7

Extend module

The meter has 2 current input options available for different applications.

1. Standard: 5Aac

2. Optional: 1Aac

Ground Terminal Connection

Before setting up the meter's wiring, please connect the meter's ground terminal and 

the switch gear's ground terminal together.

Auxiliary Power

The meter has 2 auxiliary power supply options available for different applications 

(aux. power supply terminals are 11, 12, 13).

1. Universal (standard): 100~415Vac, 50/60Hz; 100~300Vdc
2. Low Voltage DC Power: 20~60Vdc

Please make sure the right type before powering up the meter.

            Comm Port 

 Digital Output 

Digital Input

S

B

A

DO11 DO12 DO21 DO22 DI1

DI2

DI3

DI4

DIC

Содержание Acuvim-L Series

Страница 1: ...Appearance and Dimension Installation Method Terminals Wiring Diagram Settings Mode Communication I O Options Time of Use DIN Rail Installation Specification Acuvim L Series Quick Setup Guide...

Страница 2: ...00 3 583 35 90 10 00 0 394 14 00 0 551 35 90 91 00 3 583 38 00 1 496 7 60 0 300 1 413 1 413 50 70 1 996 Front View of the Display Meter and Remote Display Unit Gasket Side View of the Display Meter S...

Страница 3: ...r Installation 35mm rail of the DIN rail Meter Voltage Input Terminals Used for voltage input Current Input Terminals Used for current input Power Supply Terminals Used for aux power supply input Comm...

Страница 4: ...ical interference sources Meter s working temperature range is from 25 C to 70 C Meter can be installed into an ANSI C39 1 4 round or an IEC 92mm DIN square form Installation Steps 1 Meter Installatio...

Страница 5: ...4 2 Remove installation clips from the meter and insert the meter into the square or round hole from the front side Gasket Gasket Panel Panel...

Страница 6: ...ay meter and the remote display unit have the same installation method The DIN rail meter have a quite other installation method it must be installed on the 35mm rail You can references the others DIN...

Страница 7: ...erminal strips Model Acuvim BL CL DL EL KL share the same strips When the Acuvim BL is selected the strips is used as DO When Acuvim CL DL EL KL would be selected the strips are used for communication...

Страница 8: ...rminal and the switch gear s ground terminal together Auxiliary Power The meter has 2 auxiliary power supply options available for different applications aux power supply terminals are 11 12 13 1 Univ...

Страница 9: ...he meter setting screen Press H to move the flashing cursor to the right press P to decrease the number by 1 once a time press E to increase the number by 1 once a time press V A to accept the change...

Страница 10: ...ential signal B is differential signal and S is shield Up to 32 devices can be connectedon a RS485 bus The overall length of the bus cannot exceed 1200m 4000ft When multiple meters are connected seria...

Страница 11: ...ront panel control keys the meter with DIN rail mount option includes the same functions as the panel mount version The default device address the default baud rate and the default check of the DIN ra...

Страница 12: ...N wiring Installation Category III Pollution Degree 2 Metering Frequency 45 65Hz Overload 2times continuously 2500Vacpersecond norecurrence VoltagerangethroughPT 1000KV highest at primary side PT burd...

Отзывы: