44
P42
ACCEL / DECEL #2
This parameter sets the second acceleration and deceleration rate of the drive. To activate this
acceleration and deceleration rate, use terminal TB-13A, TB-13B or T-13C. TB-13A and TB-13B
can be set to AUXILIARY STOP which will cause the drive to decelerate to a stop according to the
time programmed in this parameter. TB-13C can be set to ACCEL/DECEL #2, which causes the
drive to accelerate and decelerate according to the time programmed in this parameter.
P43
SERIAL ADDRESS
If a serial link is being used to communicate with multiple drives, each drive must be given a different
address (from 1 to 247) so that an individual drive in the network can be accessed.
P44
PASSWORD
This allows the PASSWORD to be changed to any number between 000 and 999. Setting PASSWORD
to 000 disables the password function.
NOTE: The factory default password is 225.
P47
CLEAR FAULT HISTORY
01
MAINTAIN: Maintains the FAULT HISTORY (Parameter 50) entries for troubleshooting.
02
CLEAR: Erases the FAULT HISTORY (Parameter 50) entries.
P48
PROGRAM SELECTION
This is used to select whether the drive will operate according to the user settings or the optional
OEM default settings, and to reset the parameters to default settings. Refer to Section 13.2.
01
OPERATE WITH USER SETTINGS: The drive will operate according to the user settings.
Operation in USER mode allows the parameter values to be changed to suit any
application.
02
OPERATE WITH OEM DEFAULTS: The drive will operate according to the optional
OEM default settings, which configure the drive for a specific application. When operating
in OEM mode, the parameter values can be viewed, but not changed. If an attempt is made
to change a parameter setting, the display will flash “GE”. If the drive is not programmed
with OEM default settings, the display will flash “GF” if this option is selected.
03
RESET OEM: Resets the user parameters to the OEM default settings. If the drive is not
programmed with OEM default settings, the display will flash “GF” if this option is
selected.
04
RESET 60: Resets the user parameters to the factory defaults for a 60 Hz base frequency.
05
RESET 50: Resets the user parameters to the factory defaults for a 50 Hz base frequency.
Parameters 24, 27, and 40 will reset to 50.0 Hz.