AC to DC Transmitters, Isolated, Field Rangeable 

API 6380 G Series

Input:

 

0-50 mVAC to 0-250 VAC, 0-5 mAAC to 0-200 mAAC

Output:

 

0-1 VDC to ±10 VDC, 0-2 mADC to 0-20 mADC

 

O

One Minute Setup for Hundreds of I/O Ranges

 

O

External Switches & Tables for Range Selection

 

O

Non-Interactive Zero and Span Calibration

 

O

Full 2000 V Input/Output/Power Isolation

 

O

Input and Output LoopTracker

®

 LEDs

 

O

Output Test Button

 

O

Built-In Loop Power Supply for mA Output

 

Q

Convert AC Signals to DC Process Signals

 

Q

Monitor Line Voltage or Current Levels

 

Q

Isolate and Convert AC Signals for Panel Meters, PLCs, 
Recorders, Data Acquisition, DCS, & SCADA Systems

Applications

Model

Input

Output

Module Power

API 6380 G

Field configurable 

0-50 mVAC to 0-250 VAC 

0-5 mAAC to 0-200 mAAC

Field configurable  

0-1 VDC to 0-10 VDC 

±1 VDC to ±10 VDC 

0-2 mADC to 0-20 mADC

115 VAC

API 6380 G A230

230 VAC

API 6380 G P

85-265 VAC or 60-300 VDC

API 6380 G D

9-30 VDC

API 6380 G S

Field configurable  

True RMS input measurement 

0-50 mVAC to 0-250 VAC 

0-5 mAAC to 0-200 mAAC

Field configurable  

0-1 VDC to 0-10 VDC 

±1 VDC to ±10 VDC 

0-2 mADC to 0-20 mADC

115 VAC

API 6380 G A230 S

230 VAC

API 6380 G P S

85-265 VAC or 60-300 VDC

API 6380 G D S

9-30 VDC

Description

The API 6380 G accepts an AC voltage or current input and pro-
vides an optically isolated DC voltage or current output that is 
linearly related to the input. Accuracy is maintained over a wide 
frequency range for maximum flexibility. A true RMS model API 
6380 G S is available for distorted AC inputs. 
The full 3-way (input, output, power) isolation makes this mod-
ule useful for ground loop elimination, common mode signal 
rejection or noise pickup reduction. 
20 input and 16 output ranges can be field-configured via 
external rotary and slide switches. Popular ranges are listed 
on the module label. Consult the factory for assistance with 
special ranges. 

LoopTracker 

API exclusive features include two LoopTracker LEDs (green for 
input, red for output) that vary in intensity with changes in the 
process input and output signals. These provide a quick visual 
picture of your process loop at all times and can greatly aid in 
saving time during initial startup and/or troubleshooting. 

Output Test 

An API exclusive feature includes the test button to provide a 
fixed output (independent of the input) when held depressed. 
The test output level is potentiometer adjustable from 0 to 
100% of output span. 
The output test button greatly aids in saving time during initial 
startup and/or troubleshooting.

AC Input Ranges

Field selectable ranges via switch settings
System voltages must not exceed socket voltage rating
Voltage: 

0-50 mVAC 

to  0-250 VAC 

Current: 

0-5 mAAC 

to  0-200 mAAC 

S

 option: 

True RMS input measurement

See 

API 6380 G 5A

 for current input ranges up to 0-5 AAC

Input Impedance

Voltage (0-4 VAC):  1 M

 minimum 

Voltage (>4 VAC):  220 k

 minimum 

Current: 10 

 typical

Input Frequency

40 Hz to 1000 Hz sinusoidal

Input Protection, Common Mode

750 VDC or 750 VACp

LoopTracker

Variable brightness LEDs indicate I/O loop level and status

DC Output Ranges

Field selectable ranges via switch settings
Voltage: 

0-1 VDC 

to  0-10 VDC 

Bipolar Voltage: 

±1 VDC 

to  ±10 VDC 

Current: 

0-2 mADC 

to  0-20 mADC 

 

20 V compliance, 1000 

 at 20 mA

Output Logic

Normal acting, internal jumper for output reversal

Output Calibration

Multi-turn zero and span potentiometers for output 
±15% of span adjustment range typical

Output Loop Power Supply

20 VDC nominal, regulated, 25 mADC, max. ripple <10 mV

RMS

Output Test

Front button sets output to test level when pressed 
Potentiometer adjustable 0-100% of span

Output Ripple and Noise

Less than 10 mV

RMS

Linearity

Better than ±0.1% of span

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 

Better than ±0.02% of span per °C stability

Response Time

200 milliseconds typical (0-90%)

Isolation

2000 V

RMS

 minimum 

Full isolation: power to input, power to output, input to output

Installation Environment

IP 40, requires installation in panel or enclosure 
Use with API 008 or API 008 FS socket 
Socket mounts to 35 mm DIN rail or can be surface mounted 
UL 508C pollution degree 2 environments or better

Power

Standard: 

115 VAC ±10%, 50/60 Hz, 2.5 W max. 

P option: 

85-265 VAC 50/60 Hz, 60-300 VDC, 2.5 W  

A230 option:  230 VAC ±10%, 50/60 Hz, 2.5 W max. 
D option: 

9-30 VDC, 2.5 W typical

Free Factory 

I/O Setup!

Quick Link 

api-usa.com/6380

Minute 

Setup!

1

Free Factory Setup 

Specify I/O ranges if factory is to set switches 

Option—add to end of model number
U

 

Conformal coating for moisture resistance

Accessories—order as a separate line item
API 008

 

8-pin socket, DIN rail or surface mount 

API 008 FS

 8-pin finger safe socket, DIN rail or surface mount 

API CLP1

  Module hold-down spring for high vibration or  

 

mobile applications

API 008 

600 V Rating

API 008 FS 

300 V Rating

API CLP1

Socket Sold 

Separately

2.75"

Hot Swappable 

Plug-In Design

2.38"

1.75"

Variable Brightness 

Input LED

Output Test Button

Output Test Adjust

Output Span

Output Zero
Variable Brightness 

Output LED

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

Made in USA

E145968

115 VAC, 230 VAC models 

with input up to 150 VAC

© 08-19

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502