Multi Variable Air Conditioners Ducted Type Indoor Unit
10
(2)
Tighten the pipe clamp, with the distance between screw nut and hose smaller than
4mm (3/16 in.).
①
metal clamp(accessory)
②
drain hose(accessory)
Fig 4.3.2
(3)
Use sealing plate to make the pipe clamp and hose insulated, as shown in Fig.4.3.3.
①
metal clamp(accessory)
②
thermal sponge(accessory)
Fig 4.3.3
(4)
When connecting several drain pipes, follow the instruction as indicated in Fig 4.3.4.
Choose the drain collecting pipe that matches with unit capacity.
Fig 4.3.4
(5)
Install the trap as shown in following Fig 4.3.5.
(6)
Install one trap for each unit.
(7)
Convenience for cleaning trap in the future should be considered when installing it.
Fig 4.3.5
(8)
The horizontal pipe can be connected to vertical pipe in the same level; please select
the connection way as shown in following fig.
N
O
1: Connection of drainage pipe joints (Fig4.3.6)
N
O
2: Connection of downspout elbow (Fig4.3.7)
N
O
3: Inserting pipe connection (Fig4.3.8)