Programmable 4-Wire Digital Pressure Transmitters
F16DR, F16DRN
Ranges and Resolution
See table below. Consult factory for special engineering units.
Resolution is fixed as indicated in table.
F16DR
O
±0.25% Test Gauge Accuracy
O
316L Stainless Steel Wetted Parts
O
Low Voltage Powered
O
4-20 mA or 0-2 V Analog Output
O
Output Test Function
Accuracy
Accuracy includes linearity, hysteresis, repeatability
Standard accuracy: ±0.25% of full scale ±1 least significant digit
HA
accuracy option: ±0.1% FS ±1 LSD, see ranges for availability
Sensor hysteresis: ±0.015% FS, included in accuracy
Sensor repeatability: ±0.01% FS, included in accuracy
Display
4 readings per second nominal display update rate
4 digit LCD, 0.5" H and 5 character 0.25" H alphanumeric
DRBL
: Red LED backlight on when gauge is on
Controls
SEL
Select display for setup
TEST
Set output to test level when in test mode
s
Up:
Increase when in test or calibration mode
t
Down:
Decrease when in test or calibration mode
Zero/tare function can be enabled or disabled
Calibration
User settable pass code required to enter calibration mode
All pressure and absolute models: zero, midpoint, span
All vacuum models: –span, –midpoint, zero
Vacuum/pressure models: –span, zero, +midpoint, +span
±15 psi models: –span, –midpoint, zero, +midpoint, +span
Output Characteristics
Updated approximately 16 times per second
User scalable pressure range to correspond to output
-I
: Current output, 4-20 mA DC
Output drive (compliance) determined by power source
6,553 counts over sensor range
-V
: Voltage output, 0-2 VDC into 5k ohm or greater
6,553 counts over sensor range
-BV
: Bipolar voltage output (–2 - 0 - 2 V) for ±15 psig sensor only
±2 VDC into 5k ohm or greater
13,107 counts over sensor range
Power
8-24 VAC 50/60 Hz or 9-32 VDC
Gauge is on when power is on. Designed for continuous operation.
DR
:
30 mA maximum
DRBL
:
Approximately 40 mA maximum
Weight
9.5 ounces (approx.), shipping wt. 1 pound (approx.)
Housing
F16DR
: Extruded aluminum case, epoxy powder coated, ABS/
polycarbonate bezel (aluminum bezel optional), front and rear
gaskets, polycarbonate label
F16DRN
: ABS/polycarb. NEMA 4X case, rear gasket, polycarb. label
Connection, Material, Media Compatibility
1/4" NPT male fitting. All wetted parts are 316L stainless steel.
Overpressure, Burst, Vacuum
Ranges using 3000 psig sensor: 5000 psig
Ranges using 5000 psig sensor: 7500 psig
All others:
2 X pressure range
3000 psi, 5000 psi, and 4 digit ranges 112.5% full scale out-of-
range display: 1– – – or I –.–.–.–
4 X sensor burst pressure rating, or 10,000 psi, whichever is less
Vacuum service: 15 psia, ±15 psig, 15 psig, 30 psia,
100 psig, 100 psia, 200 psig sensors
Under-range display (non-vacuum sensors): –Err
Environmental
Storage temperature:
–40 to 203°F (–40 to 95°C)
Operating temperature:
–4 to 185°F (–20 to 85°C)
Compensated temperature:
32 to 158°F (0 to 70°C)
How to Specify
Type
F16DR
range - output - options
Standard housing
F16DRBL
range - output - options
Standard housing,
backlit display
F16DRN
range - output - options
NEMA 4X housing
F16DRNBL
range - output - options
NEMA 4X housing,
backlit display
1.65"
2.88"
3 ft long,
4-conductor
22 AWG
shielded
cable
NEMA 4X
3.0"
2.0"
Turn at hex
fitting
only!
Turn at hex
fitting
only!
3 ft long,
4-conductor
22 AWG
shielded
cable
G = gauge reference pressure
VAC = gauge reference vacuum
A = absolute reference
Output
Specify:
I
4-20 mA
V
0-2 V
BV
±2 V for ranges using ±15 psig sensor only
psi = PSI
inHg = INHG
oz/in
2
= ZIN
inH
2
O = INH2O
ftH
2
O = FTH2O
mmHg = MMHG
torr = TORR
mmH
2
O = MMH2O
kg/cm
2
= KGCM
g/cm
2
= GCM
kPa = KPA
MPa = MPA
mbar = MBAR
bar = BAR
cmH
2
O = CMH2O
atm = ATM
Range
—see table at left
F16DRN
¼" NPT
0.75"
SEL TEST
t
s
X X X X X
88888
2
Cecomp Electronics / Made in USA
3.38" Standard
3.5" NEMA 4X
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
‡ -HA option not available
PSI
Res
inHg/PSI
Res
mmH
2
O
Res
3PSIG
‡
.001
–30V15PSIG
‡
.1
2100MMH2OG
‡
1
5PSIG
‡
.001
–30V100PSIG
‡
.1
3500MMH2OG
‡
1
15PSIA
.01
–30V200PSIG
‡
.1
cmH
2
O
Res
15PSIVAC
‡
.01
inH
2
O
Res
210CMH2OG
‡
.1
±15PSIG
‡
.01
85INH2OG
‡
.01
350CMH2OG
‡
.1
15PSIG
.01
140INH2OG
‡
.1
1000CMH2OA
1
30PSIA
.01
400INH2OA
.1
1000CMH2OVAC
‡
1
30PSIG
.01
400INH2OVAC
‡
.1
±1000CMH2OG
‡
1
60PSIG
.01
±400INH2OG
‡
1
1000CMH2OG
1
100PSIA
.1
400INH2OG
.1
2100CMH2OA
1
–15V100PSIG
‡
.1
850INH2OA
1
2100CMH2OG
1
100PSIG
.1
850INH2OG
1
kPa
Res
–15V200PSIG
‡
.1
ftH
2
O
Res
20KPAG
‡
.01
200PSIG
.1
7FTH2O
‡
.001
35KPAG
‡
.1
300PSIG
.1
12FTH2O
‡
.01
100KPAA
.1
500PSIG
.1
35FTH2O
.1
100KPAVAC
‡
.1
1000PSIG
1
70FTH2O
.1
±100KPAG
‡
.1
2000PSIG
1
140FTH2O
.1
100KPAG
.1
3000PSIG
1
230FTH2O
.1
200KPAA
.1
5000PSIG
1
480FTH2O
.1
200KPAG
.1
oz/in
2
Res
700FTH2O
.1
400KPAG
.1
50ZING
‡
.01
1150FTH2O
1
700KPAA
.1
80ZING
‡
.1
2300FTH2O
1
700KPAG
.1
240ZINA
.1
4600FTH2O
1
–100V700KPAG
‡
1
240ZINVAC
‡
.1
6900FTH2O
1
1400KPAG
1
±240ZING
‡
.1
mmHg
Res
–100V1400KPAG
‡
1
240ZING
.1
150MMHGG
‡
.1
2000KPAG
1
480ZINA
.1
260MMHGG
‡
.1
3500KPAG
1
480ZING
.1
760MMHGA
.1
7000KPAG
1
inHg
Res
760MMHGVAC
‡
.1
MPa
Res
6INHGG
‡
.001
±760MMHGG
‡
1
1.4MPAG
.001
10INHGG
‡
.01
760MMHGG
.1
–0.1V1.4MPAG
‡
.001
30INHGA
.01
1600MMHGA
1
2MPAG
.001
30INHGVAC
‡
.01
1600MMHGG
1
3.5MPAG
.001
±30INHGG
‡
.01
Torr
Res
7MPAG
.001
30INHGG
.01
760TORRA
.1
14MPAG
.01
60INHGA
.01
760TORRVAC
‡
.1
20MPAG
.01
60INHGG
.01
1600TORRA
1
35MPAG
.01
120INHGG
.1
mbar
Res
g/cm
2
Res
200INHGA
.1
200MBARG
‡
.1
200GCMG
‡
.1
–30V200INHGG
‡
.1
350MBARG
‡
.1
350GCMG
‡
.1
200INHGG
.1
1000MBARA
1
1000GCMA
1
–30V400INHGG
‡
.1
1000MBARVAC
‡
1
1000GCMVAC
‡
1
400INHGG
.1
±1000MBARG
‡
1
±1000GCMG
‡
1
600INHGG
.1
1000MBARG
1
1000GCMG
1
1000INHGG
1
2000MBARA
1
2100GCMA
1
2000INHGG
1
2000MBARG
1
2100GCMG
1
4000INHGG
1
bar
Res
kg/cm
2
Res
atm
Res
1BARA
.001
1KGCMA
.001
1ATMA
.001
1BARVAC
‡
.001
1KGCMVAC
‡
.001
1ATMVAC
‡
.001
±1BARG
‡
.001
±1KGCMG
‡
.001
±1ATMG
‡
.001
1BARG
.001
1KGCMG
.001
1ATMG
.001
2BARA
.001
2KGCMA
.001
2ATMA
.001
2BARG
.001
2KGCMG
.001
2ATMG
.001
4BARG
.001
4KGCMG
.001
4ATMG
.001
7BARA
.001
7KGCMA
.001
7ATMA
.001
7BARG
.001
7KGCMG
.001
7ATMG
.001
–1V7BARG
‡
.01
–1V7KGCMG
‡
.01
–1V7ATMG
‡
.01
14BARG
.01
14KGCMG
.01
14ATMG
.01
–1V14BARG
‡
.01
–1V14KGCMG
‡
.01
–1V14ATMG
‡
.01
20BARG
.01
20KGCMG
.01
20ATMG
.01
35BARG
.01
35KGCMG
.01
34ATMG
.01
70BARG
.01
70KGCMG
.01
70ATMG
.01
140BARG
.1
140KGCMG
.1
140ATMG
.1
200BARG
.1
200KGCMG
.1
200ATMG
.1
350BARG
.1
350KGCMG
.1
340ATMG
.1
Quick Link:
cecomp.com/xmtr
NEMA 4X
Housing
Options
—add to end of model number
HA
High accuracy, ±0.1% FS ±1 LSD. See table at left for
availability.
PM
Panel mount, 4.1" x 4.1", n/a NEMA 4X
CC
Moisture resistant circuit board conformal coating
CD
Calibration data; 5 test points and date
NC
NIST traceability documentation, 5 points and date
Accessories
—order separately
WMPSK
Wall mount power supply kit, 115 VAC/12 VDC
SCR14SS
Filter screen fitting keeps debris out of gauge
sensor. Use for food vacuum packaging applica-
tions. 303 SS body, 100 micron 304 SS screen.
© 08-18
cecomp.com
1220 American Way Libertyville, IL 60048
800-942-0315
CECOMP
Div. of
A
BSOLUTE
P
ROCESS
I
NSTRUMENTS
Allow 1"
clearance
Allow 1"
clearance