Abtech STR1 Series Скачать руководство пользователя страница 2

IOM-STR1

    

 

Abtech Ltd 

Newhall Road 

Sheffield, S9 2QJ 

 

United Kingdom 

IOM-STR1 ABTQ210.docx 

Page 2 of 6 

t : +44 (0) 114 244 2424 

f : +44 (0) 114 243 4312 

e : [email protected] 

 

 

Installation 

 

1. General 

The STR1 Roadway lantern is certified to the ATEX standard, certificate number: ABT 15ATEX4111. This 

certificate should be used in conjunction with the installation, operation and maintenance of the product.  

 

Installation and electrical connections must be carried out in accordance with EN/IEC60079-14 and 

EN/IEC60079-15 as applicable and local or national standards and/or codes of practice as applicable. 

 

The STR1 roadway lantern is class 1 apparatus and must be suitably earthed. It is the installer /users 

responsibility to ensure that the luminaire and the relevant ratings are suitable for the application, zone and 

environment and ensure the materials as stated will not be attacked by existing foreseeable aggressive 

substances. 

It should be noted that this equipment will be provided with an external non-metallic coating (paint finish), to 

avoid the build-up of an electrostatic charge, clean only with a damp cloth. 

 

2.

 

Supply Voltages 

For voltage refer to rating plate. The supply voltage must be within the Vac range specified in the operational 

parameters.  

Note: it is important that the frequency of the supply matches the frequency stated on the driver rating 

label. 

 

Supply voltage variation must not exceed ±6% and the luminaire should not be operated continuously beyond 

this limit. In any case the voltage variation must NEVER exceed ±10% as this will invalidate the certification and 

could lead to the product being unsafe. If in doubt, advice should be sought from Abtech technical 

department. 

 

3.

 

Mounting Luminaire 

The luminaire should be pole mounted which is not prone to excessive levels of vibration or shock. No objects 

should be placed within 1m directly in front of the glass window. The luminaire should be fixed in position in 

accordance with lighting design parameters and secured using appropriate fixings at an angle between 0°to 

15°.  

 

4.

 

Supply Cable 

The STR1 range of roadway lanterns is suitable for use with cable with insulation rated for a minimum 

temperature of 80°C. Terminals are suitable for looping up to 4mm² conductors. Cable type must be effectively 

filled to ensure that the non-sparking properties of the luminaire are maintained.  

 

Access to the terminals is via the glass cover which can be removed by undoing the eight cover screws.  

All electrical connections and components should be inspected for security of wiring and cracks in insulation 

and stray conductor strands. The conductors should be fitted into the terminal block ensuring that conductors 

are not stretched or stressed. If removable threadlock adhesive has been applied to the terminal screws, this 

should be reapplied prior to tightening the terminal screws after adjustment. When terminating the conductor 

into the terminal block this must be carried out in an ambient temperature of between -10°C and 80°C, also it 

is vital that no more than 1mm of bare conductor protrudes from the terminal throat. The mains terminal 

block does not require threadlock adhesive to be applied to the Cable glands should be fitted with an 

appropriate sealing washer to the inside of the luminaire. The sealing washer must maintain the Restricted 

breathing properties of the luminaire and meet the minimum IP rating as noted on the apparatus label.  

 

Standard cable entry is a threaded M20x1.5. Care should be taken with threaded entries to ensure no swarf or 

debris enters any of the electrical components. All swarf and debris must be removed from the interior of the 

luminaire. 

Содержание STR1 Series

Страница 1: ...s designed for use in areas not subject to levels of vibration or shock above those considered normal for fixed installations Care should be taken not to expose the gasket s to high concentrations of hydrocarbon vapours This equipment uses an external non metallic coating To avoid the build up of an electrostatic charge clean only with a damp cloth Refer to apparatus certificates supplied with lum...

Страница 2: ...should be pole mounted which is not prone to excessive levels of vibration or shock No objects should be placed within 1m directly in front of the glass window The luminaire should be fixed in position in accordance with lighting design parameters and secured using appropriate fixings at an angle between 0 to 15 4 Supply Cable The STR1 range of roadway lanterns is suitable for use with cable with ...

Страница 3: ...ck for any signs of water ingress and remedy as necessary Check condition of all wiring and electrical components for signs of arcing or overheating Refer to Abtech technical department for advice if any components are in doubt Refit glass cover and tighten screws 3 Fault Finding Any fault finding must be carried out with the luminaire de energised and without a flammable atmosphere present Genera...

Страница 4: ...IOM STR1 Abtech Ltd Newhall Road Sheffield S9 2QJ United Kingdom IOM STR1 ABTQ210 docx Page 4 of 6 t 44 0 114 244 2424 f 44 0 114 243 4312 e sales abtech eu 2 Mounting options 3 Installation ...

Страница 5: ...IOM STR1 Abtech Ltd Newhall Road Sheffield S9 2QJ United Kingdom IOM STR1 ABTQ210 docx Page 5 of 6 t 44 0 114 244 2424 f 44 0 114 243 4312 e sales abtech eu ...

Страница 6: ...l components contain synthetic resins plastics and other inorganic compounds which may produce noxious fumes if incinerated Within the EC disposal of components must comply with WEEE directive 2002 96 EC Any local or national regulations with regard to waste disposal must also be complied with Lamps must not be incinerated Lamps should be disposed of in accordance with local or national ...

Отзывы: