background image

 
 
 

Abtech Limited 
Newhall Road 
Sheffield, S9 2QJ 
United Kingdom 

 

t : +44 (0) 114 244 2424 
f : +44 (0) 114 243 4312 

e : [email protected] 

IOM-Alpha ABTQ134rev1.doc 

Page 1 of 4 

 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

Values are nominal at 240V 50Hz. For other voltages and frequencies, please refer to our technical department. 

 
 

 

Alpha Floodlight 

CML 14ATEX1049X 

II 2 GD Ex de IIB T3 Gb 

Ex tb IIIC T190

º

C Db 

Tamb: -20

º

C to +55

º

Installation, Operation and Maintenance Instructions 

 

Description 
The Alpha floodlight is manufactured in marine grade die cast aluminium* with a toughened glass window which is 
permanently cemented in place and silicone rubber seal on both the ignitor housing and the CGB control-gear box. The 
type of protection is Ex de, flameproof and increased safety. Restrictions apply to the mounting orientation of the 
luminaire such that, the control gear enclosure must be level or below the axis of the lamp. 
 
Application 
The luminaire is suitable for use in a Zone 1 area, gas and dust hazards and reference should be made to the rating table 
below in respect of T rating and ambient temperature considerations, 
The luminaire is designed for use in areas not subject to levels of vibration or shock above those considered normal for 
fixed installations. 
Care should be taken, not to expose the gasket(s) to high concentrations of hydrocarbon vapours. 
Refer to product certificate for details of certification, coding, conditions for safe use, etc. 
 
*As an option, the luminaire may be manufactured in stainless steel or gunmetal as an alternative to aluminium. 

 

Product Reference 

Lamp  

Power 

Lamp  

Current 

Circuit 

Current 

Capacitor 

Value 

Circuit  

Power (W) 

Power factor 

Correction (µF) 

ALP150SH 

150W 

1.8A 

0.74A 

20

µF

 

174 

>0.88 

ALP250SH 

250W 

3.0A 

1.26A 

30

µF

 

280 

>0.88 

ALP400SH 

400W 

4.6A 

E40 

40

µF

 

445 

>0.88 

IOM-ALPHA

    

Zone 1 Asymmetric Floodlight

 

Luminaire Ratings

 

Product Reference 

Lamp Type 

Lamp  

Cap 

Power 

(W) 

Temperature 

Rating 

Ambient  

Temperature 

Weight 

(Kg) 

ALP150SH 

HPS/MBI 

E40 

150 

T3 

-20ºC to 55ºC 

29.6 

ALP250SH 

HPS/MBI 

E40 

250 

T3 

-20ºC to 55ºC 

27.8 

ALP400SH 

HPS/MBI 

E40 

400 

T3 

-20ºC to 55ºC 

26.5 

 

Operating Parameters

 

Содержание IOM-ALPHA ALP150SH

Страница 1: ...ea gas and dust hazards and reference should be made to the rating table below in respect of T rating and ambient temperature considerations The luminaire is designed for use in areas not subject to levels of vibration or shock above those considered normal for fixed installations Care should be taken not to expose the gasket s to high concentrations of hydrocarbon vapours Refer to product certifi...

Страница 2: ...ock is 16A continuous Only one conductor may be fitted in each terminal way Tighten all used and unused terminal screws Refit the cover ensuring that the gasket is clean and undamaged 4 Cable Glands The CGB control gear box uses increased safety Ex e as the protection concept Cable glands must be suitably certified Ex e Cable glands should be fitted with an appropriate sealing washer to the outsid...

Страница 3: ...re in doubt Refit control gearbox cover and tighten screws 3 Fault Finding Any fault finding must be carried out with the luminaire de energised or in the absence of any flammable atmosphere Generally HID control gear is very reliable and the majority of faults will relate to aged or faulty lamps if changing the Fuse Ratings 1 HID lamps are subject to a large current inrush on initial startup and ...

Страница 4: ...esins plastics and other inorganic compounds which may produce noxious fumes if incinerated Within the EC disposal of components must comply with WEEE directive 2002 96 EC Any local or national regulations with regard to waste disposal must also be complied with Lamps must not be incinerated Lamps should be disposed off in accordance with local or national regulations ...

Отзывы: