Absolute Process Instruments Cecomp DPG2000B Series Скачать руководство пользователя страница 3

Instructions 

DPG2000B D4 and M0, M1 Series

Entering User Configuration

Basic Setup

Configuration must only be done in a non-hazardous area.
Remove the 6 Phillips screws on the back of the unit and 
remove the rear cover.
Move the switch on the circuit board to the ENABLE position.
Locate the UP and DOWN buttons on the circuit board. 

User Configuration Access

With the gauge off, press and hold the UP button. Then press 
the front button. Release all buttons when the display indicates 

CFG

 and the program version. Then the full-scale range is 

indicated and the display is tested.
The display then indicates _ _ _ _ with the first underscore 
blinking, with 

CFGPC

 (configuration pass code) on the lower 

display. 

Note: The gauge will automatically revert to normal operation if 
no buttons are pressed for approximately 15 seconds. To can-
cel and return to normal operation, press and release the front 
button without entering any pass code characters.

User Configuration Pass Code Entry

The factory default is 3510, but this may be changed by the 
user under the Pass Code Configuration section. If an incorrect 
pass code is entered, the gauge will return to the start of the 
pass code entry sequence.
1.  Use the UP or DOWN buttons to set the first digit to 3.
2. Press and release the front button to move to the next 

position. The 3 will remain, and the second position will be 
blinking.

3.  Use the UP or DOWN buttons to select 5.
4.  Press and release the front button to index to the next posi-

tion. 35 will remain, and the third position will be blinking.

5.  Use the UP or DOWN buttons to select 1.
6. Press and release the front button to index to the next 

position. 351 will remain, and the fourth position will be 
blinking.

7.  Use the UP or DOWN buttons to select 0.
8.  Press and release the front center button to proceed.

Configuration must only be done in 
a non-hazardous area.
Remove the 6 Phillips screws on the 
back of the unit. 
Remove the rear cover.
Move the switch on the circuit 
board to the ENABLE position.
Locate the UP and DOWN buttons 
on the circuit board. 

Engineering Unit Selection

Engineering unit selection is done via internal buttons to help 
prevent accidental or unauthorized changes. The selected 
engineering unit is stored in non-volatile memory and will be 
retained even with the gauge off or batteries removed. The 
available engineering units depend on the sensor range and 
display resolution.
Compound (inHg/PSIG) gauges must be changed to dis-
play single-unit vacuum/pressure readings in the Advanced 
Configuration mode before different engineering units can be 
selected.
The default engineering units are mathematically converted to 
the newly selected engineering unit. When the gauge is pow-
ered up, the originally configured range is displayed and then 
the conversion with the selected engineering unit is displayed.
With the gauge powered up, press and hold the UP button. 
Release the button when the engineering units begin to flash. 
Use the UP and DOWN buttons to scroll through the list of engi-
neering units available for the pressure range of the sensor.
When the desired units are displayed, press and release the 
front button to save the selection and return to normal opera-
tion.
Note: The gauge will automatically revert to normal operation if 
no buttons are operated for approximately 15 seconds. 
If done, replace the rear cover, or proceed to the next step.

Auto Shutoff Time Selection

Auto shutoff time selection is done via internal buttons to help 
prevent accidental or unauthorized changes. The selected shut 
off time is stored in non-volatile memory and will be retained 
even with the battery off or batteries removed.
With the gauge powered up, press and hold the DOWN button. 
Release the button when the auto shutoff time is displayed on 
the upper section. 
The lower display will indicate 

AST M

 if the time displayed is 

in minutes, and 

AST H 

if it in hours. 

An auto shutoff time of 0 signifies that the auto shutoff feature 
is disabled and the front button turns the gauge on and off.
Use the UP and DOWN buttons to select 0, 1, 2, 5, 10, 15, 20 
or 30 minutes, or 1, 2, 4, or 8 hours.
When the desired time is displayed, press and release the front 
button to save the selection and return to normal operation.
Note: The gauge will automatically revert to normal operation if 
no buttons are operated for approximately 15 seconds.
Move the switch on the circuit board to the DISABLE position 
and replace the rear cover including the rubber gasket.

User Configuration

Factory/User Configuration

This gives the choice of resetting the gauge features to the 
factory settings or continuing with user configuration. 
The upper display section will be blank, and the lower section 
will display either 

USER_

 or 

FCTRY

.

If 

FCTRY

 is selected, the existing user configuration will be 

replaced by the original factory configuration. 
To select 

FCTRY

, press and release the UP button.

With 

FCTRY

 displayed press and release the front button to 

restore the factory configuration and restart the gauge.
If 

USER_

 is selected, the user configuration can be modified 

as described in the following steps. 
To select 

USER_

, press and release the DOWN button. 

With 

USER_

 displayed press and release the front center 

button to continue.
The configuration parameters vary depending on the model. Go 
to the appropriate section for your gauge.

M0, M2 Max/Min Configuration

Use the UP and DOWN buttons to select from the following:

MX/MN

  Both highest and lowest values will be captured

MX/--

 

Only highest value will be captured

--/MN

  Only lowest value will be captured

--/--

 

Capture feature is disabled

Press and release the front button to move to the next param-
eter.

M0, M2 Max/Min Memory

The upper display section will indicate 

c l r

 .

Use the UP and DOWN buttons to select from the following:

AUTO

  Automatically clear max. and min. values when the 

 

gauge is powered off

MAN

  Manually clear max. and min. values

Press and release the front button to move to the next param-
eter.

M1 Peak Reading Gauge

You can select whether to retain maximum captured values 
at power off. 
The upper display section will indicate 

c l r 

.

Use the UP and DOWN buttons to select from the following:

AUTO

  Automatically clear the maximum stored value when  

 

the gauge is powered off

MAN

 Save 

the maximum stored value when the gauge is  

 

powered off. It must be cleared manually.

Press and release the front button to move to the next param-
eter.

Gauge Type Configuration

This will only appear with 15, 100, or 200 psig ranges that 
were originally ordered as compound gauges. 
Use the UP and DOWN buttons to select from the following:

-/+EU

  Vacuum is indicated as negative pressure in the 

 

selected engineering units

CMPND

  Vacuum is negative INHG, pressure is PSIG. This setting 

 

will disable engineering unit selection.

Press and release the front button to save the user configura-
tion and restart the gauge. 
This completes the configuration for this model. Move the 
switch on the circuit board to the DISABLE position and replace 
the rear cover including the rubber gasket.

Enable/
Disable 

Switch

Internal Up/Down Buttons

cecomp.com

1220 American Way Libertyville, IL 60048 

800-942-0315

CECOMP

 

Div. of

 

A

BSOLUTE

 P

ROCESS

 I

NSTRUMENTS

Содержание Cecomp DPG2000B Series

Страница 1: ... 01 100 psig Res 1150FTH2O 1 5PSIG 001 1000MBARG 1 200KPAG 1 100PSIG 1 3500KPAG 1 10INHGG 01 1000CMH2OG 1 0 2MPAG 0001 200INHGG 1 3 5MPAG 001 140INH2OG 1 35FTH2O 01 2BARG 001 2770INH2OG 1 35BARG 01 80ZING 1 100KPAG 1 2KGCMG 001 1600ZING 1 35KGCMG 01 350GCMG 1 0 1MPAG 0001 2ATMG 001 7000GCMG 1 35ATMG 01 260MMHGG 1 1BARG 001 60 psig Res 5200MMHGG 1 1000 psig Res 260TORRG 1 1KGCMG 001 60PSIG 01 5200T...

Страница 2: ...nd then release the but ton Both maximum and minimum values are cleared and the gauge returns to the normal operating mode M0 Models are configured with minimum and maximum func tions disabled One or both can be enabled or disabled in the User Configuration mode M1 Models are peak reading gauges that only display and captures maximum readings Press and hold the button for about 1 second until MAX ...

Страница 3: ...vent accidental or unauthorized changes The selected shut off time is stored in non volatile memory and will be retained even with the battery off or batteries removed With the gauge powered up press and hold the DOWN button Release the button when the auto shutoff time is displayed on the upper section The lower display will indicate AST M if the time displayed is in minutes and AST H if it in ho...

Страница 4: ...sure signal It may take more than one of these small changes to result in a single digit change on the display To make larger changes press and hold the appropriate UP or DOWN button After about one second the display will begin to change continuously Release the button to stop Then make fine adjustments by pressing and quickly releasing the appropriate button Gauge Reference Pressure Gauges Apply...

Отзывы: