Operating Instruction and Guidelines 

1. Discharge 

End voltage with different discharge rate must be 
less than the specified value. Charge the battery 
as soon as possible after discharge. 

In order to extend the service life, the depth of 
discharge should be less than 60% of the rated 
capacity. The discharge over 60% DOD is deep 
discharge and would shorten the service life. 

2. Temperature 

The operation temperature range is -20

--55

℃. 

.All the performance data is measured at 

ambient temperature of 20

. The optimal 

temperature is 20 

±

5 , extreme high 

temperature would shorten the service life and 
very low temperature would lower the capacity 
available. The highest acceptable temperature is 
55

3.  Floating charge and Equalization Charge 

3.1 Floating charging operation is optimal for gel 
battery, battery has been in full charge ensuring 
battery maximum service life. The recommended 
battery floating charge voltage is 2.24 volts/cell at 
20

. The recharge time is about 24 to 36 hour. 

Floating charge voltage shall be adjusted 
according to the ambient temperature, and 
temperature compensate coefficient for battery is 
-3.5mV//cell, the specifications is expressed by 
the following table. 

Table Floating charge at different temperature 

Ambient temperature 

Float charge (V/cell) 

0

 

2.32 

10

 

2.28 

20

 

2.24 

25

 

2.22 

30

 

2.21 

35

 

2.19 

3.2  The batteries need an equalization charge or 

supplemental charge in the following 
conditions: 

 

Supplemental charge battery after the

 

installation of battery system and before the 
operation. 

 

The batteries are on shelf for six months. 

 

Floating operation for a long time or not

 

discharge 40% C

20

 plus, the batteries need 

an equalization charge regularly and the 
equalizing charge cycle are 6 months to one 
year. 

We recommend the below method for equalizing 
charge or supplemental charge: 

Charge with 2.35Vpc and limited current 0.15C(A) 

for 8 to 12 hours (non continuous charging is 
allowed). 

Charge voltage shall be adjusted according to the 
ambient temperature, and temperaturec 
ompensate coefficient for battery is -3.5mV//cell, 
the specifications is expressed by the following 
table. 

Table Equalizing voltage at different temperature 

Ambient temperature 

Float charge (V/cell) 

0

 

2.45 

10

 

2.39 

20

 

2.35 

25

 

2.33 

30

 

2.31 

35

 

2.30 

40

 

2.29 

4.  Cycle charge characteristic 

Cycle charge characteristic curve (at 20

/68

 

 

 

 

 

 

 

 

 

Cycle  times  at  different  DOD  and  different 
discharge rate 

GFMJ(2V)  30%DOD 50%DOD 60%DOD 70%DOD 80%DOD  100%DOD 

C

10

 

3100 

1750 

1400 

1100 

850 

700 

C

20

 

2810 

1600 

1300 

980 

720 

580 

C

50

 

2650 

1540 

1200 

850 

660 

460 

C

100

 

2300 

1400 

1040 

750 

600 

400 

C

120

 

2080 

1290 

960 

665 

520 

340 

 

GFMJ(12V)  30%DOD 50%DOD 60%DOD 70%DOD 80%DOD  100%DOD 

C

10

 

2100 

1150 

900 

750 

650 

550 

C

20

 

1810 

1050 

820 

680 

570 

470 

C

50

 

1650 

850 

750 

630 

510 

410 

C

100

 

1400 

730 

690 

550 

430 

350 

C

120

 

1280 

690 

610 

465 

310 

290 

 

 

 

 

 

 

 

 

12

 

Содержание 6GFMJ-100

Страница 1: ......

Страница 2: ...res 01 3 Applications 02 4 Standards 02 5 Certification 02 6 Battery construction 02 7 General Specifications 04 8 Technology 05 9 Performance Data 06 10 Operating instruction and Guidelines 12 11 Installation and Commissioning and Maintenance 14 ...

Страница 3: ...d long cyclic life Patented relief valve Multi fold vent system comprised of proprietary gel specialized low pressure safety valve with acid filtering and flash arrester minimizes bulging and prevents flash back explosion from external ignition source Long service life The grid is made of lead calcium tin alloy which has effect against corrosion effect and provide good gas recombination technology...

Страница 4: ...nd vibration resistant prevents leakage and container deformation Applications Telecommunication base station exchange station Dedicated telecommunication station for power system military station Data transmission and TV signal transmission EPS UPS Wind solar energy and wind pv hybrid power system Certification CE UL GOST Standards IEC60896 21 22 2004 IEC61427 2005 DIN43539 T5 1984 YD T1360 2005 ...

Страница 5: ...GFMJ 200 and GFMJ 300 GFMJ 400 500 600 GFMJ 800 and GFMJ 1000 GFMJ 1200 GFMJ 1500 and GFMJ 2000 03 ...

Страница 6: ...J 150 12 150 188 513 232 218 228 63 8 560 1600 3 65 M8 Φ16 D 6GFMJ 200 12 200 250 513 296 5 218 228 82 8 660 1850 3 20 M8 Φ16 D GFMJ 200 2 200 250 171 107 334 344 14 8 800 1900 0 68 M8 Φ18 F GFMJ 300 2 300 375 171 151 334 344 21 3 1000 2000 0 54 M8 Φ18 F GFMJ 400 2 400 500 211 175 334 344 30 1500 2800 0 45 M8 Φ18 H GFMJ 500 2 500 625 243 174 334 344 35 5 2000 3200 0 39 M8 Φ18 H GFMJ 600 2 600 750 ...

Страница 7: ...lcium alloy which inhibit the hydrogen evolution The batteries apply special gel electrolyte technology and the gel is with three dimensional net porous structures and also with some tiny cracks as gas passage The oxygen from positive electrode get to negative through the special gel and rapidly react with the spongy lead existing on the negative electrode and produce water This process is called ...

Страница 8: ...5 49 1 38 2 29 2 22 30 14 90 8 50 4 59 3 93 2 07 1 06 0 93 0 49 1 65 225 167 132 111 82 64 48 2 37 7 29 2 22 30 14 90 8 50 4 59 3 93 2 07 1 06 0 93 0 49 1 70 212 158 130 109 81 62 48 2 37 1 29 2 22 30 14 90 8 50 4 59 3 93 2 07 1 06 0 93 0 49 1 75 197 147 125 104 78 60 47 3 36 6 29 2 22 30 14 90 8 50 4 59 3 93 2 07 1 06 0 93 0 49 1 80 168 134 117 97 74 58 46 8 35 5 28 4 21 30 14 50 8 50 4 42 3 74 2...

Страница 9: ...6 81 6 55 65 48 30 38 70 31 95 16 65 14 05 7 29 3 75 3 27 1 74 1 75 450 419 372 329 276 182 108 5 80 4 54 6 47 55 37 95 31 35 16 50 13 90 7 29 3 75 3 27 1 74 1 80 420 398 344 303 255 168 104 1 76 8 52 5 45 75 36 45 30 00 16 20 13 72 7 29 3 75 3 27 1 74 1 85 360 344 314 284 239 162 98 0 72 0 49 4 42 90 34 20 28 35 15 30 13 20 7 29 3 75 3 27 1 74 GFMJ 400 1 65 680 620 576 520 404 250 150 110 76 68 0...

Страница 10: ... 204 00 159 60 135 00 67 80 57 50 29 16 15 00 13 08 6 96 1 70 1920 1770 1560 1362 1140 738 442 2 326 4 222 6 193 20 154 80 127 80 66 60 57 30 29 16 15 00 13 08 6 96 1 75 1800 1674 1488 1314 1104 726 433 8 321 6 218 4 190 20 151 80 125 40 66 00 57 00 29 16 15 00 13 08 6 96 1 80 1680 1590 1374 1212 1020 672 416 4 307 2 210 183 00 145 80 120 00 64 80 56 80 29 16 15 00 13 08 6 96 1 85 1440 1374 1254 1...

Страница 11: ... 5 95 3 16 1 63 1 43 0 76 1 75 251 203 173 147 113 85 67 52 5 42 3 30 60 20 90 12 10 6 60 5 95 3 16 1 63 1 43 0 76 1 80 234 185 165 138 108 82 66 0 51 3 41 2 29 80 19 80 11 80 6 40 5 72 3 16 1 63 1 43 0 76 6GFMJ 85 1 60 419 314 246 207 155 117 90 8 70 6 55 3 40 00 27 40 16 20 8 70 7 78 4 13 2 13 1 87 0 99 1 65 390 302 241 204 154 116 89 2 70 55 3 40 00 27 40 16 00 8 70 7 78 4 13 2 13 1 87 0 99 1 7...

Страница 12: ...39 104 71 48 60 38 50 31 90 18 30 16 70 9 72 5 00 4 40 2 34 1 75 547 515 462 410 346 229 138 103 70 46 90 37 20 30 70 18 30 16 50 9 72 5 00 4 40 2 34 1 80 523 498 434 383 325 214 135 99 68 45 20 35 80 30 00 18 30 16 10 9 72 5 00 4 40 2 34 1 85 458 439 402 366 309 211 128 0 94 0 65 0 42 90 34 10 28 30 17 60 15 30 9 72 5 00 4 40 2 34 GFMJ 300 1 65 891 827 777 707 554 348 210 156 108 75 15 60 00 49 5...

Страница 13: ...170 1915 1625 1070 675 495 340 226 00 179 00 150 00 80 50 91 50 48 60 25 00 22 00 11 70 1 85 2290 2195 2010 1830 1545 1055 640 0 470 0 325 0 215 00 171 00 142 00 76 50 88 00 48 60 25 00 22 00 11 70 GFMJ 1200 1 65 3564 3306 3108 2826 2214 1392 840 624 432 300 60 240 00 198 00 101 40 100 20 58 32 30 00 26 40 14 04 1 70 3414 3204 2850 2508 2106 1380 834 624 426 291 60 231 00 191 40 100 20 99 30 58 32...

Страница 14: ...22 30 2 21 35 2 19 3 2 The batteries need an equalization charge or supplemental charge in the following conditions Supplemental charge battery after the installation of battery system and before the operation The batteries are on shelf for six months Floating operation for a long time or not discharge 40 C20 plus the batteries need an equalization charge regularly and the equalizing charge cycle ...

Страница 15: ...to constant voltage h Constant voltage V cell Charging time h 20 0 1C10 1 6 2 35 8 0 15C10 1 2 2 35 6 50 0 1C10 4 3 2 35 14 0 15C10 3 3 2 35 12 80 0 1C10 6 8 2 35 16 0 15C10 5 5 2 35 14 100 0 1C10 8 7 2 35 18 0 15C10 6 8 2 35 16 6 Storage GEL batteries should be stored in a dry clean and ventilated location Since the batteries are fully charged the recommended storage time is as follows 6 months a...

Страница 16: ...ord the ambient temperature of the battery room battery container and terminals Check container lid and terminal surface defects and temperature of each battery Measure and record the total voltage and floating current of the battery system Correct problems once found Quarterly Maintenance Repeat every item of monthly inspection Measure and record floating voltage of every on line battery Annually...

Страница 17: ...ith Master distributors and Country managers who apply ABT commercial strategy and through Global Key Account in Advanced Battery Technology BV Add New Yorkstraat 14 1175 RD Lijnden Amsterdam Netherland Website www abtbatt com Email sales abtbatt com Version 201503 Copyright 2015 Advanced Battery Technology BV All rights reserved ...

Отзывы: