Quick Start Guide
– 2 –
Mount the Device
Ground the Device
Connect Power
1.
-48 – -60 VDC
2.
DC return
3.
4.
Signal -
Warning:
For a safe and reliable installation, use only
the accessories and screws provided with the device. Use
of other accessories and screws could result in damage to
the unit. Any damages incurred by using unapproved
accessories are not covered by the warranty.
Avertissement:
Pour une installation sûre et fiable,
utilisez uniquement les accessoires et les vis fournies avec
l’appareil. L’utilisation d’autres accessoires et vis pourrait
endommager l’appareil. Les dommages causés par
l’utilisation d’accessoires non approuvés ne sont pas
couverts par la garantie.
Caution:
The device must be installed in a restricted-access
location.
Attention:
L’appareil doit être installé dans un emplacement
à accès restreint.
Note:
The device has the Open Network Install Environment
(ONIE) software installer preloaded, but no device software
image.
Note:
The drawings in this document are for illustration only
and may not match your particular model.
Caution:
This device must be installed in a
telecommunications room or a server room where only
qualified personnel have access.
Attention:
Cet appareil doit être installé dans une salle de
télécommunications ou une salle de serveurs où seul le
personnel qualifié a accès.
Note:
Stability hazard. The rack may tip over causing serious
personal injury.
Before extending the rack to the installation position, read the
installation instructions.
Do not put any load on the slide-rail mounted equipment in the
installation position.
Do not leave the slide-rail mounted equipment in the installation
position.
1
Using the Slide-Rail Kit
Follow instructions in the install guide provided in the slide-rail kit to
mount the device in a rack.
Note:
When using only one AC PSU to power a fully loaded
system, be sure to use a high-voltage source (200–240 VAC).
2
Verify Rack Ground
Ensure the rack on which the device is to be mounted is properly
grounded and in compliance with ETSI ETS 300 253. Verify that there is
a good electrical connection to the grounding point on the rack (no
paint or isolating surface treatment).
Attach Grounding Wire
Attach a grounding wire to the grounding point on the device rear
panel using two M6 screws and washers with a grounding lug (Panduit
LCDXN2-14AF-E or equivalent, not included). The grounding lug
should accommodate #2 AWG stranded copper wire (green with
yellow stripe, not included).
3
Install one or two AC or DC PSUs and connect them to an AC or DC
power source.
4
1
1
2
2
3
Installation