Strain Gauge/Bridge/Load Cell/Pressure Transducer to DC Transmitters, Field Rangeable 

APD 4059

Input: 

100 

 to 10,000 

 Bridges, 0.5 mV/V to 40 mV/V, 1-10 VDC Excitation

Output: 

0-1 V to ±10 V or 0-2 mA to 4-20 mA (Sink or Source)

 

O

Drive up to Four 350 

 Bridges

 

O

Adjustable Excitation Power Supply 

 

O

Sense Lead Compensation

 

O

One Minute Setup for Hundreds of I/O Ranges

 

O

Removable Plugs for Faster Installation

 

O

Non-Interactive Zero and Span

 

O

Full 3-Way Input/Output/Power Isolation

 

O

Input and Output LoopTracker

®

 LEDs

 

O

Output Test or Calibration Resistor Options

Applications

Options—add to end of model number

M01

 

Switch with built-in calibration resistor.  

 

Specify resistor value.

M02

 

Switch for external calibration resistor

DF

 

Special response time. Add DF to model number  

 

followed by value in milliseconds (10 to 5000)

Option—add to end of model number

U

 

Conformal coating for moisture resistance

Accessories—order as separately

SG-EQ4

 

Junction/sum board 

SG-EQ4-BOXPG7

  Junction/sum box 

Trim pots for up to 4 strain gauges.  

For 4-wire or 6-wire load cells.

API BP4

  Spare 4 terminal plug, black

Model

Input

Output

Power

APD 4059

Field configurable. Specify the following if 

factory is to set switches 

Bridge mV/V or mV range 

Excitation voltage

Field configurable. Specify follow-

ing if factory is to set switches 

Output range 

Output type (V or mA)

85-265 VAC or 60-300 VDC

APD 4059 D

9-30 VDC or 10-32 VAC

Description

The APD 4059 accepts an input from one to four strain gauges, 
bridge type sensors, load cells, or pressure transducers. It 
filters, amplifies, and converts the resulting millivolt signal 
into the selected DC voltage or current output that is linearly 
related to the input.
The full 3-way (input, output, power) isolation makes this mod-
ule useful for ground loop elimination, common mode signal 
rejection or noise pickup reduction.
The adjustable excitation power supply generates a stable 
source of voltage to drive from one to four 350 

 (or greater) 

devices. Sense lead circuitry is included to cancel the effects 
of leadwire resistance, if required.
Input, output, excitation and zero offset are field configurable, 
via external rotary and slide switches. Offsets up to ±100% 
of span can be used to cancel sensor offsets or non-zero 
deadweights (taring). Non-interactive zero and span simplifies 
calibration.

Sink/Source Versatility

For maximum versatility the APD 4059 milliamp output can be 
selectively wired for sinking or sourcing. This allows connec-
tion to any type of mA input receiving device.

LoopTracker

API exclusive features include two LoopTracker LEDs (green for 
input, red for output) that vary in intensity with changes in the 
process input and output signals. These provide a quick visual 
picture of your process loop at all times and can greatly aid in 
saving time during initial startup and/or troubleshooting. 

Output Test

An API exclusive feature includes the test button to provide a 
fixed output (independent of the input) when held depressed. 
The output test button greatly aids in saving time during initial 
startup and/or troubleshooting. The test output level is potenti-
ometer adjustable from 0 to 100% of output span.
The output test is not available with the M01 or M02 options. A 
calibration resistor switch replaces the test button.

Housing and Connectors

IP 40, requires installation in panel or enclosure 

For use in Pollution Degree 2 Environment 

Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors 

14 AWG max wire size 

Dimensions

0.89" W x 4.62" H x 4.81" D   

22.5 mm W x 117 mm H x 122 mm D  

Height includes connectors

Power

Standard:  85-265 VAC, 50/60 Hz or 60-300 VDC 

D

 option: 

9-30 VDC (either polarity) or 10-32 VAC

Power:  

2 to 5 Watts depending on number of load cells

Strain Gauge Input Ranges

100 

Ω 

to 10,000 

Ω 

bridges at 10 VDC 

Up to four 350 

 bridges at 10 VDC

Minimum: 

0 to 5 mV range 

0.5 mV/V sensitivity 

Maximum: 

0 to 400 mV range  40 mV/V sensitivity

Millivolt output range is determined by the sensor sensitivity 

(mV/V) and the excitation voltage:  

mV/V sensitivity  X  excitation voltage  =  total mV range

Input Impedance

200 k

 typical

Common Mode Rejection

100 dB minimum

Calibration Resistor Options

M01 option:  Switch with calibration resistor inside module.  

 

Specify resistor value. 

M02 option:  Switch for external (load cell) calibration resistor.

Excitation Voltage

Switch Selectable:  0-10 VDC in 1 V increments 

Maximum Output:  10 VDC maximum at 120 mA 

Drive Capability: 

Up to four 350 

 bridges at 10 VDC 

Fine Adjustment: 

±5% via multi-turn potentiometer 

Stability: 

±0.01% per °C

Sense Lead Compensation

Better than ±0.01% per 1 

 change in leadwire resistance 

Maximum leadwire resistance: 10 

 with 350 

 at 10 VDC

LoopTracker

Variable brightness LEDs for input/output loop level and status

DC Output Ranges

Voltage (10 mA max.): 

0-1 VDC 

to  0-10 VDC 

Bipolar Voltage (±10 mA max.):  ±5 VDC 

or  ±10 VDC 

Current: 

0-2 mADC  to  0-20 mADC 

Compliance, drive at 20 mA: 

20 V, 1000 

 drive 

Current output can be selectively wired for sink or source

Output Calibration

Multi-turn zero and span potentiometers 

±15% of span adjustment range typical

Zero offset switch:  ±100% of span in 15% increments

Output Test

Sets output to test level when pressed 

Adjustable 0-100% of span 

Not available with M01 or M02 options

Output Ripple and Noise

Less than 10 mV

RMS

 ripple and noise

Linearity

Better than ±0.1% of span

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 

Better than ±0.02% of span per °C stability, nominal

Response Time

Nominal time at 63.2% of step change 

Standard: 70 milliseconds (14.3 Hz) 

DF option: Special response time, DF10 (10 milliseconds 

or 100 Hz) up to DF5000 (5 seconds). Faster than standard 

response times will cause output noise levels to be greater 

than standard specifications. Contact factory for assistance.

Isolation

1200 V

RMS

 min. 

Full isolation: power to input, power to output, input to output

 

Q

Load Cell Weighing Systems and Scales

 

Q

Strain Gauge Pressure Sensors and Transducers

 

Q

Tanks, Scales, Extruder Melt Pressure, Crane Loads

Universal Power

Removable Plugs

Minute 

Setup!

1

Free Factory 

I/O Setup!

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

Made in USA

File E145968

85-265 VAC, 60-300 VDC 

model only

Output LoopTracker 

LED

Input LoopTracker 

LED

Test Switch for 

Calibration Resistor

Connect mA Output 

for Sink or Source

Hundreds of Range 

Selections

Internal/External 

Calibration Resistor 

Options

Zero and Span for 

Output

Connect up to 4 

Load Cells

1  2  3  4

5  6  7  8

9 10 11 12

13 14 15 16

See Wiring 

Diagrams on 

Page 3

© 05-20

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

Quick Link: 

api-usa.com/4059

Applications Link 

api-usa.com/apps

Pb

Lead 

Free

Содержание APD 4059 Series

Страница 1: ...ors IP 40 requires installation in panel or enclosure For use in Pollution Degree 2 Environment Mount vertically to a 35 mm DIN rail Four 4 terminal removable connectors 14 AWG max wire size Dimensions 0 89 W x 4 62 H x 4 81 D 22 5 mm W x 117 mm H x 122 mm D Height includes connectors Power Standard 85 265 VAC 50 60 Hz or 60 300 VDC D option 9 30 VDC either polarity or 10 32 VAC Power 2 to 5 Watts...

Страница 2: ...only purpose is to adjust or cancel effects of the low end of the input range not corresponding nominally to 0 mV Setting this switch to 0 results in no offset 2 To RAISE the output zero rotate switch C from 1 thru 7 until the Zero control can be set for your application 3 To LOWER the output zero rotate switch C from 9 thru F until the Zero control can be set for your application 4 If switch posi...

Страница 3: ... 11 Cu 60 75 C conductors 14 AWG max Mounting to a DIN Rail Install module vertically on a 35 mm DIN rail in a protective enclosure away from heat sources Do not block air flow Allow 1 25 mm above and below housing vents for air circulation 1 Tilt front of module downward and position against DIN rail 2 Clip lower mount to bottom edge of DIN rail 3 Push front of module upward until upper mount sna...

Страница 4: ... transducer must be con nected per the manufacturer s specifications The sensor manufacturer should provide the percentage of full scale output for the transducer when using a calibration resistor This is often 80 of maximum output 1 Apply power to the module and allow a minimum 20 minute system warm up time 2 Using an accurate voltmeter across terminals 10 and 12 adjust the Excitation voltage pot...

Отзывы: