AC to DC Transmitters, Isolated, Factory Configured
APD 6010
Input:
True RMS 0-50 mVAC to 0-300 VAC, 0-1 mAAC to 0-1000 mAAC
Output:
0-1 V to 0-10 VDC, ±5 VDC, ±10 VDC, 0-1 mA to 0-20 mADC, 4-20 mADC
O
Full 1200 V Input/Output/Power Isolation
O
Zero and Span Output Calibration Potentiometers
O
Input and Output LoopTracker
®
LEDs
O
Functional Test Button with Remote Capability
O
Built-In Loop Power Supply for Sink/Source Output
Q
Convert an AC Signal to a DC Process Signal
Q
Monitor Voltage Ranges
Q
Convert, Amplify Low Level AC Signals
Applications
Options–add to end of model number
M01
Output reversal, such as 20-4 mA output
M09
High voltage output up to 20 V (specify range)
U
Conformal coating for moisture resistance
Accessory—order as separate line item
API BP4
Spare removable 4 terminal plug, black
Model
Input
Output
Power
APD 6010
Factory configured—specify
mVAC, VAC, or mAAC range
Factory configured—specify
VDC or mADC range
85-265 VAC or 60-300 VDC
APD 6010 D
9-30 VDC or 10-32 VAC
Description
The APD 6010 accepts an AC voltage or current input and
provides an optically isolated DC voltage or current output
that is linearly related to the input. Typical applications include
monitoring line, power supply, shunt, and motor voltages or
current (either directly or with a current transducer) for control,
preventive maintenance, etc.
The full 3-way (input, output, power) isolation makes this mod-
ule useful for ground loop elimination or noise pickup reduc-
tion. The APD 6010 is factory configured to customer require-
ments. Consult the factory for assistance with special ranges.
Sink/Source Output Versatility
For maximum versatility a milliamp output can be selectively
wired for sinking or sourcing. This allows the APD 6010 mil-
liamp output to connect to a powered or unpowered current
loop. The 20 VDC output loop supply can be used to power a
passive mA device if required.
LoopTracker
API exclusive features include two LoopTracker LEDs (green for
input, red for output) that vary in intensity with changes in the
process input and output signals. These provide a quick visual
picture of your process loop at all times and can greatly aid in
saving time during initial startup and/or troubleshooting.
Functional Test
An API exclusive feature includes the Functional Test Button
to provide a fixed output (independent of the input) when held
depressed. The test output level is potentiometer adjustable
from 0 to 100% of output span. The functional test button
greatly aids in saving time during initial startup and/or trouble-
shooting.
The functional test can also be enabled with a customer-
supplied external contact closure across terminals 5 and 6.
This allows remote testing of the output or, for example, a
PLC-controlled manual override setting.
All models are factory ranged. Please specify
Model APD 6010 or
APD 6010 D for operation on low voltage power
Order options and accessories as required
How to Order
I/O are factory set to your specifications. Please provide
Input range
Output range
Options as required
AC Input Range
Factory configured, please specify input range
Consult factory for special ranges
Voltage:
0-50 mVAC to 0-300 VAC
Current:
0-1 mAAC to 0-1000 mAAC
Measurements are true RMS
Input Impedance (Voltage Input)
220 k
Ω
minimum
Input Voltage Burden (Current Input)
1.0 V
RMS
maximum
Input Frequency
40 Hz to 1000 Hz sinusoidal
Input Protection, Common Mode
750 VDC or 750 VAC
p
Common Mode Rejection
120 dB minimum
LoopTracker
Variable brightness LEDs indicate I/O loop level and status
DC Output Ranges
Factory configured, please specify input range
Consult factory for special ranges
Voltage:
0-1 VDC to 0-10 VDC, 10 mA max
Voltage,
M09
option: 0-10 VDC to 0-20 VDC
Bipolar voltage:
±1 VDC
to ±10 VDC
Current:
0-1 mADC to 0-20 mADC
20 V compliance, 1000
Ω
at 20 mA
Output Calibration
Multi-turn zero and span potentiometers
±15% of span adjustment range typical
Output Loop Power Supply
20 VDC nominal, regulated, 25 mADC
Max. ripple, less than 10 mV
RM
S
May be selectively wired for sinking or sourcing mA output
Output Test/Override
Front momentary button or external contact closure sets out-
put to test level. Potentiometer adjustable 0-100% of span.
Output Ripple and Noise
Less than 10 mV
RMS
at 40 Hz and above
Linearity
Better than ±0.1% of span
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.02% of span per °C stability
Response Time
150 milliseconds nominal (0-90%)
Isolation
1200 V
RMS
minimum
Full isolation: power to input, power to output, input to output
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum
Dimensions
0.89" W x 4.62" H x 4.81" D
22.5 mm W x 117 mm H x 122 mm D
Height includes connectors
Connect mA Output
for Sink or Source
Output LoopTracker
LED
Input LoopTracker
LED
Custom Input
Ranges
Universal
Power
Zero and Span for
Output
Removable Plugs
Adjustable Output
Test/Override
Function
Custom Output
Ranges
© 11-19
api-usa.com
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
A
A
BSOLUTE
BSOLUTE
P
P
ROCESS
ROCESS
I
I
NSTRUMENTS
NSTRUMENTS
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
See Wiring
Diagrams on
Next Page
Quick Link:
api-usa.com/6010
Free Factory
I/O Setup!
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
File E145968
85-265 VAC, 60-300 VDC
model only
Applications Link
api-usa.com/apps
Pb
Lead
Free