AC to DC Transmitters, Isolated, Field Rangeable
APD 6380
Input:
True RMS 0-40 mVAC to 0-300 VAC, 0-4 mAAC to 0-200 mAAC
Output:
0-1 V to 0-10 VDC, ±5 VDC, ±10 VDC, 0-2 mA to 20 mADC
O
One Minute Setup for Hundreds of I/O Ranges
O
External Switches & Tables for Range Selection
O
Zero and Span Output Calibration Potentiometers
O
Full 1200 V Input/Output/Power Isolation
O
Input and Output LoopTracker
®
LEDs
O
Output Test Button
O
Built-In Loop Power Supply for Sink/Source Output
Q
Convert, Boost, and Rescale Process Signals
Q
Isolate Single-Ended (Common Ground) PLC Inputs
Q
Interface Process Signals with Panel Meters, PLCs,
Recorders, Data Acquisition, DCS, & SCADA Systems
Applications
Options–add to end of model number
M01
Output reversal, such as 20-4 mA output
U
Conformal coating for moisture resistance
Accessory—order as separate line item
API BP4
Spare removable 4 terminal plug, black
Model
Input
Output
Power
APD 6380
Field configurable—specify range if
factory is to set switches
Field configurable—specify range if
factory is to set switches
85-265 VAC or 60-300 VDC
APD 6380 D
9-30 VDC or 10-32 VAC
Description
The APD 6380 accepts an AC voltage or current input and
provides an optically isolated DC voltage or current output that
is linearly related to the input.
Typical applications include signal isolation, conversion, boost-
ing or a combination of the three. Full 3-way isolation (input,
output, power) makes this module useful for ground loop
elimination, common mode signal rejection or noise pickup
reduction.
Sink/Source Output Versatility
For maximum versatility a milliamp output can be selectively
wired for sinking or sourcing. This allows the APD 6380 mil-
liamp output to connect to a powered or unpowered current
loop. The 20 VDC output loop supply can be used to power a
passive mA device if required.
LoopTracker
API exclusive features include two LoopTracker LEDs (green for
input, red for output) that vary in intensity with changes in the
process input and output signals. These provide a quick visual
picture of your process loop at all times and can greatly aid in
saving time during initial startup and/or troubleshooting.
Output Test
An API exclusive feature includes the test button to provide a
fixed output (independent of the input) when held depressed.
The test output level is potentiometer adjustable from 0 to
100% of output span.
The output test button greatly aids in saving time during initial
startup and/or troubleshooting.
All models are field rangeable
For APD 6380, specify if UL version is required
Order options and accessories as required
Order D versions for operation on low voltage power
How to Order
Free factory setup. Please specify on your order
Input range
Output range
AC Input Ranges
Field selectable ranges via switch settings
Voltage:
0-40 mVAC to 0-300 VAC
Current:
0-4 mAAC to 0-200 mAAC
Measurements are true RMS
Input Impedance
Voltage (0-4 VAC): 1 M
Ω
minimum
Voltage (>4 VAC): 220 k
Ω
minimum
Current: 10
Ω
typical
Input Frequency
40 Hz to 1000 Hz sinusoidal
Common Mode Rejection
120 dB minimum
LoopTracker
Variable brightness LEDs indicate I/O loop level and status
DC Output Ranges
Field selectable ranges via switch settings
Voltage:
0-1 VDC to 0-10 VDC, 10 mA max
Bipolar voltage: ±1 VDC to ±10 VDC
Current:
0-2 mADC to 0-20 mADC
20 V compliance, 1000
Ω
at 20 mA
Output offset:
±100% in 15% increments
Output Calibration
Multi-turn zero and span potentiometers
±15% of span adjustment range typical
Output Loop Power Supply
20 VDC nominal, regulated, 25 mADC
Max. ripple, less than 10 mV
RMS
May be selectively wired for sinking or sourcing mA output
Output Test
Front momentary button sets output to test level
Potentiometer adjustable 0-100% of span
Output Ripple and Noise
Less than 10 mV
RMS
ripple and noise
Linearity
Better than ±0.1% of span
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.02% of span per °C stability
Response Time
200 milliseconds nominal (0-90%)
Isolation
1200 V
RMS
minimum
Full isolation: power to input, power to output, input to output
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
Dimensions
0.89" W x 4.62" H x 4.81" D
22.5 mm W x 117 mm H x 122 mm D
Height includes connectors
Connect mA Output
for Sink or Source
Output LoopTracker
LED
Input LoopTracker
LED
Adjustable Output
Test Function
Hundreds of Range
Selections
Adjustable Output
Offset
Universal
Power
Zero and Span for
Output
Removable Plugs
© 11-19
api-usa.com
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
A
A
BSOLUTE
BSOLUTE
P
P
ROCESS
ROCESS
I
I
NSTRUMENTS
NSTRUMENTS
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
See Wiring
Diagrams on
Page 3
Quick Link:
api-usa.com/6380
Minute
Setup!
1
Free Factory
I/O Setup!
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
File E145968
85-265 VAC, 60-300 VDC
model only
Applications Link
api-usa.com/apps
Pb
Lead
Free