsibility of the unit and accessories 
while in storage. The manufacturer will not be 
responsible for damage during storage. These 
suggestions are provided solely as a convenience to 
the user.

Table of Contents

Receiving and Handling.   .   .   .   .   .   .   .   .   .   .   .   .   . 2
Installation
  Control Box Mounting . . . . . . . . . . . . . 3
  Resistive Temperature Detector .   .   .   .   .   .   .   . 3
Pneumatic Static Pressure Kit . . . . . . . . . . 4
Keypad Mounting . . . . . . . . . . . . . . . . . 4
Wiring  . . . . . . . . . . . . . . . . . . . . . . . 5
Wiring Diagrams  . . . . . . . . . . . . . . . . 6-7
Connection Checklist . . . . . . . . . . . . . . . 8
Controller Setup   . . . . . . . . . . . . . . . . . 8
Controller Display .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   9-12
Sequence of Operations  . . . . . . . . . . . .  13
Daily Operations  . . . . . . . . . . . . . . . .  14
System Optimization . . . . . . . . . . . . . .  14
Troubleshooting   . . . . . . . . . . . . . . . .  15
Warranty .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   16

Содержание Vari-Flow

Страница 1: ...ed personnel should install this unit Personnel should have a clear understanding of these instructions and should be aware of general safety precautions Improper installation can result in electric shock possible injury due to coming in contact with moving parts as well as other potential hazards Other considerations may be required if high winds or seismic activity are present If more informatio...

Страница 2: ...e bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The carrier will make notification on the delivery receipt acknowledging any damage to the product All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier A Carrier Inspection Repo...

Страница 3: ...l the lock washer and 1 1 2 inch nut on the threaded portion of the compression seals and tighten securely RING OVER 1 4 inch Compression Seal Gasket Temperature Sensor Lock Washer Nut Octagon Cover Exhaust Area Supply Area optional Sensor Install Cut Out Area Top View of Exhaust Hood 75 to 875 inch diameter hole Hood Surface OcOOca Octagon Extension 3 Place the octagon box provided over the fitti...

Страница 4: ...from the sensor in the control panel to a secure location in the space to be controlled NOTE The keypad may be factory mounted If so continue to the next section 1 For systems with remote controls or keypad a 25 ft cable is supplied to connect the keypad to the controls The cable is plenum rated and does not need to be run through conduit unless required by local codes If the keypad is to be mount...

Страница 5: ... 6 Hood Lights Relay R1 Hood Run Contact 14 11 GRN Hood Run Indicator L1 7 4 6 15 14 9 13 11 H1 Canopy Lighting circuit must not exceed 15A total curre AVPS 13 31 DI7 Fan Override 33 32 NO C PS1 PRESSURE 1 2 3 R5 Hood Light LED Relay A1 A2 R5 Hood Light LED Contact 14 11 GRN Hood Light Indicator L2 2 HL DO2 COM 44 12 AI5 1 AICOM V1 VC GGH 20 VAV Fan Mode 0 VDC Fan Auto 5 VDC Fan OFF 10 VDC Fan On ...

Страница 6: ...T4 23 22 OR R1 24 21 R4 14 11 R4 Shunt Trip Contact Closes on Shunt Trip 22 21 36 37 Fire Contact 24 VAC 24 VAC 24 VAC 24 VAC 48 49 50 51 Fire System 35 34 REMOVE JUMPER IF USED R4 Fire Shunt Trip Relay A1 A2 24 VAC 44 45 PR PR 47 46 Tempering Status Contact Closed Tempering On Open Tempering Off BL YW YW YW BR YW OR OR OR OR OR PR PR PR PR PR BL PR PR PR PR RD OR BR GN RD RD 34 31 58 59 54 55 56 ...

Страница 7: ...ay A1 A2 24 VAC 44 45 PR PR 47 46 Tempering Status Contact Closed Tempering On Open Tempering Off BL YW YW YW BR YW OR OR OR OR OR PR PR PR PR PR BL PR PR PR PR RD OR BR GN RD RD 34 31 58 59 54 55 56 57 OR RD RD R1 RD RD XT91D00 XP91D02 J1 RT RT COM 1 2 3 4 1 2 3 4 I1 I2 I3 I4 CN1 CN2 INPUTS Note 4 wire jumper assembly T5 T6 25 24 27 26 29 28 T7 T8 31 30 TB1 COM 24 VAC TB1 COM 24 VAC TB1 24 VAC O7...

Страница 8: ... up and down arrow buttons 6 To back out of any menu press the escape ESC button Controller U1 Up ESC Return Down Power to Vari Flow Cabinet Connect 120 VAC power for controls terminals H N Connect 120 VAC power for hood lights terminals H1 N1 Connect lights terminals HL N1 Power to Variable Frequency Drive s Line power to VFD input terminals L1 L2 L3 Load power from VFD output terminals T1 T2 T3 ...

Страница 9: ...o Indicates if T6 is linked to EF1 T7 to EF1 No Yes No Indicates if T7 is linked to EF1 T8 to EF1 No Yes No Indicates if T8 is linked to EF1 Temperature Sensor on EF2 T1 to EF2 No Yes No Indicates if T1 is linked to EF2 T2 to EF2 No Yes No Indicates if T2 is linked to EF2 T3 to EF2 No Yes No Indicates if T3 is linked to EF2 T4 to EF2 No Yes No Indicates if T4 is linked to EF2 T5 to EF2 No Yes No I...

Страница 10: ...onnected T3 No Yes No Indicates if T3 is connected T4 No Yes No Indicates if T4 is connected Temperature Interlock IMC Compliance Temp Interlock TempInt Enabled No Yes Yes If set to yes Temperature Interlock feature is enabled Exhaust fan will start if hood temperature exceeds the Temperature Interlock set point and will run until the hood temperature falls below set point for the off delay time S...

Страница 11: ...t Use Min Speed Set 0 100 50 The minimum output control limit for the MUA VFD or damper Must be set to a value that ensures proper design full flow CFM Adjustable from 0 to 100 Max Speed Set 0 100 100 The maximum output control limit for the MUA VFD or damper Must be set to a value that ensures proper design full flow CFM Adjustable from 0 to 100 Tempering Set 0 100 66 Minimum run percentage for t...

Страница 12: ... F The temperature at which EF4 runs at the maximum speed EF5 Low Temp F 90 F The temperature at which EF5 runs at the minimum speed EF5 High Temp F 115 F The temperature at which EF5 runs at the maximum speed Exhaust Mode Exhaust in Fire No Yes Yes Indicates the exhaust fan s will run in case of fire Fans Full Speed No Yes Indicates the operator overrode the exhaust fan to full speed operation 10...

Страница 13: ...cording to Temperature Hood Full Speed DDC Temperature Control Enabled Hood VFD Set to Full Speed 15 minute timer Full Speed Cancel Full Speed Cancel Return to System Start Stop MUA SF OA Damper Pressure Control Compare Space Static Pressure Reading with Space Pressure Setpoint 05 WC adjustable MUA SF VFD Speed Set According to Pressure OA Damper Position Set open closed Hood Running Signal Receiv...

Страница 14: ... Supply Fan Run When LED is lit the controller is commanding the supply fans to run 3 Supply Fan Heat Cool When LED is lit the supply fan is operating in heating or cooling 4 Pressure Sensor Fault When LED is lit the pressure sensor is experiencing a fault 5 Fire When LED is lit the system is operating in fire mode 6 Temperature Sensor Fault When LED is lit the controller is not receiving a correc...

Страница 15: ...onnection If fan 100 LED does not light check keypad connection Fan switch is on but fans do not turn on Broken fan belt Replace fan belt VFD fault Check VFD for faults Bad wiring connection If fan on off LED does not light check keypad connection Hood lights LED on but no lights come on Light bulbs are burned out Replace hood light bulbs Bad wiring connection If hood lights LED is lit check wirin...

Страница 16: ...nt Accurex reserves the right to change specifications without notice Product warranties can be found online at accurex com either on the specific product page or in the Warranty section of the website at Accurex com Resources Warranty Our Commitment P O Box 410 Schofield WI 54476 Phone 800 333 1400 Fax 715 241 6191 Parts 800 355 5354 accurex com ...

Отзывы: