background image

10

ENGLISH

Commissioning

In some instances, multiple words can be read for a single register. When this is done for 
the registers below, the response from the drive will be for the number of words, rather 
than the number of registers, requested:

•  Register #500 (Fault History) can be read as 1 word (returning the two most recent 

faults) or as 4 words (returning the entire fault history).

•  Register #511 (Total kWh) can be read as 1 word (returning only the low word of the 

32-bit register value) or as 2 words (returning the complete 32-bit register value).

•  Register #540 (Total Runtime Hours) can be read as 1 word (returning only the low 

word of the 32-bit register value) or as 2 words (returning the complete 32-bit register 
value).

•  Register #541 (Total Power On Hours) can be read as 1 word (returning only the low 

word of the 32-bit register value) or as 2 words (returning the complete 32-bit register 
value).

06 - Preset Single Register (4X references)

Write a single register.

16 - Preset Multiple Registers (4X references)

While code 16 is supported it’s implementation is limited to addressing only one register 
per write.

Modbus Message Details

The following abbreviations will be used throughout this section when illustrating the 
message structure:

R

 

Read

W

 

Write

RS

 

Response

SA

 

Slave Address (01 ... F7 hex)

EC

 

Exception Code

RH

 

Register Address (high byte)

RL

 

Register Address (low byte)

DxH

  Data (high byte)

DxL

 

Data (low byte)

CRCH

  CRC (high byte)

CRCL

  CRC (low byte)

Содержание Lenze RS-485

Страница 1: ...CMVMB401B SMVector RS 485 Modbus Communication Module Communications Interface Reference Guide...

Страница 2: ...splay 1 01 then writing to any drive register over the Modbus network MUST NOT BE ATTEMPTED as it would have the potential for unexpected consequences potentially resulting in damage to the equipment...

Страница 3: ...nditions 13 6 4 Exception Responses 13 7 Commissioning 14 7 1 Drive Monitoring 14 7 2 Drive Programming and Control 14 7 3 Unlocking Locking of Drive Controls and Parameters 14 7 4 Network Watchdog Ti...

Страница 4: ...ance with the EMC Directive 89 336 EEC The drive controllers meet the requirements of the Low Voltage Directive 73 23 EEC The harmonised standards of the series EN 50178 DIN VDE 0160 apply to the cont...

Страница 5: ...operation of the inverter drive The system design must incorporate adequate protection to prevent personnel from accessing moving equipment while power is applied to the drive system Pictographs used...

Страница 6: ...ndustrial environment The ESVZAR0 module provides both galvanic and optical isolation of this physical interface 2 2 SMVector Modbus RTU Implementation Speci cations Typical communications between mas...

Страница 7: ...l is connected to the Modbus network GND common If only two wires are used TXA and TXB in the network connect Terminal 1 to chassis earth ground 2 TXA If controller is located at either end of the net...

Страница 8: ...6 ENGLISH Installation 3 3 Installing the Terminal Cover...

Страница 9: ...ed Read only Online state 3 indicates that the communications between the drive and module are working properly 1 Initialization Module to EPM 2 Initialization EPM to Module 3 Online 4 Failed Initiali...

Страница 10: ...ata bits Even Parity 1 stop bit 3 8 Data bits Odd Parity 1 stop bit P425 Network Message time out 10 0 0 0 s 300 0 P426 Network Message time out action 4 0 Not active 1 STOP see P111 2 Quick stop 3 In...

Страница 11: ...pported by the drive are The function codes supported by the drive are 03 Read Holding Register 4X references 04 Read Input Register 3X references Note We do not differentiate between 4X and 3X refere...

Страница 12: ...low word of the 32 bit register value or as 2 words returning the complete 32 bit register value Register 541 Total Power On Hours can be read as 1 word returning only the low word of the 32 bit regis...

Страница 13: ...mple Total Run time Hours 305419896 12345678h Register 60 low word of total run time hours 5678h Register 61 high word of total run time hours 1234h R SA 03 00 3C 00 02 CRCH CRCL RS SA 03 04 56 78 12...

Страница 14: ...only R SA 03 00 18 00 06 CRCH CRCL RS SA 0C D1H D1L D2H D2L D3H D3L D4H D4L D5H D5L D6H D6L CRCH CRCL Command Frequency D1H D1L Register 24 DH DL Actual Frequency D2H D2L Register 25 DH DL Load D3H R...

Страница 15: ...put buffer over ow occurs 6 4 Exception Responses If a valid message is received i e parity crc address and message length all pass validity checks but the message contents are somehow invalid the dri...

Страница 16: ...ting to Register 48 Unlock Controls with a value equal to the drive s programming password P194 will unlock the Drive Control register 1 and all other writable drive registers This enables the writing...

Страница 17: ...ll occur The watchdog timer does not operate unless Controls have been UNLOCKED via Register 48 and a time out action other than IGNORE has been speci ed using parameter P426 7 5 Watchdog Timer Contro...

Страница 18: ...y writing the drive password P194 to Register 49 The drive will remain in its normal control mode 2 Write to all necessary drive con guration or parameters registers 3 The watchdog timer is not enable...

Страница 19: ...etup to display the actual frequency in RPM using P178 29 17 the actual speed would be displayed on the drive as 1000 RPM but would still be sent over the Modbus communications as 343 or 01 57 hex 9 2...

Страница 20: ...Command 0 0 Hz P102 P103 See Section 8 3 45 Network PID Setpoint Command 0 0 999 0 3100 0 Read only See Sections 8 3 and 9 2 8 46 Network Torque Command 0 0 0 400 0 See Sections 8 3 48 Unlock Controls...

Страница 21: ...e desired action should be set to 1 For example to stop the drive according to P111 bit 2 should be set i e send 0004h To start the drive bit 3 should be set i e send 0008h Locking security i e settin...

Страница 22: ...HP 2 2 kW 21 240 VAC Three Phase 0 5 HP 0 37 kW 23 1 HP 0 75 kW 24 1 5 HP 1 1 kW 25 2 HP 1 5 kW 26 3 HP 2 2 kW 28 5 HP 4 kW 29 7 5 HP 5 5 kW 30 10 HP 7 5 kW 42 480 VAC Three Phase 0 5 HP 0 37 kW 44 1...

Страница 23: ...7 10 MOP 11 Network 9 10 11 12 Control 0 Keypad 1 Terminal 2 Remote Keypad 3 Network 13 14 0 Network Control DISABLED 1 Network control ENABLED 15 0 DC Braking not active 1 DC Braking active 9 2 4 Re...

Страница 24: ...t commands from optional remote keypad P100 2 or 5 3 Network Only Start commands from Network but Network control is not active P100 3 4 Network Control Start commands from Network and Network control...

Страница 25: ...t F EF 32 Follower Lost F FoL 14 Control Fault F CF 33 ISO Comm Fault F F11 15 Start Error F UF 34 SPI Time out F ntF 16 Incompatibility Fault F cF 35 Invalid Message Received F Fnr 17 Internal Fault...

Страница 26: ...state of the relay or digital output TB14 Drive Programming Parameter P140 and or P142 must be set to 25 Network Controlled 9 2 11 Register 71 Network Controlled Analog Output To control the state of...

Страница 27: ...um Frequency over the Modbus network you would read register 103 10 1 Negative Number Transmission Drive parameters P160 P161 P204 P205 P214 P215 P231 P232 P233 P522 and P523 are signed integer values...

Страница 28: ...531 the Keypad Status data returned can be interpreted as follows Data Low Byte 0 UP Push button State Data High Byte 8 Unused 1 DOWN Push button State 9 Unused 2 MODE Push button State 10 Unused 3 FW...

Страница 29: ...nd P402 Incorrect Modbus settings Use P403 to reset Modbus parameters Verify P410 and P411 P412 Improper wiring Check wiring between the Modbus Network and communication module Ensure that terminal bl...

Страница 30: ...AC Technology Corporation 630 Douglas Street Uxbridge MA 01569 USA 1 508 278 9100 www actech com Document CMVMB401B...

Отзывы: